Product Details:
Payment & Shipping Terms:
|
The 1756-RM2XT (also written 1756RM2XT) is the ControlLogix-XT redundancy module. Electrically it matches the standard 1756-RM2 at 1.16 A on 5.1 V DC and 3.4 mA on 24 V DC; what changes is the chassis it fits and the environment it survives.
It is the part for redundant pairs built in 1756-A7XT or 1756-A10XT chassis, where the standard RM2 is outside the published mounting scope.
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
Controller redundancy module, XT |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-RM2XT |
Current Draw |
1.16 A @ 5.1 V DC; 3.4 mA @ 24 V DC |
Power Dissipation |
6 W, max |
Thermal Dissipation |
21 BTU/hr |
Slot Width |
1 slot |
Module Location |
Chassis-based, any slot |
Chassis |
1756-A7XT, 1756-A10XT |
Controller Families |
ControlLogix 5570, ControlLogix 5580 |
Connector Cables |
1756-RMC1 (1 m), 1756-RMC3 (3 m), 1756-RMC10 (10 m) |
Power Supply, Standard |
1756-PAXT, 1756-PBXT |
Mounting |
ControlLogix-XT chassis, single-slot |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The chassis list is short and specific: 1756-A7XT and 1756-A10XT. A standard 1756-RM2 does not appear on that list, and a mixed rack of standard and XT chassis is not a supported redundant pair.
The supply list changes with it. The XT pair is fed from 1756-PAXT and 1756-PBXT, and the publication lists no redundant supply set for the XT variant — the redundancy in the supply path is a separate decision.
Power and thermal figures are identical to the standard module: 1.16 A at 5.1 V, 3.4 mA at 24 V, 6 W maximum dissipation, 21 BTU/hr. Two modules still cost 2.32 A on the 5.1 V rail.
The pairing rule does not relax in XT installations. Both modules must carry the same catalogue number, so an XT pair is two RM2XT modules, not one RM2 plus one RM2XT.
Cabling is shared with the rest of the family: 1756-RMC1, RMC3 and RMC10, ordered separately. In a cold or hot enclosure the cable is usually the first item to be re-specified, because its service temperature is outside the module's rating.
Supported controllers are ControlLogix 5570 and 5580, the same as the standard module, so an XT redundancy upgrade does not change the controller family.
A redundancy fault is almost always a pairing, fiber or supply problem; the module pair tolerates a failed chassis, not a mismatched cable.
| Indicator | State | Meaning and first action |
| Redundancy module shows a link fault | — | Check the LC connector and the fiber type against the SFP fitted; singlemode and multimode fiber are not interchangeable. |
| Module draws more than expected from the chassis supply | — | 1756-RM2 draws 1.16 A at 5.1 V plus 3.4 mA at 24 V, and 1756-RM3 draws 1 A at 5.1 V plus 5 mA at 1.2 V. |
| Swap of one chassis does not restore redundancy | — | The cable must be re-terminated on the replacement module; a loose LC ferrule reads as a link failure even when the module is healthy. |
Current draw, dissipation, connector and cable data per Rockwell publication 1756-TD001-EN-P and 1756-IN050.
Match the XT suffix to the chassis before ordering; the mounting list is published and short.
Keep both modules the same catalogue number when replacing one of a pair.
Recheck the XT supply loading after adding the second module.
What is the 1756-RM2XT?
The redundancy module for ControlLogix-XT redundant chassis pairs.
What current does it draw?
1.16 A at 5.1 V DC and 3.4 mA at 24 V DC.
Which chassis does it fit?
1756-A7XT and 1756-A10XT.
Which power supplies are used?
1756-PAXT and 1756-PBXT.
Is it different from 1756-RM2 electrically?
No, the current and dissipation figures are the same.
Which cables does it use?
1756-RMC1, RMC3 or RMC10, ordered separately.
How much does it dissipate?
6 W maximum, 21 BTU/hr.
Which controllers are supported?
ControlLogix 5570 and 5580.
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) - redundancy module current draw, dissipation, chassis and cable data for 1756-RM2XT and the manufacturer's product page for 1756-RM2XT. Values re-checked 16 November 2026.