Product Details:
Payment & Shipping Terms:
|
The 1756-OG16 (also written 1756OG16) is the 16-point TTL-level DC output module: 4.5...5.5 V DC, 24 mA per point, with a user supply of 5.5 V DC at 384 mA maximum (60 °C), backplane 210 mA at 5.1 V DC and 2 mA at 24 V DC, isolation 250 V continuous basic outputs-to-backplane and 250 V basic output group-to-group (1756-IN062).
This is the only output in the family that does not switch a field voltage. It switches 5 V logic levels, 24 mA per point, and it needs the user to supply 5.5 V DC — up to 384 mA at 60 °C — on the field side. Without that supply the module has nothing to switch.
Backplane draw is 210 mA at 5.1 V DC, modest for sixteen points, and the isolation arrangement is 250 V to the backplane and 250 V between output groups, with the points inside a group sharing a return.
Its place in a ControlLogix panel is the interface to another logic family: a TTL input card on a third-party controller, a solid-state relay board, or a drive's discrete input block that expects 5 V levels. It is a level translator, not a power output.
1756-IB16 |
16 sinking inputs, 10...31.2 V DC 10 mA, backplane 100 mA, UPC 612598171293 |
In stock |
1756-IB16D |
16 diagnostic inputs, 10...30 V DC 13 mA, backplane 150 mA |
In stock |
1756-IB16I |
16 isolated inputs, 10...30 V DC 10 mA, backplane 135 mA |
In stock |
1756-IB16IF |
16 fast peer-control inputs, 10...30 V DC 5 mA, backplane 275 mA |
In stock |
1756-IB16ISOE |
16 sequence-of-events inputs, 10...55 V DC 5.1 mA, backplane 320 mA |
In stock |
1756-IB32 |
32 sinking inputs, 10...31.2 V DC 5.5 mA, backplane 120 mA, UPC 612598171309 |
In stock |
1756-IC16 |
16 inputs, 30...60 V DC, backplane per 1756-IN062 |
In stock |
1756-IG16 |
16 TTL inputs, backplane per 1756-IN062 |
In stock |
1756-IV16 |
16 inputs, 48 V DC, backplane per 1756-IN062 |
In stock |
Application |
Discrete output |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-OG16 |
Communication |
Backplane (producer/consumer) |
Display |
— |
Enclosure |
None (open-style) |
Interface |
Removable terminal block |
Mounting |
Chassis slot |
Number Of Channels |
16 |
Standard |
CE, UL, CSA, RCM |
Sub Brand |
ControlLogix |
Type |
Digital Output Module |
UNSPSC |
— |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN062 (DC digital I/O installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Use the OG16 where a ControlLogix chassis must hand on/off commands to 5 V logic: a TTL input card, a solid-state relay board, or a drive's discrete interface that is not 24 V tolerant.
Because the module switches only 24 mA, it is also the way to keep a high-count, low-current output list inside the chassis — indicator LEDs, logic gates, or opto inputs — with 384 mA of user supply covering sixteen points many times over.
Keep the 5 V runs short and away from contactor wiring. The module's isolation protects the backplane; it cannot protect the signal from noise injected downstream.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | User supply required | 5.5 V DC at up to 384 mA on the field side, supplied externally. |
| Check 3 | 24 mA per point | A TTL load budget, not a pilot duty rating — the number to use when counting solid-state relay inputs. |
| Check 4 | Group isolation only | 250 V between output groups; the points inside a group share a common. |
| Check 5 | Logic-level wiring | Short, screened runs, because 5 V levels are far more sensitive to noise than 24 V circuits. |
Specifications per Rockwell publication 1756-IN062 (ControlLogix DC Digital I/O Modules installation instructions); module behaviour per 1756-UM058 and technical data 1756-TD002 and 1756-IN050.
For 24 V DC pilot duty outputs, 1756-OB16E publishes 1 A per point with 2 A inrush.
For 24 V DC at 2 A, 1756-OB16I carries 250 V reinforced isolation.
For a 24 V DC sinking arrangement, 1756-OV16E publishes 10...30 V DC at 1 A pilot duty.
What is the 1756-OG16?
A 16-point TTL-level output module, 4.5...5.5 V DC at 24 mA per point, with a 5.5 V DC user supply of 384 mA.
Can it switch a 24 V DC load?
No. The output range is 4.5...5.5 V DC; 24 V loads belong on a standard DC output module.
Does it need an external supply?
Yes — 5.5 V DC at up to 384 mA at 60 °C on the user-supply terminals.
What is the per-point current?
24 mA.
How is it isolated?
250 V basic outputs-to-backplane and 250 V basic between output groups.
What is the backplane current?
210 mA at 5.1 V DC and 2 mA at 24 V DC.
What is its temperature code?
T4A under the North American classification.
Which document covers it?
1756-IN062, the ControlLogix DC digital I/O installation instructions.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-OG16. Values re-checked 15 November 2026.