Product Details:
Payment & Shipping Terms:
|
The 1756-L7SPXT / 1756L7SPXT is the GuardLogix 5570 safety controller built on the 5570 hardware: — MB of standard user memory with a separate configured to match the primary controller MB safety memory, one chassis slot, the 1 GB SD card in the slot, and the paired safety partner that turns a standard controller into a SIL 3 / PLe pair.
Published figures for the GuardLogix 5570 controllers are 0.98 MB I/O memory, 128,000 digital I/O maximum, 1756-ESMCAP energy storage module shipped installed, 800 mA at 5.1 V DC and 5 mA at 1.2 V DC, 2.5 W and 8.5 BTU/hr, 30 V continuous basic isolation from the USB port to the system, and a shipping weight of 0.25 kg (0.55 lb) (1756-TD001). The safety partner uses its own energy storage module — 1756-SPESMNSE or 1756-SPESMNRM — which is a separate line on the same specification table.
| 1756-L71 | ControlLogix 5570 controller, 2 MB user memory | IN STOCK |
| 1756-L72 | ControlLogix 5570 controller, 4 MB user memory | IN STOCK |
| 1756-L73 | ControlLogix 5570 controller, 8 MB user memory | IN STOCK |
| 1756-L71S | GuardLogix 5570 safety controller, 2 MB / 1 MB safety | IN STOCK |
| 1756-L72S | GuardLogix 5570 safety controller, 4 MB / 2 MB safety | IN STOCK |
| 1756-L73S | GuardLogix 5570 safety controller, 8 MB / 4 MB safety | IN STOCK |
| 1756-L7SP | GuardLogix 5570 safety partner, pairs with L71S / L72S / L73S | IN STOCK |
| 1756-L73XT | ControlLogix-XT 5570 controller, 8 MB, -25 to +70 C | IN STOCK |
| 1756-L73SXT | GuardLogix-XT 5570 safety controller, 8 MB / 4 MB safety | IN STOCK |
| 1756-L7SPXT | GuardLogix-XT 5570 safety partner, pairs with L73SXT | IN STOCK |
Application |
Safety Programmable Logic Controller |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-L7SPXT |
Communication |
EtherNet/IP |
Display |
Digital |
Enclosure |
None (open-style) |
Interface |
1756-L7SPXT |
Mounting |
Chassis |
Number Of Channels |
1756-L7SPXT |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Controller |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-UM001 (ControlLogix controller user manual). Certification details, with certificate and file numbers, are listed in the FAQ below.
The XT partner is ordered with the XT controller and shipped as its own line: two slots, two energy storage modules, two indicators. In a cold panel the pair is the safety system, and the temperature qualification covers both items.
Spares planning is the practical problem: an XT partner without an XT controller is unusable, and the reverse is equally true, so the stock position is a pair count rather than a module count.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| RUN | Steady green | Controller is in Run mode. |
| FORCE | Off | No tags contain I/O force values, or forces are disabled. |
| FORCE | Steady yellow | I/O forces are enabled. A field wiring check made now is not valid. |
| FORCE | Flashing yellow | Forced addresses exist but forces are not enabled; enabling them applies every stored force at once. |
| OK | Off | No power applied to the controller. |
| OK | Flashing red | New controller that needs a firmware update, or a major fault on a controller in service. |
| OK | Steady red | Power-up diagnostics, ESM discharge at power-down, project transfer to nonvolatile memory, or a controller that is powered but inoperable. |
| OK | Steady green | Controller operating normally. |
| Status display | TEST / PASS | Power-up tests running, then completed. |
| Status display | CHRG | Capacitor energy storage module charging; do not remove the ESM. |
| Status display | BUSY | I/O modules in the project are not yet fully powered. |
| Status display | No Project | Controller memory is empty; download the project or load it from the SD card. |
| Status display | Rev XX.xxx | Firmware major and minor revision currently installed. |
Indicator behaviour per Rockwell publication 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and 1756-IN050.
For an extreme-temperature GuardLogix rack, the XT pair replaces the standard pair module for module; the chassis and the safety I/O move to XT at the same time.
Rockwell publishes both partner variants on the GuardLogix 5570 specification table in 1756-TD001, so the pairing rule and the energy storage difference can be checked before ordering.
Which controller does the 1756-L7SPXT pair with?
1756-L73SXT, the XT GuardLogix 5570 controller with 8 MB standard and 4 MB safety memory.
Which energy storage modules belong to the partner?
1756-SPESMNSEXT (removable, no residual wall-clock backup) or 1756-SPESMNRMXT (non-removable, blocks USB and card access).
What temperature range applies?
-25…+70 °C, the XT envelope. Chassis, I/O and supplies in the rack must be XT parts for the assembly to hold that rating.
Does the partner have its own memory?
No. It is configured to match the primary controller; the safety memory figure of 4 MB belongs to the 1756-L73SXT primary.
What current does it draw?
The GuardLogix 5570 XT controllers are published at 800 mA at 5.1 V DC and 5 mA at 1.2 V DC, 2.5 W and 8.5 BTU/hr; the rack budget covers both devices of the pair.
Can an XT partner be used with a standard controller?
No. The pair has to match: standard controller with 1756-L7SP, XT controller with 1756-L7SPXT.
Which indicators show partner state?
The partner carries its own indicator set and its own energy storage state; diagnostics are read from the pair in the programming software rather than from the primary controller alone.
What is the isolation rating?
The GuardLogix 5570 XT controllers are published with 30 V continuous basic insulation from the USB port to the system; the partner is part of the same certified assembly.
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) and 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and the manufacturer's product page for 1756-L7SPXT. Values re-checked 16 November 2026.