Product Details:
Payment & Shipping Terms:
|
The 1756-SPESMNRMXT (also written 1756SPESMNRMXT) is the extreme-temperature, non-removable energy storage module for the GuardLogix-XT safety partner. It permanently prevents USB connection and SD card use and draws 330 mA at 5.1 V DC.
It combines the two constraints that appear together in harsh-environment cabinets: extended temperature and permanent access restriction.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
Energy storage module for safety partner |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-SPESMNRMXT |
Current Draw |
330 mA at 5.1 V DC |
Removable |
No |
WallClockTime Backup |
No |
Memory Limit |
1756-L73 (8 MB) or smaller |
Type |
Capacitor energy storage module |
Sub Brand |
GuardLogix |
Enclosure |
None (open-style) |
Temperature Code |
T4 |
Operating Temperature |
0…60 °C (32…140 °F) |
Non-Operating Temperature |
-40…85 °C (-40…185 °F) |
Relative Humidity |
5…95%, non-condensing |
Vibration |
2 g @ 10…500 Hz |
Shock, Operating |
30 g |
Shock, Non-Operating |
50 g |
Certification |
c-UL-us, CE, RCM, ATEX/IECEx zone 2, UKEx, UKCA, KC, CCC |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Both properties are fixed at build time. The module is non-removable and the USB and SD access block is permanent, so the decision is made when the XT panel is specified, not during commissioning.
The SD card rule is the one that catches maintenance teams: a card installed before the NRM module was fitted remains functional but cannot be removed afterwards, and a card fitted after it is unusable.
Current draw is 330 mA at 5.1 V, the same as the non-XT security module and 30 mA above the removable NSE variants. On a large XT chassis this is a rounding item, but it is published for a reason — the value is used in supply sizing.
The transport depletion rule published for the removable modules does not apply here because the part does not come out; service means replacing the controller assembly.
Wireless or USB-based service access is exactly what this part removes. An XT installation that expects to download over USB after commissioning should not specify it.
Environmental and certification data follow the safety-partner ESM family, with zone 2 certification (Ex ec IIC T4 Gc), c-UL-us Class I Division 2, CE, RCM, UKEx, UKCA, KC and CCC.
An energy storage module has no status display; the relevant facts are the depletion wait before transport, whether the part is removable, and whether USB and SD access are blocked.
| Indicator | State | Meaning and first action |
| Safety partner reports no partner after a swap | — | The ESM belongs to the L7SP safety partner, not to the standard controller; a standard 1756-ESM in that slot is the wrong part. |
| USB port dead after maintenance | — | 1756-SPESMNRM and SPESMNRMXT permanently disable the USB connection and SD card use by design. |
| SD card will not come out | — | An SD card installed before the NRM ESM was fitted remains functional but is no longer removable. |
Description, current draw and environmental figures per Rockwell publication 1756-TD001-EN-P and 1756-IN050.
Plan replacement at controller level; the module cannot be removed on its own.
Verify the XT suffix against the chassis before ordering.
Confirm that no field service procedure depends on the USB port, which this module disables permanently.
What is the 1756-SPESMNRMXT?
The extreme-temperature, non-removable capacitor ESM for the GuardLogix-XT safety partner.
What current does it draw?
330 mA at 5.1 V DC.
Can USB be used after fitting it?
No — the USB connection and SD card use are permanently prevented.
Is it removable?
No.
What happens to an SD card already installed?
It remains functional but is not removable.
Which system does it belong to?
A GuardLogix-XT system with a 1756-L7SPXT safety partner.
What is the temperature code?
T4.
What is the non-XT equivalent?
1756-SPESMNRM.
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) - GuardLogix 5570 safety partner energy storage modules, current draw, environmental and certification data for 1756-SPESMNRMXT and the manufacturer's product page for 1756-SPESMNRMXT. Values re-checked 16 November 2026.