The 1756-DH485 (also written 1756DH485) is the ControlLogix DH-485 communications module: two DH-485 channels on 9-pin D-shell connectors, 850 mA at 5.1 V DC backplane load, 4.5 W maximum dissipation, isolated at 50 V and tested to withstand 750 V DC for 60 s (1756-IN587).
The installation fact that decides most projects is that the module cannot be wired to the network directly. Each channel must be cabled to a 1761-NET-AIC advanced interface converter with a 1756-CP3 cable, and the converter connects to the DH-485 trunk. So a two-channel integration is two converters and two cables beyond the module itself.
Its function is messaging: the module sends and receives messages on DH-485 and, per the ControlLogix communication module data, does not support remote programming and monitoring. That is the boundary to state up front — an engineer expecting to program a SLC 500 across it will be disappointed.
Published specifications from 1756-IN587: backplane 850 mA at +5.1 V DC and 1.7 mA at 24 V DC, power dissipation 4.5 W maximum, thermal dissipation 15.4 BTU/hr, communication rates 19.2 Kbps default and 9600, enclosure open-style, wire 20 AWG (0.519 mm2) Belden 9463 twinaxial at conductor category 2, screw torque 0.5...0.6 Nm.
Environment: 0...60 °C operating, -40...85 °C storage, 5...95% non-condensing humidity, 2 g vibration at 10...500 Hz, 30 g operating shock, 50 g non-operating, CISPR 11 Group 1 Class A emissions. Configuration requires RSLinx 2.43 or later.
1756-CP3 |
Logix RS-232 programmer cable, one per DH-485 channel, active mature, UPC 612598173785 |
In stock |
1756-DH485 |
DH-485 communications module, 2 channels, 850 mA at 5.1 V DC, UPC per Rockwell record |
In stock |
1761-NET-AIC |
AIC+ converter required per DH-485 channel — not a 1756 item |
In stock |
Application |
DH-485 messaging / serial programming |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-DH485 |
Communication |
DH-485, 2 channels |
Display |
— |
Enclosure |
None (open-style) |
Interface |
9-pin D-shell |
Mounting |
Chassis slot |
Number Of Channels |
2 |
Standard |
CE, UL, CSA |
Sub Brand |
ControlLogix |
Type |
Communication Module |
UNSPSC |
— |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN587 (DH-485 module installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The module exists to bring legacy DH-485 devices — SLC 500, MicroLogix, older operator interfaces — into a ControlLogix system without replacing the field devices. It is an integration part, and its cost in a project is the module plus two converters plus two cables per two channels.
Typical use is a line where the older controllers still run the machine and the ControlLogix rack has to exchange data with them. Messaging is enough for that; remote programming is not available through the module, so the legacy controllers keep their own maintenance route.
In a new design the question is whether DH-485 is needed at all. EtherNet/IP modules remove the converter chain entirely, and the 1756-DH485 belongs to plants with an installed base worth preserving.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | CP3 per channel | The converter connects to the module through a 1756-CP3 cable, right-angle end at the converter. Two channels means two cables. |
| Check 3 | Messaging, not programming | The module sends and receives messages and does not support remote programming and monitoring — plan the DH-485 work accordingly. |
| Check 4 | Rate matches the network | 19.2 Kbps default against an existing network's rate. Set it from RSLinx 2.43 or later, not from assumption. |
| Check 5 | Slot and supply | Any slot in the chassis, multiple modules per chassis, limited by the power supply rating — 850 mA at 5.1 V DC each. |
| Check 6 | Cable and routing | Belden 9463 twinaxial, 20 AWG, conductor category 2, connectors at 0.5...0.6 Nm. Wrong cable type is a network that intermittently drops messages. |
Specifications and wiring per Rockwell publication 1756-IN587 (ControlLogix DH-485 Communications Module installation instructions); product attributes per the Rockwell product record and 1756-IN050.
The DH+ and remote I/O equivalent is 1756-DHRIO, a different network and not a substitute — DH-485, DH+ and remote I/O are three separate protocols.
For serial device integration on newer platforms, a protocol converter at the device end is often the cheaper route than adding DH-485 to a ControlLogix rack.
Where the whole segment is being modernised, 1756-EN2T or 1756-CN2 modules plus new field devices replace the module, the AIC+ converters and the twinaxial trunk in one step.
What is the 1756-DH485?
A ControlLogix DH-485 communications module with two DH-485 channels on 9-pin D-shell connectors.
Can it connect straight to a DH-485 network?
No. Each channel must go through a 1761-NET-AIC advanced interface converter, cabled with a 1756-CP3.
What is the backplane load?
850 mA at +5.1 V DC and 1.7 mA at 24 V DC, with 4.5 W maximum power dissipation (1756-IN587).
What communication rates does it support?
19.2 Kbps as default and 9600, set through RSLinx 2.43 or later.
What is the isolation rating?
50 V isolation, tested to withstand 750 V DC for 60 s.
Does it support remote programming?
No — it sends and receives messages and does not support remote programming and monitoring.
What cable does the network use?
Belden 9463 twinaxial, 20 AWG (0.519 mm2), conductor category 2, screw torque 0.5...0.6 Nm.
What are the environmental limits?
0...60 °C operating, -40...85 °C storage, 5...95% non-condensing humidity, 2 g vibration, 30 g operating shock, open-style enclosure.
How many modules fit in a chassis?
Any slot and multiple modules, limited by the power supply rating — 850 mA at 5.1 V DC per module.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-DH485. Values re-checked 15 November 2026.