Product Details:
Payment & Shipping Terms:
|
1783-US03T01F is a Stratix 2000 unmanaged switch: it forwards frames and does nothing else — no management, no VLANs, no ring.
Three copper ports and one fibre port is the smallest sensible way to put a fibre stub in a cabinet without a media converter pair.
| 1783-BMS20CL | Stratix 5700, 20 ports, 16 copper + 2 combo + 2 SFP | IN STOCK |
| 1783-BMS20CGP | Stratix 5700, 20 ports, gigabit combo | IN STOCK |
| 1783-BMS20CGL | Stratix 5700, 20 ports, gigabit combo, Lite firmware | IN STOCK |
| 1783-BMS20CGPK | Stratix 5700, 20 ports, gigabit combo, kit | IN STOCK |
| 1783-BMS06TA | Stratix 5700, 6 copper ports | IN STOCK |
| 1783-BMS06TL | Stratix 5700, 6 copper ports, Lite firmware | IN STOCK |
| 1783-BMS06TGA | Stratix 5700, 4 copper + 2 gigabit copper | IN STOCK |
| 1783-BMS06SA | Stratix 5700, 4 copper + 2 SFP | IN STOCK |
| 1783-BMS06SL | Stratix 5700, 4 copper + 2 SFP, Lite firmware | IN STOCK |
| 1783-BMS06SGA | Stratix 5700, 4 copper + 2 gigabit SFP | IN STOCK |
| 1783-BMS06SGL | Stratix 5700, 4 copper + 2 gigabit SFP, Lite firmware | IN STOCK |
| 1783-MS06T | Stratix 8000, 6 port chassis | IN STOCK |
| 1783-MS10T | Stratix 8000, 10 port chassis | IN STOCK |
| 1783-RMS06T | Stratix 8300, 6 port layer 3 | IN STOCK |
| 1783-RMS10T | Stratix 8300, 10 port layer 3 | IN STOCK |
| 1783-EMS04T | Stratix 6000, 4 port managed | IN STOCK |
| 1783-MX08T | Stratix 8000 copper 8 port expansion | IN STOCK |
| 1783-MX08F | Stratix 8000 fibre 8 port expansion | IN STOCK |
| 1783-MCF | Stratix 8000 CompactFlash spare card | IN STOCK |
| 1783-RMCF | Stratix 8300 CompactFlash spare card | IN STOCK |
| 1783-ETAP | EtherNet/IP tap, 3 copper ports | IN STOCK |
| 1783-ETAP2F | EtherNet/IP tap, 1 copper + 2 fibre | IN STOCK |
| 1783-SFP100FX | 100FX multimode SFP, 2 km | IN STOCK |
| 1783-SFP100LX | 100LX singlemode SFP, 10 km | IN STOCK |
| 1783-SFP1GSX | 1000SX multimode SFP, 550 m | IN STOCK |
| 1783-SFP1GLX | 1000LX singlemode SFP, 10 km | IN STOCK |
| 1783-US8T | Stratix 2000, 8 copper ports, unmanaged | IN STOCK |
| 1783-US03T01F | Stratix 2000, 3 copper + 1 fibre, unmanaged | IN STOCK |
Catalog number |
1783-US03T01F |
Description |
Stratix 2000 unmanaged Ethernet switch |
Number of ports |
3 copper ports plus 1 fibre port |
RJ45 ports |
3 * 10/100 |
SFP slots |
1 fibre |
Combo ports |
0 |
Lifecycle status |
Discontinued August 28, 2014 |
Replacement category |
Direct Replacement |
Replacement product |
Published as Direct Replacement |
Publication |
1783-IN003 |
Same-family catalog numbers: 1783-US8T. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1783 family.
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1783-UM011 (module specifications) and Rockwell literature library (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
3 copper ports plus 1 fibre port; 3 * 10/100 RJ45, 1 fibre SFP slots, 0 combo ports.
An unmanaged switch is chosen because nobody has to own its configuration. That is also its limit: it cannot segment traffic or diagnose a duplicate IP.
Machine-level fan-out where a managed switch would end up unmanaged in practice — several devices in one cabinet sharing a single uplink.
Where the network architecture needs segmentation, this is the wrong device. Put a managed switch at the cell boundary instead.
No IGMP snooping means multicast I/O traffic is flooded to every port. On a small island that is harmless; on a large one it is not.
No diagnostics means a failing link shows up as a stopped machine. Keep a spare — the units are cheap and the diagnosis time is not.
Discontinued August 28, 2014, replacement category Direct Replacement, replacement product Published as Direct Replacement.
Unmanaged switches are the least visible part of an Ethernet control network and the first part missed in a spares review.
Managed alternatives: Stratix 5700 (1783-BMS…) for cells, Stratix 8000 and 8300 for larger panels.
Taps for device-level rings: 1783-ETAP and 1783-ETAP2F.
On a used unit, count the ports from the front label rather than a photograph. The housings of these two catalog numbers are close in size, and a wrong port count is only discovered when the uplink is plugged in.
How many ports does 1783-US03T01F have?
3 copper ports plus 1 fibre port
Is 1783-US03T01F managed?
No. It is an unmanaged switch.
Is 1783-US03T01F still available from Rockwell?
No. Discontinued August 28, 2014; replacement category Direct Replacement.
What replaces 1783-US03T01F?
Published as Direct Replacement
Does 1783-US03T01F support VLANs?
No. Unmanaged switches have no configuration.
