Product Details:
Payment & Shipping Terms:
|
The 1794-IM16 is the sixteen-point 240V AC input card, at 22.2 kOhm input impedance and 6 W dissipation, on the 1794-TBN or -TBNK base.
It suits a 240V panel that needs point density: sixteen mains-voltage signals on one slot, with the field circuit terminated on the fused TBN base.
| 1794-IA8 | 8-point 120V AC input module | IN STOCK |
| 1794-IA8I | 8-point 120V AC input module, 1240V isolation | IN STOCK |
| 1794-IA16 | 16-point 120V AC input module | IN STOCK |
| 1794-IA16K | 16-point 120V AC input module, conformal coated | IN STOCK |
| 1794-IM8 | 8-point 240V AC input module | IN STOCK |
| 1794-IM16 | 16-point 240V AC input module | IN STOCK |
| 1794-OA8 | 8-point 120V AC output module | IN STOCK |
| 1794-OA8I | 8-point 120V AC isolated output module | IN STOCK |
| 1794-OA8K | 8-point 120V AC output module, conformal coated | IN STOCK |
| 1794-OA16 | 16-point 220V AC output module | IN STOCK |
| 1794-OA16K | 16-point 220V AC output module, conformal coated | IN STOCK |
| 1794-OM8 | 8-point 240V AC output module | IN STOCK |
| 1794-OM16 | 16-point 240V AC output module | IN STOCK |
Application |
FLEX I/O digital input, 1794 terminal base |
Cat Num |
1794-IM16 |
Brand Name |
Rockwell |
Inputs |
16, AC |
Input voltage |
240V AC nominal |
Input impedance |
22.2 kOhm |
Isolation |
Field to system, type tested |
Power dissipation |
6 W (20.47 BTU/hr) |
Terminal base |
1794-TBN, -TBNK |
Operating temperature |
0...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
16 channels at 240V AC nominal with a 22.2 kOhm input impedance, the same order as the 8-point card and half the per-point heat.
6 W (20.47 BTU/hr) for sixteen channels is only 1.3 W more than the eight-point 1794-IM8 — the modules share the same input stage, and the density is what changes.
One slot for sixteen mains signals is the reason this card exists: a panel with two full rows of 240V devices fits one island.
A 240V input card in a 120V panel is a maintenance trap: every channel reads off and the card is blamed before the voltage class is checked.
The published 240V threshold policy leaves a wide band between on and off, which is what stops a marginal supply from producing chatter on the controlled bit.
Because the field terminals sit on the base, a fuse change at the TBN base is a two-screw job rather than a rewire of sixteen conductors.
Two input rows on one slot usually removes a whole island from the drawing, including its adapter and its rail length.
The 240V threshold policy is the same as the 1794-IM8: a high on-voltage and a low off-voltage, sized so a sagging supply still reads and induced noise does not.
22.2 kOhm limits the current a field switch has to carry, which keeps a mechanical contact clean and lets a small pilot device drive the input.
Shared common. A grounded field device on one channel grounds the common of all sixteen; keep the field circuit floating where the panel allows.
Keep 240V conductors in a separate duct from analog and communication wiring; the input filter is not a substitute for separation.
1794-TBN or 1794-TBNK, the base with fused terminals and optional knife disconnects.
Field terminals live on the base, so the card can be exchanged without disturbing sixteen field wires.
Keying decides which module can enter which base; check the key before insertion rather than after a bent connector.
0...55 deg C operating range, with the general FLEX I/O storage, humidity, vibration and shock ratings.
240V control circuits in process panels where starters, float switches and pressure switches are wired at mains voltage.
Retrofit of relay logic. Sixteen existing 240V contacts land on one card, and the relay panel comes out.
Not interchangeable with 120V cards. The on threshold makes a 120V circuit read off; the product line splits at the voltage class.
Confirm the line voltage at the terminals and the neutral reference before the first power-up; a 240V card on a 120V circuit reads everything off.
Watch the sixteen yellow LEDs as each field device is operated, which separates a field fault from a mapping fault in one pass.
Document the fuse rating at the TBN base in the panel drawing, because the base, not the card, carries the field protection.
How many inputs has the 1794-IM16?
Sixteen 240V AC inputs at 22.2 kOhm input impedance.
Which bases are used?
1794-TBN and 1794-TBNK, the fused-terminal bases with optional knife disconnects.
What is the module dissipation?
6 W, equal to 20.47 BTU/hr.
What temperature range does it accept?
0...55 deg C operating, with the general FLEX I/O environmental ratings.
Does it work on a 120V circuit?
No. The card is a 240V AC product; use 1794-IA8 or 1794-IA16 for 120V circuits.
Is the input isolated channel to channel?
No. Field to system isolation only; the sixteen channels share a common.