The 1794-IP4 puts four independent counters in one FLEX I/O slot at 100 kHz, with 6V on-state and 3V off-state thresholds and overflow detection referenced to the internal clock.
Four channels is the practical difference from the two-channel cards: four meters, four shafts or four production lines counted from one base.
| 1794-IJ2 | 2-channel frequency input module, 1...32 kHz | IN STOCK |
| 1794-IJ2XT | 2-channel frequency input module, extended temperature | IN STOCK |
| 1794-VHSC | 2-axis very high speed counter, 1 MHz, 8 compare windows | IN STOCK |
| 1794-ID2 | 2-channel counter with A, B, Z and gate inputs | IN STOCK |
| 1794-IP4 | 4-channel counter module, 100 kHz | IN STOCK |
Application |
FLEX I/O counter, 1794 terminal base |
Cat Num |
1794-IP4 |
Brand Name |
Rockwell |
Channels |
4 counter channels |
Frequency |
100 kHz |
Input thresholds |
6V on-state, 3V off-state |
Sensor current |
3, 9 and 15 mA |
Overflow detection |
65 ms at the 1 MHz clock, 6.5 ms at 10 MHz |
Operating temperature |
0...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Four counter channels at 100 kHz in a single slot, which is twice the channel count of the 1794-ID2.
6V on-state and 3V off-state thresholds define the sensor interface; a 5V encoder output is marginal against a 6V threshold and a 24V sensor needs an interface.
Sensor current of 3, 9 and 15 mA at the corresponding supply levels is the published drive capability.
Overflow is detected at 65 ms with the 1 MHz clock and 6.5 ms with the 10 MHz clock, which is how a counter that wraps is reported rather than silently lost.
100 kHz is the ceiling on every channel, so four fast inputs do not share a bandwidth pool.
The overflow window is the number to check against the process: a count that can wrap inside 65 ms needs a wider preset, not a faster card.
0...55 deg C operating range places the card in a heated enclosure.
Thresholds at 6V on and 3V off give 3V of hysteresis, which is what keeps a noisy signal from double-counting.
Check the sensor's guaranteed output at the lowest supply voltage, not at nominal 24V; that is where a marginal 5V encoder drops under the 6V threshold.
One terminal base serves four counters, so the field wiring is denser than on the two-channel cards and the schedule is drawn before installation.
Shielded twisted pair per channel with the shield at the panel, and the pairs kept apart from drive feeders.
Verify each channel with a known pulse source before the line runs, because a threshold problem looks like a count problem.
Field power removed before insertion, as with every module on a 1794 base.
Four independent counters on one island — meters, shafts or line totals.
Simple totalising without quadrature or compare windows.
Not for quadrature position; the 1794-VHSC decodes A, B and Z at up to 1 MHz.
Not for sine wave pickups; the 1794-IJ2 accepts 1...32 kHz analogue input with wire-off detection.
1794-IP4: four channels, 100 kHz, 6V/3V thresholds, overflow detection, no gate or index inputs published.
1794-ID2: two channels with A, B, Z and gate inputs and a 304.8 m cable allowance.
1794-VHSC: two axes to 1 MHz with eight compare windows and two outputs.
1794-IJ2: two frequency channels for 1...32 kHz pickups with two isolated outputs.
How many counters has the 1794-IP4?
Four independent counter channels.
What is the maximum count rate?
100 kHz on each channel.
What are the input thresholds?
6V on-state and 3V off-state, with 3, 9 or 15 mA sensor current.
How is overflow reported?
Detected within 65 ms at the 1 MHz clock or 6.5 ms at 10 MHz.
What is the operating temperature?
0...55 deg C.
How does it differ from the 1794-ID2?
Four channels instead of two, without the A, B, Z and gate inputs of the ID2.