Product Details:
Payment & Shipping Terms:
|
1783-US8T is a Stratix 2000 unmanaged switch: it forwards frames and does nothing else — no management, no VLANs, no ring.
Eight copper ports in a DIN rail housing is the classic machine-level fan-out: one uplink and seven devices.
| 1783-BMS20CL | Stratix 5700, 20 ports, 16 copper + 2 combo + 2 SFP | IN STOCK |
| 1783-BMS20CGP | Stratix 5700, 20 ports, gigabit combo | IN STOCK |
| 1783-BMS20CGL | Stratix 5700, 20 ports, gigabit combo, Lite firmware | IN STOCK |
| 1783-BMS20CGPK | Stratix 5700, 20 ports, gigabit combo, kit | IN STOCK |
| 1783-BMS06TA | Stratix 5700, 6 copper ports | IN STOCK |
| 1783-BMS06TL | Stratix 5700, 6 copper ports, Lite firmware | IN STOCK |
| 1783-BMS06TGA | Stratix 5700, 4 copper + 2 gigabit copper | IN STOCK |
| 1783-BMS06SA | Stratix 5700, 4 copper + 2 SFP | IN STOCK |
| 1783-BMS06SL | Stratix 5700, 4 copper + 2 SFP, Lite firmware | IN STOCK |
| 1783-BMS06SGA | Stratix 5700, 4 copper + 2 gigabit SFP | IN STOCK |
| 1783-BMS06SGL | Stratix 5700, 4 copper + 2 gigabit SFP, Lite firmware | IN STOCK |
| 1783-MS06T | Stratix 8000, 6 port chassis | IN STOCK |
| 1783-MS10T | Stratix 8000, 10 port chassis | IN STOCK |
| 1783-RMS06T | Stratix 8300, 6 port layer 3 | IN STOCK |
| 1783-RMS10T | Stratix 8300, 10 port layer 3 | IN STOCK |
| 1783-EMS04T | Stratix 6000, 4 port managed | IN STOCK |
| 1783-MX08T | Stratix 8000 copper 8 port expansion | IN STOCK |
| 1783-MX08F | Stratix 8000 fibre 8 port expansion | IN STOCK |
| 1783-MCF | Stratix 8000 CompactFlash spare card | IN STOCK |
| 1783-RMCF | Stratix 8300 CompactFlash spare card | IN STOCK |
| 1783-ETAP | EtherNet/IP tap, 3 copper ports | IN STOCK |
| 1783-ETAP2F | EtherNet/IP tap, 1 copper + 2 fibre | IN STOCK |
| 1783-SFP100FX | 100FX multimode SFP, 2 km | IN STOCK |
| 1783-SFP100LX | 100LX singlemode SFP, 10 km | IN STOCK |
| 1783-SFP1GSX | 1000SX multimode SFP, 550 m | IN STOCK |
| 1783-SFP1GLX | 1000LX singlemode SFP, 10 km | IN STOCK |
| 1783-US8T | Stratix 2000, 8 copper ports, unmanaged | IN STOCK |
| 1783-US03T01F | Stratix 2000, 3 copper + 1 fibre, unmanaged | IN STOCK |
Catalog number |
1783-US8T |
Description |
Stratix 2000 unmanaged Ethernet switch |
Number of ports |
8 ports |
RJ45 ports |
8 * 10/100 |
SFP slots |
0 |
Combo ports |
0 |
Lifecycle status |
Discontinued June 23, 2025 |
Replacement category |
Functional Replacement |
Replacement product |
1783-USP8T |
Publication |
1783-IN003 |
Same-family catalog numbers: 1783-US03T01F. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1783 family.
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1783-UM011 (module specifications) and Rockwell literature library (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
8 ports; 8 * 10/100 RJ45, 0 SFP slots, 0 combo ports.
An unmanaged switch is chosen because nobody has to own its configuration. That is also its limit: it cannot segment traffic or diagnose a duplicate IP.
Machine-level fan-out where a managed switch would end up unmanaged in practice — several devices in one cabinet sharing a single uplink.
Where the network architecture needs segmentation, this is the wrong device. Put a managed switch at the cell boundary instead.
No IGMP snooping means multicast I/O traffic is flooded to every port. On a small island that is harmless; on a large one it is not.
No diagnostics means a failing link shows up as a stopped machine. Keep a spare — the units are cheap and the diagnosis time is not.
Discontinued June 23, 2025, replacement category Functional Replacement, replacement product 1783-USP8T.
Unmanaged switches are the least visible part of an Ethernet control network and the first part missed in a spares review.
Managed alternatives: Stratix 5700 (1783-BMS…) for cells, Stratix 8000 and 8300 for larger panels.
Taps for device-level rings: 1783-ETAP and 1783-ETAP2F.
On a used unit, count the ports from the front label rather than a photograph. The housings of these two catalog numbers are close in size, and a wrong port count is only discovered when the uplink is plugged in.
How many ports does 1783-US8T have?
8 ports
Is 1783-US8T managed?
No. It is an unmanaged switch.
Is 1783-US8T still available from Rockwell?
No. Discontinued June 23, 2025; replacement category Functional Replacement.
What replaces 1783-US8T?
1783-USP8T
Does 1783-US8T support VLANs?
No. Unmanaged switches have no configuration.
