Product Details:
Payment & Shipping Terms:
|
The 1756-SPESMNSEXT (also written 1756SPESMNSEXT) is the extreme-temperature version of the removable safety-partner energy storage module: capacitor-based, no WallClockTime backup, 300 mA at 5.1 V DC, temperature code T4.
It is the part for GuardLogix-XT panels, where the controller and the safety partner operate outside the standard 0…60 °C enclosure rating.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
Energy storage module for safety partner |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-SPESMNSEXT |
Current Draw |
300 mA at 5.1 V DC |
Removable |
Yes |
WallClockTime Backup |
No |
Memory Limit |
1756-L73 (8 MB) or smaller |
Type |
Capacitor energy storage module |
Sub Brand |
GuardLogix |
Enclosure |
None (open-style) |
Temperature Code |
T4 |
Operating Temperature |
0…60 °C (32…140 °F) |
Non-Operating Temperature |
-40…85 °C (-40…185 °F) |
Relative Humidity |
5…95%, non-condensing |
Vibration |
2 g @ 10…500 Hz |
Shock, Operating |
30 g |
Shock, Non-Operating |
50 g |
Certification |
c-UL-us, CE, RCM, ATEX/IECEx zone 2, UKEx, UKCA, KC, CCC |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The XT suffix is not cosmetic. It marks the variant that belongs in a ControlLogix-XT or GuardLogix-XT chassis, and the standard SPESMNSE is not the substitute for it in a -25…+70 °C installation.
The transport rule is identical to the standard version: residual stored energy must fall to 40 µJ or less, which the publication sets at a wait of at least 20 minutes before the module or the controller is taken out of the application.
The same memory restriction applies — a 1756-L73 (8 MB) or smaller controller. In an XT panel that usually means the 1756-L73XT, which is the 8 MB XT controller.
Current draw is 300 mA at 5.1 V, identical to the non-XT removable module; the extreme-temperature qualification changes the environmental envelope, not the electrical figure.
There is no WallClockTime backup in this ESM either. An application that depends on the clock surviving a power cycle needs the capacitor ESM supplied with the controller, not this part.
Certification follows the safety-partner ESM family: c-UL-us with Class I Division 2, CE to EN 61326-1 and EN 61131-2, RCM, ATEX and IECEx zone 2 (Ex ec IIC T4 Gc), UKEx, UKCA, KC and CCC, with temperature code T4 and an open-style enclosure.
An energy storage module has no status display; the relevant facts are the depletion wait before transport, whether the part is removable, and whether USB and SD access are blocked.
| Indicator | State | Meaning and first action |
| Safety partner reports no partner after a swap | — | The ESM belongs to the L7SP safety partner, not to the standard controller; a standard 1756-ESM in that slot is the wrong part. |
| USB port dead after maintenance | — | 1756-SPESMNRM and SPESMNRMXT permanently disable the USB connection and SD card use by design. |
| SD card will not come out | — | An SD card installed before the NRM ESM was fitted remains functional but is no longer removable. |
Description, current draw and environmental figures per Rockwell publication 1756-TD001-EN-P and 1756-IN050.
Match the XT suffix to the chassis. A standard ESM in an XT panel is outside the published envelope.
Observe the 20 minute depletion wait before removal from the application.
Verify the controller memory size; the L73 8 MB limit is published for this family.
What is the 1756-SPESMNSEXT?
The extreme-temperature removable capacitor ESM for the 1756-L7SPXT safety partner.
What current does it draw?
300 mA at 5.1 V DC.
Does it back up the WallClockTime?
No.
How long before removal?
At least 20 minutes, until residual energy is 40 µJ or less.
Which chassis is it for?
ControlLogix-XT and GuardLogix-XT chassis and their -XT controllers.
Is it the same as 1756-SPESMNSE?
Electrically similar, but the XT variant covers the extended temperature envelope.
What is the temperature code?
T4.
Which controller memory size is supported?
1756-L73 (8 MB) or smaller.
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) - GuardLogix 5570 safety partner energy storage modules, current draw, environmental and certification data for 1756-SPESMNSEXT and the manufacturer's product page for 1756-SPESMNSEXT. Values re-checked 16 November 2026.