Product Details:
Payment & Shipping Terms:
|
The 1756-EWEB (also written 1756EWEB) is the web server module for the ControlLogix platform: it publishes control-system information to a standard browser, so a maintenance terminal or a plant intranet page reads controller data without an HMI licence. One RJ45 Category 5 port at 10/100 Mbps, chassis mounted and one slot wide.
Capacity is below the bridge modules by design — 64 TCP connections, 128 CIP connections and 128 + 128 CIP unconnected messages (1756-TD003 Table 28) — because the port serves pages rather than carrying I/O. Current draw is 700 mA at 5.1 V DC, 3.7 W and 12.6 BTU/hr, isolation 30 V basic type tested at 707 V DC for 60 s (Table 30). Rockwell declared the module End of Life on 1 November 2021.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
EtherNet/IP |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-EWEB |
Communication |
EtherNet/IP |
Display |
Digital |
Enclosure |
None (open-style) |
Interface |
1 Copper RJ45 (10/100 Mbps, Category 5) |
Mounting |
Chassis |
Number Of Channels |
1 |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Communication Module |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
It sits in the slot where a browser is the interface: a maintenance page for the line, a read-only view of controller tags for a shift supervisor, a page hosted on the module itself and reachable from the plant network.
It is not a substitute for an EtherNet/IP bridge. The 64 TCP and 128 CIP connections serve the web and messaging side; I/O modules and drives belong on an EN2T, EN2TR or EN3TR, which publish 128 TCP and 256 CIP.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| OK | Flashing green | Power-up self-test in progress; wait for the solid state. |
| OK | Off | No chassis power at the slot, or the module failed its self-test. |
| NET | Green solid | CIP connections established; a browser session can read tags. |
| NET | Flashing green | IP address present, no CIP connection — check the controller path used by the web page. |
| NET | Off | No IP address; the module is not on the network yet. |
| LINK | Green solid | Port linked at 10 or 100 Mbps. |
| LINK | Off | No link: cable, connector or switch port. |
Indicator behaviour per Rockwell publication 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and 1756-IN050.
Rockwell declared the 1756-EWEB End of Life on 1 November 2021. The published engineered replacement is the ControlLogix 1756 Compute module — 1756-CMS1B1 or 1756-CMS1C1 — with the migration detail in publication 1756-RM013.
The check before touching a running panel is what the pages actually use: tag access, email and hosted pages all have to be rebuilt against the Compute module, they are not copied across. Until that rebuild is done, the EWEB stays in service only as long as the spares last, because it is no longer produced.
What is the 1756-EWEB used for?
Providing access to control-system information through a web browser. It hosts pages on the module and serves controller data to them over one RJ45 Category 5 port at 10/100 Mbps, so a maintenance terminal or an intranet page reads tags without an HMI runtime.
What are its connection limits?
64 TCP connections, 128 CIP connections and 128 + 128 CIP unconnected messages (1756-TD003 Table 28) — half the TCP capacity of the bridge modules, sized for web and messaging traffic rather than implicit I/O.
Can the 1756-EWEB still be bought?
No. It reached End of Life on 1 November 2021. The engineered replacement is the 1756-CMS1B1 or 1756-CMS1C1 ControlLogix Compute module, documented in the EtherNet/IP Web Server Module Migration Reference Manual, publication 1756-RM013.
Can it be used as the EtherNet/IP bridge for I/O modules?
It should not be. The module publishes 64 TCP and 128 CIP connections for web and messaging use; a chassis carrying I/O and drives needs the 128 TCP / 256 CIP budget of the EN2T, EN2TR or EN3TR.
What are the environmental limits and certifications?
Operating 0…60 °C; storage -40…85 °C; 5…95% RH non-condensing; 2 g vibration at 10…500 Hz; 30 g operating and 50 g non-operating shock; CISPR 11 Class A; ESD 6 kV contact and 8 kV air; EFT ±2 kV at 5 kHz and surge ±2 kV line-earth on the Ethernet port; open-style (Tables 30 and 31). Certifications: c-UL-us UL E65584 and Class I Division 2 UL E194810, CSA LR54689C and LR69960C, CE to 2004/108/EC, RCM, ATEX 94/9/EC II 3 G Ex nA IIC T4 Gc X, UKEX UL22UKEX2604X, UKCA, FM Class I Division 2, KC and ODVA conformance (Table 32).
Does the module support socket services and SNMP?
Yes to both. Table 29 of 1756-TD003 lists socket services as available, SNMP support requiring a password, and duplicate-IP detection starting at revision 2.2 — useful when the module is added to a plant network whose addressing is managed elsewhere.
What is its backplane current draw?
700 mA at 5.1 V DC and 3 mA at 24 V DC, dissipating 3.7 W and 12.6 BTU/hr, with 30 V basic isolation type tested at 707 V DC for 60 s (Table 30). The draw is the same as the ENBT it followed in the catalogue.
Which chassis and power supplies accept it?
Any slot of 1756-A4, A7, A10, A13 or A17, with the 1756-PA72, PA75, PB72, PB75, PC75 or PH75 supply or the redundant PA75R, PB75R and PSCA2 pair (Table 30). One slot wide, one RJ45 Category 5 port.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-EWEB. Values re-checked 15 November 2026.