The 1756-OH8I (also written 1756OH8I) is the ControlLogix 125 V DC isolated output module: eight outputs, each individually isolated, rated 2 A per point and 8 A per module at 60 °C, operating from 90…146 V DC.
It exists for the places where 125 V DC is already the control voltage — switchgear, battery-backed substation panels, and older plant where the DC tripping supply is 125 V rather than 24 V. Sourcing and sinking are both supported, so the module can sit on either side of the load without an external interface relay.
1756-OH8I |
8 isolated 125 V DC outputs, 2 A per point |
In stock |
1756-OB16I |
16 isolated 24 V DC outputs |
In stock |
1756-OW16I |
16 isolated relay contacts, AC or DC |
In stock |
1756-OB16E |
16 electronically fused 24 V DC outputs |
In stock |
1756-TBCH |
Removable terminal block, 36 terminals |
In stock |
Application |
125 V DC isolated digital output |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-OH8I |
Type |
Digital DC output module |
Sub Brand |
ControlLogix |
Mounting |
1756 ControlLogix chassis |
Number Of Channels |
8 individually isolated |
Voltage Category |
125 V DC sink/source |
Operating Voltage |
90…146 V DC |
Current Per Point |
2 A at 60 °C |
Current Per Module |
8 A at 60 °C |
Surge Current |
4 A for 10 ms per point, every 1 s |
Minimum Load |
2 mA per point |
Backplane Current |
210 mA at 5.1 V DC, 2 mA at 24 V DC |
Backplane Power |
1.11 W |
Power Dissipation |
3.3 W at 60 °C |
Thermal Dissipation |
11.25 BTU/hr |
Off-State Leakage |
1 mA per point |
On-State Drop |
2 V DC at 2 A |
Output Delay |
2 ms maximum, off-to-on and on-to-off |
Terminal Block |
1756-TBCH or 1756-TBS6H |
Operating Temperature |
0…60 °C (32…140 °F) |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The point of an isolated 125 V DC output card is that the field circuit is already at a voltage the controller cannot share. Eight separate outputs mean eight separate returns, and that is what allows one chassis to drive trip coils from two different battery strings without bonding them.
The 2 A per point rating at 60 °C is unusual for a 125 V DC output: most cards in this voltage class publish 1 A or less. It suits contactor coils and small DC solenoids directly, and the 4 A for 10 ms surge per point covers the inrush of a DC coil that a steady-state rating alone would not.
The published 2 V DC on-state drop at 2 A is the number to carry into the load voltage budget. A 125 V DC coil fed through this module sees about 123 V at full current, and a panel that sized its coil for exactly 125 V has to accept that difference.
Off-state leakage is 1 mA per point. On a contactor coil that is irrelevant; on a monitoring input or an intrinsic-safety barrier it can hold a circuit in the wrong state, and the design has to account for it rather than assume a perfect open.
Because the outputs are individually isolated, the module does not need a common return bus, and that changes the wiring plan: the terminal block carries eight separate DC feeds and eight separate returns rather than one group common. The drawing is longer, and the isolation is the reason.
At 3.3 W maximum dissipation and 11.25 BTU/hr the module is not a heat source in the rack, but the 210 mA at 5.1 V backplane draw has to be counted in the chassis power budget alongside every other card in the slot list.
The published off-state leakage, on-state drop and per-point current are the numbers that decide whether this module fits a 125 V DC circuit; the indicator only confirms the command.
| Indicator | State | Meaning and first action |
| OUT 0…7 | Will not turn off | Off-state leakage is 1 mA per point; on a high-impedance monitoring circuit that reads as a false on. |
| OUT 0…7 | Voltage at the load low | On-state drop is 2 V DC at 2 A; at 125 V DC that is measurable at the terminals and should be subtracted from the load voltage budget. |
| OK | Green | Module operating normally. |
| Several points at once | Dead | Check the chassis supply and the 5.1 V backplane draw of 210 mA per module before condemning the card. |
Output ratings and environmental limits per Rockwell publication 1756-TD002N-EN-E and 1756-IN050.
A dead output in this voltage class is usually the field device or the field fuse, not the module. Measure the voltage at the terminal with the output commanded on before replacing the card.
Check the 125 V DC supply under load. A battery string that reads 130 V open can fall below 90 V during a trip sequence, and the module will drop out exactly when the circuit is needed.
The module uses the 1756-TBCH or 1756-TBS6H terminal block; the wiring is individual per point, so photograph the terminations before pulling the card.
What is the 1756-OH8I?
A ControlLogix 125 V DC isolated output module with 8 individually isolated outputs.
What is the operating voltage range?
90…146 V DC, sourcing or sinking.
What current can each point carry?
2 A at 60 °C, with 8 A per module at 60 °C.
What surge current does it allow?
4 A for 10 ms per point, repeatable every 1 s at 60 °C.
What is the minimum load?
2 mA per point.
What does it draw from the backplane?
210 mA at 5.1 V DC and 2 mA at 24 V DC, 1.11 W total, 3.3 W maximum dissipation.
How much leakage is there when the output is off?
1 mA per point maximum.
What is the output delay?
2 ms maximum off-to-on and on-to-off.
Data sources. Technical values on this page come from Rockwell publications 1756-TD002N (1756 ControlLogix I/O Modules Specifications, November 2021) - 1756-OH8I technical, environmental and certification data; 1756-UM058 (ControlLogix Digital I/O Modules User Manual) and the manufacturer's product page for 1756-OH8I. Values re-checked 16 November 2026.