Product Details:
Payment & Shipping Terms:
|
The 1756-L64 (also written 1756L64) is the 16 MB controller of the ControlLogix 5560 range: twice the user memory of the 1756-L63 and half that of the 1756-L65, in the same one-slot package with one RS-232 programming port and backplane access to the rack. Rockwell lists it as discontinued on 1 June 2017 under the functional replacement category, series B, UPC 612598330829, country of origin United States of America.
The 5560 envelope applies: 478 KB of I/O memory, 128,000 digital and 4,000 analogue I/O points as maximums, 32 tasks with 100 programs per task, 250 controller connections, 1200 mA at 5.1 V DC plus 14 mA at 24 V DC, 3.5 W and 11.9 BTU/hr (1756-TD001). Two published cautions come with the large-memory 5560 parts: a project loaded in an L64 or L65 can scan more slowly than the same project in the smaller controllers, and the L64 and L65 do not hold the ATEX certification the rest of the family carries.
| 1756-L61 | 5560 controller, 2 MB | IN STOCK |
| 1756-L62 | 5560 controller, 4 MB | IN STOCK |
| 1756-L63 | 5560 controller, 8 MB | IN STOCK |
| 1756-L63XT | ControlLogix-XT 5560 controller, 8 MB, conformal coated | IN STOCK |
| 1756-L64 | 5560 controller, 16 MB | IN STOCK |
| 1756-L65 | 5560 controller, 32 MB | IN STOCK |
| 1756-L71 | 5570 controller, 2 MB | IN STOCK |
| 1756-L73 | 5570 controller, 8 MB | IN STOCK |
Application |
Programmable Logic Controller |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-L64 |
Communication |
Backplane (EtherNet/IP, ControlNet, DeviceNet, DH+, Remote I/O, SERCOS) |
Display |
Indicators (OK, RUN, I/O, FORCE, BATTERY, RS-232) |
Enclosure |
None (open-style) |
Interface |
1 RS-232 serial port |
Mounting |
Chassis |
Number Of Channels |
1 |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Controller |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-UM001 (ControlLogix controller user manual). Certification details, with certificate and file numbers, are listed in the FAQ below.
16 MB is chosen where the program carries a large recipe or tag set but not the full cell-level scope of an L65: a converting line, a batch skid, a machine with heavy recipe management. It is the middle answer when 8 MB was outgrown and 32 MB is more than the application will ever use.
The scan-time caution matters more than the memory figure in most upgrades. A project written for an L63 and moved into an L64 does not automatically run faster; if the task structure and program density stay the same, the larger controller can take longer per scan, which is why the task periods are re-measured after the swap.
The same 250-connection ceiling applies, so the memory can grow without the connection count growing.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| OK | Flashing green | Power-up self-test in progress; wait for solid. |
| OK | Red | Major fault or self-test failure. Read the fault in the project before any restart. |
| RUN | Green solid | Program running. |
| RUN | Red | Major fault latched; the program is stopped. |
| I/O | Green solid | All configured I/O modules are communicating. |
| I/O | Flashing green | One or more configured modules are not responding. |
| I/O | Red | Faulted I/O connection; the program may still be running. |
| FORCE | Amber | Forces enabled — a live wiring check is not valid while this is lit. |
| BATTERY | Red | Battery low or missing; the project in RAM is not protected across a power cycle. |
| RS-232 | Green flashing | Serial activity on the programming port. |
Indicator behaviour per Rockwell publication 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and 1756-IN050.
Rockwell's notice sets the 1756-L64 discontinuation at 1 June 2017, functional replacement category. The successor families are the 5570 (1756-L71E to L73E) and the 5580 (L81E to L85E), where 16 MB of user memory sits between the L72E and L73E.
The migration is a program migration, not a module swap: the controller loses the serial port in favour of USB and Ethernet, the memory is re-sized, and every task period and motion axis is re-verified against the new scan behaviour.
Where the installed program fits a smaller memory size, an L63 or L62 replacement is simpler and keeps the enclosure budget unchanged.
How much user memory does the 1756-L64 have?
16 MB of user memory, with 478 KB of I/O memory and maximums of 128,000 digital and 4,000 analogue I/O points (1756-TD001).
How does it differ from the 1756-L63 and L65?
Memory only: 16 MB against 8 MB on the L63 and 32 MB on the L65. Current draw, connections and environmental limits are the same across the 5560 family.
Is the module still available new?
No — Rockwell lists the discontinuation date as 1 June 2017, replacement category functional replacement, series B.
What are the UPC and country of origin?
UPC 612598330829, country of origin United States of America, as published on the Rockwell product record.
Does a larger memory make the scan faster?
Not necessarily. Rockwell publishes the caution that a project in an L64 or L65 can scan more slowly than the same project in the smaller 5560 controllers, so task periods have to be re-measured after the swap.
Does it carry ATEX certification?
No — the L64 and L65 are the two 5560 controllers that do not hold the ATEX certification the rest of the family carries (1756-TD001).
How much current does it draw?
1200 mA at 5.1 V DC and 14 mA at 24 V DC, 3.5 W and 11.9 BTU/hr, one slot wide.
Which chassis and power supplies are approved?
1756-A4, A7, A10, A13 or A17 in any slot; standard supplies 1756-PA50, PA72, PA75, PB50, PB72, PB75, redundant 1756-PA75R / PB75R with the 1756-PSCA2 adapter.
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) and 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and the manufacturer's product page for 1756-L64. Values re-checked 16 November 2026.