1783-US03T01F is part of the Allen-Bradley Stratix industrial Ethernet range, described here from the Rockwell technical data and installation instructions so that the supply, the isolation and the temperature limits on the page are the ones an integrator can actually design against.
| Specification | Value |
|---|---|
| Ports | 3 copper ports plus 1 fiber port, autonegotiating 10 or 100 Mbps |
| Fiber data rate | 100 Mbps, full duplex |
| Fiber wavelength | 1310 nm |
| Fiber cable | Graded index multimode fiber |
| Configuration | This is the port combination illustrated in the Stratix 2000 installation instructions |
| Series features | Unmanaged, no configuration, automatic cable crossover detection, broadcast storm protection |
| Supply | Dual power inputs, 24V DC or 20V AC nominal depending on the installation |
| Enclosure and rating | Rugged metal housing with an IP30 rating |
| Temperature | Extended range on select versions, from -40 to 75 degrees C |
| Role | Three local copper devices plus one fiber uplink, the shape a remote enclosure usually needs |
| Source | Stratix 2000 installation instructions and publication ENET-PP010 |
The three plus one shape is the one a remote enclosure usually asks for: a drive, an I/O head and an HMI on copper, and a single fiber strand back to the main cabinet. It is an unmanaged part, so there is nothing to configure and nothing to restore, which is exactly what a maintenance team wants at the end of a line.
The fiber port is 100 Mbps full duplex at 1310 nm over graded index multimode, so the distance is a property of the cable and the connectors rather than of a specification sheet headline. Where the run is longer than a few hundred meters, the fiber tap and switch options in the managed range are the parts to price instead of stretching this one.
Two attributes in the table decide more installations than the port count does: the supply range, because a 24V nominal device with a 20.4V lower limit behaves differently from one that accepts 12V, and the surrounding air limit, because a switch rated at 60 degrees C in a cabinet designed for 70 degrees C is a thermal problem rather than a network problem.
On 1783-US03T01F the 24V DC input is Class 2 or SELV, which is what allows a cabinet to feed them from the same distribution as the PLC without a separate transformer. Where a site still runs 24V AC, that option exists on the unmanaged range and disappears on the managed ones, and the difference is worth checking before a retrofit order is placed.
Precision time is a separate question from data. IEEE 1588 CIP Sync is what lets a controller timestamp an input at the switch edge rather than at the scanner, and only the Full firmware variants carry it. If an application needs coordinated motion or sequence of events, the Lite part on the shelf will not do the job.
Temperature is quoted at the surrounding air rather than at the board, and the 60 degrees C ceiling on the managed units is lower than the 70 degrees C that the FLEX Ex and most I/O families allow. A cabinet that was designed around an I/O module rating will need a thermal review before a switch is added at the top of the rail.
A switch that has been in a cabinet for eight years, 1783-US03T01F among them, is usually still electrically sound and functionally obsolete. The practical question at replacement time is whether the firmware can still be managed by the current tool, and a unit that cannot be reached by the engineering software is a unit that will be replaced on failure rather than on schedule.
A managed switch adds the diagnostics that make a network debuggable: port level counters, spanning tree, and in the Stratix range a Device Level Ring that survives a single cable break. The catalog suffix tells you whether that firmware is present, and a Lite unit is not upgradeable into a Full one by flashing it. For 1783-US03T01F the suffix is the only reliable statement of which firmware set ships.
Every one of these units, 1783-US03T01F included, is open style, which means it belongs in an enclosure with a pollution degree 2 environment. The IP30 rating protects against fingers and tools, not against water, and a switch mounted on an open panel in a wet area is a warranty claim waiting to happen.
Cybersecurity hardening starts at the switch, not at the firewall. Disabling unused ports, changing the default credentials, and keeping the management interface off the plant backbone are the three steps that close most findings in an industrial network assessment, and none of them require a licence.
Ethernet ports are rated for Category 5e cable at minimum, and the connector is the IEC 60603-7 RJ45 that every industrial patch cord already uses. Where a cabinet is wired with older Category 5 cable, the link will usually train at 100 Mbps but the error counters will climb, which is why the cable class is printed next to the port table.
For 1783-US03T01F the NAT variants exist for the machine builder who must hand over a cell with a fixed internal address scheme. A configurable NAT router lets the same internal IP plan be reused on every machine while the plant side sees a different address, which removes an entire class of commissioning arguments.
Spare parts strategy on a switch is driven by firmware, not by hardware. A Lite spare cannot replace a Full unit in a ring that depends on CIP Sync, so the stocking list should carry the suffix rather than the base number, and the label on the failed unit is the authority.
In a plant network the switch, 1783-US03T01F included, is usually the part that gets blamed last and fails first, because it sits between a drive that trips and a controller that logs nothing. Keeping the port count, the supply range and the temperature rating on the page means a maintenance engineer can replace a unit without opening a drawing set.
Device Level Ring is the reason many of these switches exist in a machine line. A ring built from two ports per device survives one open cable without dropping the cell, and the recovery time is a property of the ring rather than of any single switch, so a mixed vendor ring has to be checked as a whole.
The emission class is CISPR 11 Class A, which is an industrial environment statement. Mounting one of these in a light industrial or residential panel can require additional filtering, and that is a compliance question rather than a performance one, so it belongs in the quotation stage.
The distance an SFP reaches is a property of the optic and the fiber, not of the switch. Multimode runs to a few hundred meters, singlemode runs to kilometers, and the budget has to cover connectors and splices, so the link loss calculation belongs in the same document as the port list.
Match the fiber port to the uplink media, keep the unmanaged choice on the drawing so nobody expects diagnostics it cannot give, and confirm the extended temperature version on the label before a cold store installation.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley 1783 network switches category.