Product Details:
Payment & Shipping Terms:
|
The 1756-L73XT (also written 1756L73XT) is the 8 MB ControlLogix 5570 controller built for the XT range: the same one-slot controller with the same memory and electrical figures, but shipped with extreme-temperature energy storage modules and rated for -25…+70 °C panel air instead of 0…60 °C.
The published controller table gives 8 MB user memory, 0.98 MB I/O memory, 128,000 digital, 4,000 analogue and 128,000 total I/O points as maximums, 800 mA at 5.1 V DC and 5 mA at 1.2 V DC, 2.5 W and 8.5 BTU/hr, and 30 V continuous basic isolation from the USB port to the backplane under IEC/UL 61010-1 (1756-TD001). The module list for this controller is the XT set: 1756-ESMCAPXT installed, 1756-ESMNSEXT and 1756-ESMNRMXT as alternatives.
| 1756-L71 | ControlLogix 5570 controller, 2 MB user memory | IN STOCK |
| 1756-L72 | ControlLogix 5570 controller, 4 MB user memory | IN STOCK |
| 1756-L73 | ControlLogix 5570 controller, 8 MB user memory | IN STOCK |
| 1756-L71S | GuardLogix 5570 safety controller, 2 MB / 1 MB safety | IN STOCK |
| 1756-L72S | GuardLogix 5570 safety controller, 4 MB / 2 MB safety | IN STOCK |
| 1756-L73S | GuardLogix 5570 safety controller, 8 MB / 4 MB safety | IN STOCK |
| 1756-L7SP | GuardLogix 5570 safety partner, pairs with L71S / L72S / L73S | IN STOCK |
| 1756-L73XT | ControlLogix-XT 5570 controller, 8 MB, -25 to +70 C | IN STOCK |
| 1756-L73SXT | GuardLogix-XT 5570 safety controller, 8 MB / 4 MB safety | IN STOCK |
| 1756-L7SPXT | GuardLogix-XT 5570 safety partner, pairs with L73SXT | IN STOCK |
Application |
Programmable Logic Controller |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-L73XT |
Communication |
EtherNet/IP |
Display |
Digital |
Enclosure |
None (open-style) |
Interface |
1756-L73XT |
Mounting |
Chassis |
Number Of Channels |
1756-L73XT |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Controller |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-UM001 (ControlLogix controller user manual). Certification details, with certificate and file numbers, are listed in the FAQ below.
The XT variant is bought for the temperature range, not the memory. Cold-store, rooftop, skid and unheated outdoor enclosures are where the standard controller's 0 °C floor becomes the design constraint, and where the whole rack — chassis, modules, supplies — has to move to XT together.
Inside the panel the electrical budget does not change: 800 mA at 5.1 V DC, 2.5 W of dissipation and 8.5 BTU/hr are the same figures as the standard L73. What changes is the surrounding hardware, because an XT controller in a standard chassis only moves the temperature limit of one component.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| RUN | Steady green | Controller is in Run mode. |
| FORCE | Off | No tags contain I/O force values, or forces are disabled. |
| FORCE | Steady yellow | I/O forces are enabled. A field wiring check made now is not valid. |
| FORCE | Flashing yellow | Forced addresses exist but forces are not enabled; enabling them applies every stored force at once. |
| OK | Off | No power applied to the controller. |
| OK | Flashing red | New controller that needs a firmware update, or a major fault on a controller in service. |
| OK | Steady red | Power-up diagnostics, ESM discharge at power-down, project transfer to nonvolatile memory, or a controller that is powered but inoperable. |
| OK | Steady green | Controller operating normally. |
| Status display | TEST / PASS | Power-up tests running, then completed. |
| Status display | CHRG | Capacitor energy storage module charging; do not remove the ESM. |
| Status display | BUSY | I/O modules in the project are not yet fully powered. |
| Status display | No Project | Controller memory is empty; download the project or load it from the SD card. |
| Status display | Rev XX.xxx | Firmware major and minor revision currently installed. |
Indicator behaviour per Rockwell publication 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and 1756-IN050.
As a functional replacement for a 5560 controller in an extreme-temperature panel, the L73XT takes the same slot and the same I/O. The chassis and the supply have to be the XT parts, and the energy storage modules are the XT catalogue numbers.
Within the XT range the GuardLogix equivalent is the 1756-L73SXT, which adds the safety partner pair for SIL 3 applications in the same temperature envelope.
What temperature range does the 1756-L73XT cover?
The XT (extreme temperature) range is rated -25…+70 °C; the standard 5570 controller is 0…60 °C. The controller must be installed with XT chassis and XT modules so the whole rack shares the rating.
Does the XT version have different memory?
No. 8 MB user memory, 0.98 MB I/O memory and the same 128,000 / 4,000 / 128,000 I/O maximums as the standard 1756-L73 (1756-TD001).
Which energy storage modules are used?
1756-ESMCAPXT, shipped installed in every XT controller; 1756-ESMNSEXT as the removable module without residual wall-clock backup; 1756-ESMNRMXT as the non-removable module that prevents USB connection and SD card removal.
Are the current draw and dissipation different?
No. 800 mA at 5.1 V DC, 5 mA at 1.2 V DC, 2.5 W and 8.5 BTU/hr are the published figures for 1756-L73XT, identical to the standard controller (1756-TD001).
What isolation does it provide?
30 V continuous, basic insulation type, from the USB port to the backplane, compliant and tested according to IEC/UL 61010-1.
Can a standard L73 simply be swapped for an XT part?
Only after the rest of the rack is checked: XT chassis, XT I/O and XT supplies. A single XT controller in a standard chassis does not extend the assembly's temperature rating.
How is firmware handled in a cold panel?
Through the SD card at power-up (UPDT on the display) or over USB in the panel. The card and the controller share the same temperature rating, so an update performed at -25 °C is inside the published envelope.
What does the status display report?
TEST then PASS at power-up, CHRG while the capacitor module charges, the firmware revision, the project name or No Project, and SAVE / LOAD / UPDT during SD card activity (1756-UM001).
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) and 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and the manufacturer's product page for 1756-L73XT. Values re-checked 16 November 2026.