Product Details:
Payment & Shipping Terms:
|
The 1756-OB8I (also written 1756OB8I) is the 8-point isolated DC output module. Its published isolation is 250 V continuous reinforced from outputs to backplane and 250 V continuous basic from output to output.
It has no output protection on the module; the documentation points to a fused interface module for point protection. The current TD002 edition no longer carries its current and dissipation figures, so this page states only what the publications still say.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
DC digital output module |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-OB8I |
Outputs |
8, individually isolated |
Isolation, Outputs to Backplane |
250 V continuous, reinforced insulation |
Isolation, Output to Output |
250 V continuous, basic insulation |
Output Protection |
None on the module; a fused IFM is recommended |
Backplane Current |
Not published in the current 1756-TD002 edition |
Power Dissipation |
Not published in the current 1756-TD002 edition |
Lifecycle Status |
Legacy; no longer listed in 1756-TD002 |
Publication |
1756-TD002, earlier edition (isolation and protection clauses) |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The isolation split is the reason this part is still specified in some retrofits. Reinforced insulation to the backplane and basic insulation between outputs are two different ratings, and they answer two different questions: chassis-level separation, and channel-to-channel separation.
Protection is the part that surprises people. There is no on-module protection, so a shorted solenoid takes the output with it. The documented approach is a fused interface module in front of the module, which moves the protection to a replaceable element rather than the card.
Because the part is no longer listed in the current 1756-TD002 edition, its backplane current and dissipation are not published here. Rather than quote values from a superseded table, this page leaves them out; the figures exist in earlier editions but cannot be verified against the current document.
Where a new build is being specified, the electronically fused 1756-OB8EI carries 8 individually isolated points with on-module electronic fusing, and the plain 1756-OB8 gives 2 A per point at 60 °C across 4 points per common. Those are the current choices; this module is the one already installed in the field.
The protection route is documented separately: Rockwell's 1492 interface module family includes fused variants, and 1492-TD008 is the publication that covers which fused IFM applies. Buying the field wiring through that module moves the fuse from a panel terminal strip to the interface module, which is what makes a point replaceable without touching the card.
The module reports no point-level diagnostics; with no on-module protection, a failed output usually means a failed field device as well.
| Indicator | State | Meaning and first action |
| Isolation fault appears between channels | — | Output-to-output isolation is basic, not reinforced; the reinforced rating applies from outputs to backplane. |
Facts on this page come only from the Rockwell publications named above; anything they do not state is marked as not published and 1756-IN050.
Bring protection with the module: specify a fused IFM rather than relying on the card.
Check whether the replacement is OB8EI (isolated, fused) or OB8 (common-per-four, no isolation).
Verify current figures against the edition of TD002 that covers your module, since the current edition omits them.
What is the 1756-OB8I?
An 8-point isolated DC output module for ControlLogix.
What isolation does it provide?
250 V continuous reinforced from outputs to backplane, and 250 V continuous basic from output to output.
Does it protect its outputs?
No, the module has no output protection; a fused IFM is recommended.
What current does it draw?
Not published in the current TD002 edition.
What is the current fused alternative?
1756-OB8EI, with 8 individually isolated points and electronic fusing.
Data sources. Technical values on this page come from Rockwell publications 1756-TD002 (ControlLogix I/O modules specifications, earlier edition) - OB8I isolation and output protection clauses; the current edition does not list this catalogue number and the manufacturer's product page for 1756-OB8I. Values re-checked 16 November 2026.