Product Details:
Payment & Shipping Terms:
|
The 1794-TBNK is the coated NEMA-style base: 16 I/O, 2 common and 2 +V terminals, rated to 264V AC/DC and shipped with a cover over the I/O wiring.
264V is what makes the NEMA base different from the rest of the family. It is the base for 120/220V AC modules where the field wiring itself sits at line potential.
| 1794-TB2 | 16-terminal cage clamp base, 2-wire, up to 132V AC | IN STOCK |
| 1794-TB3 | 16-terminal cage clamp base, 3-wire devices | IN STOCK |
| 1794-TB3S | 16-terminal spring clamp base, 3-wire devices | IN STOCK |
| 1794-TB32 | 32-terminal cage clamp base for 32-point modules | IN STOCK |
| 1794-TB32S | 32-terminal spring clamp base for 32-point modules | IN STOCK |
| 1794-TB3T | temperature base with two cold junction compensation sets | IN STOCK |
| 1794-TB3TS | spring clamp temperature base with CJC sets | IN STOCK |
| 1794-TB3G | grounded screw clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TB3GS | grounded spring clamp base, 36 I/O, 10 chassis ground | IN STOCK |
| 1794-TBKD | cage clamp base with 16 knife disconnects | IN STOCK |
| 1794-TBN | NEMA-style screw clamp base, up to 264V AC/DC | IN STOCK |
| 1794-TBNF | fused NEMA-style base, eight 5 x 20 mm fuses | IN STOCK |
| 1794-TB37DS | 37-pin D-shell termination for digital and analog modules | IN STOCK |
| 1794-TB62DS | 62-pin D-shell termination for digital and analog modules | IN STOCK |
Application |
FLEX I/O NEMA-style terminal base, high voltage |
Cat Num |
1794-TBNK |
Brand Name |
Rockwell |
Termination |
Screw clamp, NEMA style, with wiring cover |
Connections |
16 I/O, 2 common, 2 +V |
Voltage |
Up to 264V AC/DC |
Wire size |
0.34...3.3 mm2 (22...12 AWG), 75 deg C or greater |
Dimensions |
94 x 94 x 69 mm |
Operating temperature |
-20...70 deg C |
Coating |
Conformal |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
16 I/O, 2 common and 2 +V terminals, NEMA-style screw clamp with larger gauge capacity.
264V AC/DC rating on the terminals, above the 132V AC / 156V DC of the cage clamp family.
A cover for I/O wiring is part of the base, which is what the NEMA designation is for.
-20...70 deg C with the K coating over the assembly.
Terminal voltage rating is not a module rating; the installed module must also be rated for the circuit.
Field wiring at line potential needs the cover and separation from low-voltage signals.
2 common and 2 +V only, so this base is not a 16-point 3-wire digital base.
The 1794-TBN is the uncoated equivalent at the same 264V rating.
120/220V AC input and output modules in a FLEX I/O island.
Panels where field circuits are at line voltage and a covered termination is required.
Not for 32-point cards; the 1794-TB32 is the 32-point base.
Not for fused output protection; the 1794-TBNF carries eight fuses.
35 x 7.5 mm DIN rail with 25 mm air space.
Zinc-plated, yellow-chromated steel rail for chassis grounding.
1794-NM1 panel kit where no rail is used.
One end cap per system, bases plugging together into the backplane.
1794-TBN: uncoated NEMA base, 264V AC/DC.
1794-TBNK: the same base with conformal coating.
1794-TBNF: fused NEMA base, eight 5 x 20 mm fuses.
Choose the K version for -XT modules and condensing cabinets.
What voltage is the 1794-TBNK rated for?
Up to 264V AC/DC at the terminals.
How many terminals does it have?
16 I/O, 2 common and 2 +V.
Does it include a wiring cover?
Yes; the cover is part of the NEMA-style construction.
What is the K suffix?
Conformal coating, paired with -XT modules.
What is the operating temperature?
-20...70 deg C.
Can it take 32-point modules?
No; use the 1794-TB32 for 32-point cards.
1794-TBNK is a FLEX I/O terminal base unit, not an I/O module. It is the part that carries the field terminals, plugs into the adjacent base to form the backplane, and holds the module on top. The termination type here is Screw clamp, NEMA style with 16 I/O, 2 common, 2 +V.
| Attribute | Value |
| Catalog number | 1794-TBNK |
| Termination type | Screw clamp, NEMA style |
| Connections | 16 I/O, 2 common, 2 +V |
| Current capacity, maximum | module dependent |
| Wiring category | module dependent |
| Field voltage | 264V AC / DC |
| Operating temperature | -20...+70 C |
| Purpose in the range | The conformal coated version of the 1794-TBN. |
The conductor range for this base is 0.34 to 3.3 mm2 (22 to 12 AWG) solid or stranded copper rated 75 C or greater, with 1.2 mm maximum insulation, with a maximum current capacity of module dependent across the base. Those figures are the base rating and not the module rating: a 16 point module on a 10 A base is still limited by the module output current per channel.
Selecting a base is a compatibility step, not a preference step. The module data sheet names the bases that are permitted for it, and a base outside that list may key differently, may not carry the required common and voltage terminals, or may not be rated for the field voltage of the module.
Conformal coated variants carry a K suffix and exist because the same base can be asked to survive washdown, condensate, or corrosive atmosphere. Ordering the uncoated base and treating it in the field is not equivalent and does not carry the same published rating.
FLEX I/O bases and modules are separate line items on a purchase order, and the price of getting that wrong is a second shipment: a module without its base cannot be installed, and a base of the wrong termination type cannot be reworked in the field because the module keys to the base family.
For a retrofit into an existing slice, the addressing is decided by position rather than by catalog number: FLEX I/O assigns the module its place in the rack by the order of the bases on the rail, so inserting a module in the middle shifts the addresses of everything to its right and requires the program to be re-checked.
On the 32 point bases the common and voltage terminals are grouped in eight pairs rather than eighteen, which is why the 32 point digital modules can mix sinking and sourcing groups in one slice and why the terminal numbering on the drawing does not follow the 16 point pattern.
Any FLEX I/O position is a pair on the purchase order: one base, one module. Stocking modules without bases, or bases without the matching modules, produces a slice that cannot be commissioned, and the two part numbers are never interchangeable across the 8, 16 and 32 point families.
Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.
Related models, options and spare parts for this range are listed in the Allen-Bradley Flex I/O 1794 modules category.