1783-US8T is a Stratix industrial Ethernet switch from the Allen-Bradley range, specified here against the Rockwell technical data rather than a distributor summary, so the port count, the supply range and the temperature ceiling are the figures an integrator can build a cabinet around.
| Specification | Value |
|---|---|
| Series | Stratix 2000 unmanaged, Series B |
| Ports on this model | 8 RJ45 Fast Ethernet ports |
| Power input | 24V nominal, 12 to 48V DC or 18 to 30V AC 50/60 Hz, SELV |
| Power consumption | 3.4 to 10 W across the series, model dependent |
| Inrush current | 0.33 to 1.85 A maximum across the series |
| Wire size, power | 0.25 to 4 mm2 (24 to 12 AWG) twisted pair copper rated 86 degrees C above ambient |
| Screw torque | 0.50 to 0.56 N m on power terminals, 0.91 N m on the ground terminal |
| Ground wire | 2.5 mm2 (14 AWG) copper with a ring terminal |
| Enclosure rating | None, open style |
| Temperature code | T4 to T5 depending on model, ATEX T4 |
| Source | 1783-TD002D-EN-P, May 2023 |
This is the unmanaged member of the family, and its value is that it has no configuration to lose. Eight Fast Ethernet ports, one 24V feed, an open style housing and nothing to restore after a controller swap: in a machine cell handed to a customer who will never see the drawing, that simplicity is the specification.
The supply is the one place this part is more flexible than a managed unit, because it accepts 24V AC as well as 12 to 48V DC. A retrofit into a cabinet that still runs an AC control bus therefore does not need a new power supply, and the current figures make the load easy to add to an existing budget.
Where a value in this table is a range rather than a single figure, it is a range because the Rockwell table publishes it that way across the model group; the individual unit is then fixed by its catalog suffix. Anything an engineer needs beyond this, including the certification file and the full EMC test list, is in the technical data publication named at the bottom of the table.
On 1783-US8T conformal coating is a suffix rather than a separate product, and it matters in washdown or sulfur bearing atmospheres. Where a cabinet sits in a food plant or near a rubber process, the coated variant is the one to quote, because condensation on an uncoated board is a failure that shows up months later.
Commissioning a switch takes an afternoon the first time and twenty minutes afterwards: address it, set the ring or the redundant path, confirm the port counters stay clean under load, and record the firmware revision on the as-built drawing. The failures that survive to production are almost always a duplicate address or a loop nobody documented.
On 1783-US8T the 24V DC input is Class 2 or SELV, which is what allows a cabinet to feed them from the same distribution as the PLC without a separate transformer. Where a site still runs 24V AC, that option exists on the unmanaged range and disappears on the managed ones, and the difference is worth checking before a retrofit order is placed.
Precision time is a separate question from data. IEEE 1588 CIP Sync is what lets a controller timestamp an input at the switch edge rather than at the scanner, and only the Full firmware variants carry it. If an application needs coordinated motion or sequence of events, the Lite part on the shelf will not do the job.
Temperature is quoted at the surrounding air rather than at the board, and the 60 degrees C ceiling on the managed units is lower than the 70 degrees C that the FLEX Ex and most I/O families allow. A cabinet that was designed around an I/O module rating will need a thermal review before a switch is added at the top of the rail.
A switch that has been in a cabinet for eight years is usually still electrically sound and functionally obsolete. The practical question at replacement time is whether the firmware can still be managed by the current tool, and a unit that cannot be reached by the engineering software is a unit that will be replaced on failure rather than on schedule.
A managed switch adds the diagnostics that make a network debuggable: port level counters, spanning tree, and in the Stratix range a Device Level Ring that survives a single cable break. The catalog suffix tells you whether that firmware is present, and a Lite unit is not upgradeable into a Full one by flashing it. For 1783-US8T the suffix is the only reliable statement of which firmware set ships.
Every one of these units, 1783-US8T included, is open style, which means it belongs in an enclosure with a pollution degree 2 environment. The IP30 rating protects against fingers and tools, not against water, and a switch mounted on an open panel in a wet area is a warranty claim waiting to happen.
Cybersecurity hardening starts at the switch, not at the firewall. Disabling unused ports, changing the default credentials, and keeping the management interface off the plant backbone are the three steps that close most findings in an industrial network assessment, and none of them require a licence.
Ethernet ports are rated for Category 5e cable at minimum, and the connector is the IEC 60603-7 RJ45 that every industrial patch cord already uses. Where a cabinet is wired with older Category 5 cable, the link will usually train at 100 Mbps but the error counters will climb, which is why the cable class is printed next to the port table.
For 1783-US8T the NAT variants exist for the machine builder who must hand over a cell with a fixed internal address scheme. A configurable NAT router lets the same internal IP plan be reused on every machine while the plant side sees a different address, which removes an entire class of commissioning arguments.
Spare parts strategy on a switch is driven by firmware, not by hardware. A Lite spare cannot replace a Full unit in a ring that depends on CIP Sync, so the stocking list should carry the suffix rather than the base number, and the label on the failed unit is the authority.
In a plant network the switch, 1783-US8T included, is usually the part that gets blamed last and fails first, because it sits between a drive that trips and a controller that logs nothing. Keeping the port count, the supply range and the temperature rating on the page means a maintenance engineer can replace a unit without opening a drawing set.
Device Level Ring is the reason many of these switches exist in a machine line. A ring built from two ports per device survives one open cable without dropping the cell, and the recovery time is a property of the ring rather than of any single switch, so a mixed vendor ring has to be checked as a whole.
Match the port count to the cell rather than to the catalogue, keep the open style housing inside an enclosure, and put the unmanaged choice on the drawing so that nobody troubleshoots a switch that has no diagnostics to give.
This part sits in the Allen-Bradley 1783 network switches category, with the other models and spare parts listed alongside it.