The 1756-IF8H (also written 1756IF8H) is the 8-channel HART analog input: eight differential current inputs that carry both the 4...20 mA signal and the HART digital channel, so a transmitter's secondary variables, tag and diagnostics are readable from the controller without a separate multiplexer (1756-TD002).
The module is published in two series, and the difference is not cosmetic. A series: 300 mA at 5.1 V DC and 135 mA at 24 V DC, 4.77 W, one HART modem for the whole module, 50 V basic isolation. B series: 230 mA at 5.1 V DC and 80 mA at 24 V DC, 3.1 W, one HART modem per channel, 250 V reinforced isolation.
That single line decides most projects. One modem per module means HART instruments are polled in sequence; one modem per channel means eight simultaneous HART sessions. Fifty volts of basic isolation is not a field barrier; 250 V reinforced is.
Resolution is 16 to 21 bits depending on the range configuration, and the input is current-only — this is not the module for 0...10 V signals. Technical data 1756-TD002, user manual 1756-UM009, installation instructions 1756-IN063.
1756-IF4FXOF2F |
4 high-speed differential inputs + 2 outputs, 375 mA, reinforced isolation |
In stock |
1756-IF6CIS |
6 isolated current inputs with sourcing 24 V DC loop supply |
In stock |
1756-IF6I |
6 isolated inputs, 16-bit, 250 mA, channel-to-channel basic isolation |
In stock |
1756-IF8 |
8 single-ended / 4 differential inputs, 200 mA, 250 V basic to backplane |
In stock |
1756-IF8H |
8 differential HART current inputs, A and B series |
In stock |
1756-IF16 |
16 single-ended / 8 differential inputs, 200 mA, 15 Hz bandwidth |
In stock |
1756-IF16H |
16 differential HART current inputs, A and B series |
In stock |
1756-IRT8I |
8 isolated RTD and thermocouple inputs, 24-bit, 1756-CJC required |
In stock |
1756-IR6I |
6 isolated RTD inputs, 20-pin block, discontinued 2017 |
In stock |
1756-IT6I |
6 thermocouple inputs, two mV ranges, one CJC sensor |
In stock |
1756-IT6I2 |
6 isolated thermocouple inputs, 16-bit, two CJC sensors |
In stock |
Application |
Analog input |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-IF8H |
Communication |
Backplane (producer/consumer) |
Display |
— |
Enclosure |
None (open-style) |
Interface |
Removable terminal block |
Mounting |
Chassis slot |
Number Of Channels |
8 |
Standard |
CE, UL, CSA, RCM |
Sub Brand |
ControlLogix |
Type |
Analog Input Module |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN063 (analog I/O installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The IF8H is for plants that already run HART transmitters and want the digital data in the controller: device tags, ranged values, sensor diagnostics, and the second and third variables that would otherwise need extra transmitters or a handheld.
The B series is the specification for a new installation, because per-channel modems and 250 V reinforced isolation match how modern instrument loops are actually documented. The A series is the pragmatic choice for a retrofit where eight instruments are polled on a slow cycle anyway.
Where the panel only needs the 4...20 mA value, the HART capability is an unused cost; the 1756-IF8 does the measurement for 200 mA backplane and 1.74 W.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | One modem or eight | On the A series HART is multiplexed through a single modem, so polling eight transmitters takes eight times as long as one. Time-critical diagnostics need the B series. |
| Check 3 | A series isolation is 50 V basic | Not a field barrier. A panel requiring separation between field circuits needs the B series at 250 V reinforced. |
| Check 4 | Current input only | No voltage range. Voltage transmitters need an IF8, IF16 or IF6I, or a signal conditioner. |
| Check 5 | HART needs configuration | The HART channel is commissioned in the Logix Designer project; a module installed without it measures 4...20 mA and reports nothing digital. |
Specifications per Rockwell publication 1756-TD002 (ControlLogix I/O Modules Specifications); module behaviour per 1756-UM009 and 1756-IN050.
Without HART, the 1756-IF8 measures 8 single-ended channels at 200 mA backplane and 250 V basic isolation to the backplane.
For 16 HART channels, 1756-IF16H carries 16 differential current inputs with a modem per channel on the B series.
For isolated non-HART channels, 1756-IF8I provides 8 isolated inputs at 24-bit resolution with 250 V reinforced isolation.
What is the 1756-IF8H?
An 8-channel differential current input module with HART communication, published in A and B series.
What is the backplane current?
A series 300 mA at 5.1 V DC and 135 mA at 24 V DC (4.77 W); B series 230 mA at 5.1 V DC and 80 mA at 24 V DC (3.1 W).
What is the difference between A and B series?
A series has one HART modem per module and 50 V basic isolation; B series has one modem per channel and 250 V reinforced isolation.
What resolution does it have?
16 to 21 bits, depending on the configured range.
Does it accept voltage inputs?
No. The channels are current inputs; voltage signals need a different module or a signal conditioner.
How many HART channels can be polled at once?
One on the A series — HART is multiplexed through a single modem. Eight on the B series, one modem per channel.
What isolation does the B series provide?
250 V continuous reinforced insulation, against 50 V basic on the A series.
What documents cover it?
1756-TD002 for technical data, 1756-UM009 for the user manual and 1756-IN063 for installation.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-IF8H. Values re-checked 15 November 2026.