Product Details:
Payment & Shipping Terms:
|
The 1756-DHRIO (also written 1756DHRIO) is the Data Highway Plus and remote I/O bridge for the ControlLogix 1756 platform: two ports on the front, each selectable independently as DH+ or remote I/O, chassis mounted and one slot wide. It is the module that lets a ControlLogix controller own an installed base of legacy SLC, PLC-5 and 1771 remote racks instead of replacing that wiring.
DH+ runs at 57.6, 115.2 or 230.4 kbps. In remote I/O mode the module is a scanner only, with 32 logical rack connections and 16 block transfer connections per channel; the module supports 32 connections in total (1756-TD003 Table 13). Current draw is 850 mA at 5.1 V DC plus 1.7 mA at 24 V DC, dissipating 4.5 W and 15.4 BTU/hr. Isolation is 30 V continuous basic insulation from DHRIO A and B to the backplane and from the A port to the programming port, with no isolation between port A and the programming port, type tested at 877 V DC for 60 s.
| 1756-DHRIO | DH+ or remote I/O bridge, two selectable ports, 32 connections | IN STOCK |
| 1756-RIO | Remote I/O module, scanner or adapter, 32 physical racks | IN STOCK |
| 1756-DH485 | DH-485 network communication module | IN STOCK |
| 1756-SYNCH | SynchLink fibre module, 5 Mbps, 50 us frame, 2 ports | IN STOCK |
Application |
DH+ / Remote I/O |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-DHRIO |
Communication |
DH+ / Remote I/O |
Display |
Digital |
Enclosure |
None (open-style) |
Interface |
2 ports, each DH+ or remote I/O |
Mounting |
Chassis |
Number Of Channels |
2 |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Communication Module |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-UM001 (ControlLogix system user manual). Certification details, with certificate and file numbers, are listed in the FAQ below.
The module is the retrofit slot. An existing PLC-5 or SLC installation keeps its 1771 racks, its DH+ peer links and its block transfers, and the ControlLogix controller reads and writes them through this one card — no rewiring of the legacy drops.
The limits are the planning figures: 32 logical rack connections and 16 block transfer connections per channel, 32 connections in total, at 57.6/115.2/230.4 kbps. A segment that already saturates those numbers is not extended by adding a second DHRIO to the same chassis; it is re-scoped.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| OK | Flashing green | Power-up self-test in progress; wait for the solid state. |
| OK | Off | No chassis power at the slot, or the module failed its self-test. |
| Port A / B | Green solid | The port is up and exchanging data on DH+ or remote I/O. |
| Port A / B | Flashing green | Port configured, no data — rack assignment or node address not matching the segment. |
| Port A / B | Flashing red | Communication fault on that port: duplicate node, bad baud rate or a break in the trunk. |
| Port A / B | Off | Port not configured, or no activity on the link. |
Indicator behaviour per Rockwell publication 1756-UM001 (ControlLogix System User Manual) and 1756-IN050.
No successor is published for this module — the DH+ and remote I/O links it serves are installed-base networks, and the replacement path is a migration of the devices on those links to EtherNet/IP, not an exchange of a catalogue number.
Two checks decide whether the module is the right answer for a given panel. One: is the legacy traffic scheduled and within 32 connections per channel. Two: does the application need DH+ peer messaging — a DHRIO configured for remote I/O only does not carry it.
What do the two ports of the 1756-DHRIO do?
Each port is selectable independently as Data Highway Plus or remote I/O (1756-TD003 Table 13), so one module can serve a DH+ peer link and a remote I/O trunk at the same time. DH+ runs at 57.6, 115.2 or 230.4 kbps.
Can it be a remote I/O adapter as well as a scanner?
No. Table 13 lists the remote I/O function as scanner only, with 32 logical rack connections and 16 block transfer connections per channel. Where adapter behaviour is required, that is the 1756-RIO in adapter mode.
How many connections does it support?
32 connections in total (Table 13). The per-channel figures are 32 logical rack connections and 16 block transfers, so the total is reached with both channels loaded.
What is its backplane draw and isolation?
850 mA at 5.1 V DC and 1.7 mA at 24 V DC, 4.5 W and 15.4 BTU/hr. Isolation is 30 V continuous basic insulation from DHRIO A and B to the backplane and from port A to the programming port, with no isolation between port A and the programming port, type tested at 877 V DC for 60 s (Table 13).
What are its environmental limits?
Operating 0…60 °C, storage -40…85 °C, 5…95% RH non-condensing, 2 g vibration at 10…500 Hz, 30 g operating and 50 g non-operating shock, CISPR 11 Class A, ESD 6 kV contact and 8 kV air, radiated RF immunity 10 V/m from 80…2000 MHz and 3 V/m from 2000…2700 MHz, EFT ±2 kV at 5 kHz and surge ±2 kV line-earth, conducted RF 10 V rms (Table 14).
Which certifications does it carry?
c-UL-us UL E65584 and Class I Division 2 UL E194810, CSA LR54689C and LR69960C, CE to 2014/30/EU, RCM, ATEX II 3 G Ex ec IIC T4 Gc, UKEX UL22UKEX2604X, UKCA, IECEx UL 22.0063X, KC, Morocco and CCC 2020122309111998 (Table 15). FM approval is not listed for this module in that table.
Which chassis accept it and how is it wired?
1756-A4, A7, A10, A13 or A17, one slot wide (Table 13). Wiring category 2 applies on the DHRIO ports and category 3 on the local programming port; the local programming port is for temporary connection, not a permanent network drop.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications) and 1756-UM001 (ControlLogix System User Manual) and the manufacturer's product page for 1756-DHRIO. Values re-checked 15 November 2026.