Product Details:
Payment & Shipping Terms:
|
The 1756-IC16 (also written 1756IC16) is the 16-point DC input module for higher-voltage DC circuits: 30...55 V DC at 60 °C and 30...60 V DC at 55 °C, both at 7 mA, with a backplane load of 135 mA at 5.1 V DC and 3 mA at 24 V DC (1756-IN062).
Read the two rows together and the module's real constraint appears: the top of the voltage range depends on the ambient temperature. 60 V DC is allowed at 55 °C, not at 60 °C — the derating is printed in the same cell, and a design that quotes '30...60 V DC' without the temperature is quoting half the specification.
Isolation is 250 V continuous basic from inputs to backplane and 125 V basic between input groups, with no isolation between the individual inputs of a group — the group boundary is where the 125 V stops.
This is the module for 48 V DC control circuits and for 24 V systems that sit well above the 31.2 V ceiling of the IB family. Where a panel already runs 48 V DC, the IC16 avoids a voltage converter per channel.
1756-IB16 |
16 sinking inputs, 10...31.2 V DC 10 mA, backplane 100 mA, UPC 612598171293 |
In stock |
1756-IB16D |
16 diagnostic inputs, 10...30 V DC 13 mA, backplane 150 mA |
In stock |
1756-IB16I |
16 isolated inputs, 10...30 V DC 10 mA, backplane 135 mA |
In stock |
1756-IB16IF |
16 fast peer-control inputs, 10...30 V DC 5 mA, backplane 275 mA |
In stock |
1756-IB16ISOE |
16 sequence-of-events inputs, 10...55 V DC 5.1 mA, backplane 320 mA |
In stock |
1756-IB32 |
32 sinking inputs, 10...31.2 V DC 5.5 mA, backplane 120 mA, UPC 612598171309 |
In stock |
1756-IC16 |
16 inputs, 30...60 V DC, backplane per 1756-IN062 |
In stock |
1756-IG16 |
16 TTL inputs, backplane per 1756-IN062 |
In stock |
1756-IV16 |
16 inputs, 48 V DC, backplane per 1756-IN062 |
In stock |
Application |
Discrete input |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-IC16 |
Communication |
Backplane (producer/consumer) |
Display |
— |
Enclosure |
None (open-style) |
Interface |
Removable terminal block |
Mounting |
Chassis slot |
Number Of Channels |
16 |
Standard |
CE, UL, CSA, RCM |
Sub Brand |
ControlLogix |
Type |
Digital Input Module |
UNSPSC |
— |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN062 (DC digital I/O installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The IC16 belongs on 48 V DC control circuits — older machine tools, some marine and heavy-vehicle systems, and plant where 48 V DC is the house standard. It reads those circuits directly without a per-channel converter.
It also handles 24 V systems that run high: a battery-backed 24 V rail can sit above 31 V during equalise charging, outside the IB16 window but inside the IC16's.
Because the top of its range moves with ambient, a panel that runs hot needs the 55 °C row, not the 60 °C one. Check the enclosure temperature, not the datasheet ceiling.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | 7 mA per point | Higher than the IB family's 5...10 mA range, so the field burden is not the lightest option. |
| Check 3 | 135 mA backplane | Comparable to the IB16I, and 35 % above the standard IB16. |
| Check 4 | 125 V group isolation | Group-to-group is basic at 125 V, and there is no isolation inside a group. |
| Check 5 | 24 V systems do not need it | For a 24 V DC field supply the IB16 covers the range at lower input current; the IC16 is for 30 V DC and above. |
Specifications per Rockwell publication 1756-IN062 (ControlLogix DC Digital I/O Modules installation instructions); module behaviour per 1756-UM058 and technical data 1756-TD002 and 1756-IN050.
The 10...31.2 V DC standard module is 1756-IB16 for 24 V DC circuits.
The wide-window 10...55 V DC module is 1756-IB16ISOE, which covers both 24 V and 48 V DC in one catalogue number.
For 90...146 V DC circuits the equivalent is 1756-IH16I, whose derating is expressed in channels-on versus ambient.
What is the 1756-IC16?
A 16-point DC input module for 30...55 V DC at 60 °C and 30...60 V DC at 55 °C, at 7 mA per input.
Why are there two voltage ranges?
The published table derates the upper voltage with ambient temperature: 60 V DC is specified at 55 °C, not at 60 °C.
What is the backplane current?
135 mA at 5.1 V DC and 3 mA at 24 V DC.
What isolation does it provide?
250 V continuous basic inputs-to-backplane, 125 V basic between input groups, and no isolation between individual inputs in a group.
Can I use it on a 24 V DC system?
It would work within range, but the 1756-IB16 is the module specified for 24 V DC, with a lower input current.
Is it a 48 V DC module?
Yes — 48 V DC sits inside the 30...55 V DC range at 60 °C.
What is the input current per point?
7 mA, printed for both voltage rows.
What documents cover it?
1756-IN062 for installation and specifications, 1756-TD002 for technical data and 1756-UM058 for the user manual.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-IC16. Values re-checked 15 November 2026.