Product Details:
Payment & Shipping Terms:
|
The 1756-L73S / 1756L73S is the GuardLogix 5570 safety controller built on the 5570 hardware: 8 MB of standard user memory with a separate 4 MB safety memory, one chassis slot, the 1 GB SD card in the slot, and the paired safety partner that turns a standard controller into a SIL 3 / PLe pair.
Published figures for the GuardLogix 5570 controllers are 0.98 MB I/O memory, 128,000 digital I/O maximum, 1756-ESMCAP energy storage module shipped installed, 800 mA at 5.1 V DC and 5 mA at 1.2 V DC, 2.5 W and 8.5 BTU/hr, 30 V continuous basic isolation from the USB port to the system, and a shipping weight of 0.25 kg (0.55 lb) (1756-TD001). The safety partner uses its own energy storage module — 1756-SPESMNSE or 1756-SPESMNRM — which is a separate line on the same specification table.
| 1756-L71 | ControlLogix 5570 controller, 2 MB user memory | IN STOCK |
| 1756-L72 | ControlLogix 5570 controller, 4 MB user memory | IN STOCK |
| 1756-L73 | ControlLogix 5570 controller, 8 MB user memory | IN STOCK |
| 1756-L71S | GuardLogix 5570 safety controller, 2 MB / 1 MB safety | IN STOCK |
| 1756-L72S | GuardLogix 5570 safety controller, 4 MB / 2 MB safety | IN STOCK |
| 1756-L73S | GuardLogix 5570 safety controller, 8 MB / 4 MB safety | IN STOCK |
| 1756-L7SP | GuardLogix 5570 safety partner, pairs with L71S / L72S / L73S | IN STOCK |
| 1756-L73XT | ControlLogix-XT 5570 controller, 8 MB, -25 to +70 C | IN STOCK |
| 1756-L73SXT | GuardLogix-XT 5570 safety controller, 8 MB / 4 MB safety | IN STOCK |
| 1756-L7SPXT | GuardLogix-XT 5570 safety partner, pairs with L73SXT | IN STOCK |
Application |
Safety Programmable Logic Controller |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-L73S |
Communication |
EtherNet/IP |
Display |
Digital |
Enclosure |
None (open-style) |
Interface |
1756-L73S |
Mounting |
Chassis |
Number Of Channels |
1756-L73S |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Controller |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-UM001 (ControlLogix controller user manual). Certification details, with certificate and file numbers, are listed in the FAQ below.
8 MB / 4 MB is the size chosen when the safety architecture is plant-wide rather than per machine: one safety task spanning several zones, with the standard program carrying the line and the HMI traffic in the same controller.
The larger safety memory does not relax any certification requirement. The pair, the safety I/O and the wiring remain the certified assembly; memory only decides how much of the plant fits in one validated task.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| RUN | Steady green | Controller is in Run mode. |
| FORCE | Off | No tags contain I/O force values, or forces are disabled. |
| FORCE | Steady yellow | I/O forces are enabled. A field wiring check made now is not valid. |
| FORCE | Flashing yellow | Forced addresses exist but forces are not enabled; enabling them applies every stored force at once. |
| OK | Off | No power applied to the controller. |
| OK | Flashing red | New controller that needs a firmware update, or a major fault on a controller in service. |
| OK | Steady red | Power-up diagnostics, ESM discharge at power-down, project transfer to nonvolatile memory, or a controller that is powered but inoperable. |
| OK | Steady green | Controller operating normally. |
| Status display | TEST / PASS | Power-up tests running, then completed. |
| Status display | CHRG | Capacitor energy storage module charging; do not remove the ESM. |
| Status display | BUSY | I/O modules in the project are not yet fully powered. |
| Status display | No Project | Controller memory is empty; download the project or load it from the SD card. |
| Status display | Rev XX.xxx | Firmware major and minor revision currently installed. |
Indicator behaviour per Rockwell publication 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and 1756-IN050.
The 5560 GuardLogix replacement path ends here: this controller plus an L7SP carries the memory of an L63S with the 5570 programming path and nonvolatile storage.
Above the 5570 range, the GuardLogix 5580 controllers add embedded Ethernet and CIP Security, at a different packet-rate class and a different price band.
What are the memory figures of the 1756-L73S?
8 MB of standard memory and 4 MB of safety memory — the largest split in the GuardLogix 5570 range — with 0.98 MB I/O memory and a 128,000 digital I/O maximum (1756-TD001).
What does 4 MB of safety memory buy?
Room for a plant-wide safety task: several zones, the full safety I/O configuration and the diagnostics logic, without the safety program competing with the standard program for space.
Which partner is required?
1756-L7SP in its own slot, with a 1756-SPESMNSE or SPESMNRM energy storage module.
What is the electrical specification?
800 mA at 5.1 V DC, 5 mA at 1.2 V DC, 2.5 W, 8.5 BTU/hr, 30 V continuous basic isolation from the USB port to the system (1756-TD001).
Is the XT version available?
Yes — 1756-L73SXT, same memory split, XT energy storage modules and the -25…+70 °C rating for the whole rack.
How is the safety program validated?
The safety task is built in ladder logic only, the safety signature is generated in the project, and the installed pair is verified against that signature before the zone is commissioned.
What storage ships with the controller?
A 1 GB 1784-SD1 Secure Digital card, pre-installed; the card is written during SAVE and read during LOAD or UPDT at power-up.
What is the weight and origin factor?
0.25 kg (0.55 lb) as published for the GuardLogix 5570 controllers; origin and lifecycle are read from Rockwell's product record for the specific catalogue number.
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) and 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and the manufacturer's product page for 1756-L73S. Values re-checked 16 November 2026.