The 1756-CPR2 (also written 1756CPR2) is the cable that joins a ControlLogix redundant power supply to the 1756-PSCA2 chassis adapter. Rockwell publishes it as a 0.91 m (3 ft) cable with a 12.7 cm (5.0 in.) bend radius, ordered separately from both the supply and the adapter (1756-IN620).
It is not included with the 1756-PA75R, 1756-PB75R, 1756-PAXTR or 1756-PBXTR when those are bought as individual supplies, which is why an incomplete redundant kit usually traces back to this line item. The 1756-PAR2 and 1756-PBR2 bundles are the exception — those catalogue numbers list the connection cables as included.
Two variants exist for tight layouts: 1756-CPR2D and 1756-CPR2U. Both require 10.16 cm (4.0 in.) of clearance beside the chassis adapter, where the standard CPR2 does not. The cable carries wire category 3 on its connections, and the male end plugs into the chassis adapter.
The safety point is printed as a warning, not a note: connecting or disconnecting a 1756-CPR2 while either backplane power source is on can produce an electric arc. In a hazardous location that is an explosion risk; in any location repeated arcing wears the contact pins on the cable and the mating connector, and worn contacts introduce resistance that can disturb module operation.
| 1756-PA75R | AC redundant supply, 120/240 V AC, 13 A at 5.1 V DC, 75 W | IN STOCK |
| 1756-PB75R | DC redundant supply, 24 V DC, 13 A at 5.1 V DC, 75 W | IN STOCK |
| 1756-PAXT | XT AC supply, 8 A at 5.1 V DC, 42 W at -25 to +70 C | IN STOCK |
| 1756-PBXT | XT DC supply, 10 A at 5.1 V DC, 52 W at -25 to +70 C | IN STOCK |
| 1756-PAXTR | XT AC redundant supply, 42 W, 0-60 C in a non-XT chassis | IN STOCK |
| 1756-PA75 | Non-redundant AC supply, single, 13 A at 5.1 V DC, 75 W | IN STOCK |
Application |
Chassis Power |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-CPR2 |
Communication |
— |
Display |
— |
Enclosure |
None (open-style) |
Interface |
Backplane, via 1756-PSCA2 |
Mounting |
Remote, cable-connected |
Number Of Channels |
— |
Standard |
CE, UL, RCM, EAC, Morocco DOC |
Sub Brand |
ControlLogix |
Type |
Redundant Power Supply |
UNSPSC |
— |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN620 (redundant power supply instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The cable is the mechanical link between two devices that are deliberately mounted in different places: the supplies in the enclosure where heat and wiring are manageable, the adapter in the chassis where the backplane connector is. Its fixed 0.91 m length defines the enclosure layout.
In service the cable is a wear item. Every connection and disconnection under load erodes the pins, so a maintenance procedure that unplugs cables to test a supply is an expensive habit. Use the annunciator contacts to identify a failed supply instead.
Because the redundancy claim excludes the cables, a spare CPR2 belongs in the spares kit next to the spare supply. It is a low-cost part that can stop a redundant rack exactly as effectively as a failed supply.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | Clearance for D and U variants | 1756-CPR2D and 1756-CPR2U need 10.16 cm beside the adapter. The bend radius rule still applies: 12.7 cm minimum on the cable. |
| Check 3 | Ordered separately | One cable per supply. A two-supply redundant assembly needs two CPR2 cables; the bundles include them, the individual supplies do not. |
| Check 4 | De-energise before connecting | Either backplane source on means an arc risk at the connector. Isolate first, especially in classified areas. |
| Check 5 | Connector orientation | The male end goes to the chassis adapter, the other end to the supply. Reversing the run does not work and the connector keying will not allow it. |
| Check 6 | Wiring category | Wire category 3 applies on the CPR2 connections — keep the routing separated from the power and signal classes around it. |
Installation checks per Rockwell publication 1756-IN620, which covers adapter mounting, cable seating, load sharing, fusing and the chassis compatibility table and 1756-IN050.
The redundant DC and AC supplies share this cable: 1756-PA75R, 1756-PB75R, 1756-PAXTR and 1756-PBXTR all connect through 1756-CPR2 or its D/U variants to a 1756-PSCA2 or 1756-PSCA2XT adapter.
If a bundle is being renewed, the cables arrive with it: 1756-PAR2 for the AC assembly and 1756-PBR2 for the DC assembly both list connection cables as included.
There is no substitute part. 1756-CPR2 is the only cable the installation instructions list for connecting a redundant supply to the chassis adapter.
What is the 1756-CPR2 used for?
Connecting a ControlLogix redundant power supply — 1756-PA75R, PB75R, PAXTR or PBXTR — to the 1756-PSCA2 or 1756-PSCA2XT chassis adapter (1756-IN620).
How long is it?
0.91 m (3 ft), with a 12.7 cm (5.0 in.) minimum bend radius.
Is the cable included with the power supply?
No when the supplies are ordered individually. The 1756-PAR2 and 1756-PBR2 bundles list the connection cables as included; a single 1756-PA75R or 1756-PB75R ships without one.
What are the CPR2D and CPR2U variants?
Alternative versions of the same cable for layouts that suit them, both requiring 10.16 cm (4.0 in.) of clearance beside the chassis adapter.
Can I unplug it while the system is running?
No. Connecting or disconnecting the cable while either backplane source is energised can arc — an explosion hazard in hazardous locations, and a cause of connector wear and contact resistance anywhere.
How many cables does a redundant rack need?
One per supply. A two-supply assembly needs two cables; each supply has its own run to the adapter.
Which end goes where?
The male end connects to the chassis adapter and the other end to the supply. The connector design does not permit the reverse.
What wiring category applies?
Wire category 3 on the 1756-CPR2 connections.
Does a spare cable matter?
Yes. The redundant system's coverage excludes the chassis adapter and the cables, so a damaged cable stops the rack even with both supplies healthy. Keep one in the spares kit.
Data sources. Technical values on this page come from Rockwell publications 1756-IN620 (ControlLogix Redundant Power Supply, installation instructions), 1756-IN619 (ControlLogix Power Supply installation instructions) and 1756-TD005 (ControlLogix power supply technical data) and the manufacturer's product page for 1756-CPR2. Values re-checked 15 November 2026.