Product Details:
Payment & Shipping Terms:
|
The 1756-IA32 (also written 1756IA32) is the 32-point AC input module: 74...132 V AC at 50/60 Hz, 15 mA per point, backplane 165 mA at 5.1 V DC and 2 mA at 24 V DC, isolation 250 V continuous basic inputs to backplane and 125 V basic group to group (1756-IN064).
The input window is what distinguishes it. Every other 120 V AC input in the family is published at a flat 120 V AC; the IA32 publishes 74...132 V AC, which means it keeps working at 74 V — a third below nominal — and tolerates 132 V on a supply running high. On a 110 V nominal system with a loaded control transformer, that window is the difference between a reliable input and a intermittent one.
Thirty-two points in a single slot is the highest density in the AC input family, and it is paid for on the 5.1 V rail: 165 mA, against 100 mA for the 16-point IA16. Two groups of sixteen share the group-to-group barrier at 125 V, with no isolation between the points inside a group.
The module suits the large, mostly-uniform 120 V pilot circuit that fills a whole chassis slot in a process panel — dozens of valve position, level and interlock contacts on one card, where wiring two groups of sixteen is simpler than spreading the same signals across four cards.
1756-IB16 |
16 sinking inputs, 10...31.2 V DC 10 mA, backplane 100 mA, UPC 612598171293 |
In stock |
1756-IB16D |
16 diagnostic inputs, 10...30 V DC 13 mA, backplane 150 mA |
In stock |
1756-IB16I |
16 isolated inputs, 10...30 V DC 10 mA, backplane 135 mA |
In stock |
1756-IB16IF |
16 fast peer-control inputs, 10...30 V DC 5 mA, backplane 275 mA |
In stock |
1756-IB16ISOE |
16 sequence-of-events inputs, 10...55 V DC 5.1 mA, backplane 320 mA |
In stock |
1756-IB32 |
32 sinking inputs, 10...31.2 V DC 5.5 mA, backplane 120 mA, UPC 612598171309 |
In stock |
1756-IC16 |
16 inputs, 30...60 V DC, backplane per 1756-IN062 |
In stock |
1756-IG16 |
16 TTL inputs, backplane per 1756-IN062 |
In stock |
1756-IV16 |
16 inputs, 48 V DC, backplane per 1756-IN062 |
In stock |
Application |
Discrete input |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-IA32 |
Communication |
Backplane (producer/consumer) |
Display |
— |
Enclosure |
None (open-style) |
Interface |
Removable terminal block |
Mounting |
Chassis slot |
Number Of Channels |
32 |
Standard |
CE, UL, CSA, RCM |
Sub Brand |
ControlLogix |
Type |
Digital Input Module |
UNSPSC |
— |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN062 (DC digital I/O installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The IA32 is the density answer: thirty-two 120 V status and interlock signals per slot, with the widest published input window in the family at 74...132 V AC.
It is the right card where the field supply is a loaded control transformer that sags under inrush. At 74 V the input still reads; a module published at a flat 120 V would be outside its specification.
Two groups of sixteen support a split panel — typically one group from the machine's control circuit and the second from the safety-status or utility circuit — without a second card or a second common.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | 165 mA at 5.1 V DC | The price of 32 points in one slot. Count it against the chassis power budget before filling the rack. |
| Check 3 | Two groups of sixteen | 125 V group-to-group isolation, none within a group. Thirty-two signals means two commons, not thirty-two. |
| Check 4 | 15 mA per point | Higher than the IA16's 13 mA — better leakage immunity across a densely wired marshalling panel. |
| Check 5 | T4A temperature code | 60 °C maximum surrounding air, with 0.33...2.1 mm² wire on the removable terminal block. |
Specifications per Rockwell publication 1756-IN062 (ControlLogix DC Digital I/O Modules installation instructions); module behaviour per 1756-UM058 and technical data 1756-TD002 and 1756-IN050.
For 16 points at a flat 120 V AC rating and half the backplane current, use 1756-IA16.
For 16 individually isolated 120 V AC inputs, use 1756-IA16I at 125 V input-to-input.
For 240 V AC inputs, use 1756-IM16I.
What is the 1756-IA32?
A 32-point AC input module with a 74...132 V AC input window, 15 mA per point, backplane 165 mA at 5.1 V DC.
What is its input voltage range?
74...132 V AC at 50/60 Hz, as published in 1756-IN064.
Why is the range wider than the other 120 V modules?
Rockwell publishes the IA32 over 74...132 V AC; the IA16, IA16I and IA8D are specified at 120 V AC.
How many groups does it have?
Two groups of sixteen with 125 V basic isolation between them, and no isolation between points within a group.
How much backplane current does it draw?
165 mA at 5.1 V DC and 2 mA at 24 V DC.
How much current does each input draw?
15 mA.
Does it accept 240 V AC?
No. The published maximum is 132 V AC, and the group barrier is 125 V.
What is the maximum ambient temperature?
60 °C surrounding air, temperature code T4A.
Which document has the full ratings table?
1756-IN064, the ControlLogix AC digital I/O installation instructions.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-IA32. Values re-checked 15 November 2026.