Product Details:
Payment & Shipping Terms:
|
The 1794-IF2XOF2IXT is the extended-temperature isolated two-in/two-out analog module: -20...70 deg C, conformally coated, and a 75 mm deep body.
It takes the isolated loop pair into an unheated panel, which the standard card's 55 deg C ceiling does not allow.
| 1794-IE8 | 8-channel analog input module | IN STOCK |
| 1794-IE8XT | 8-channel analog input module, extended temperature | IN STOCK |
| 1794-IE8H | 8-channel HART analog input module | IN STOCK |
| 1794-IE12 | 12-channel analog input module | IN STOCK |
| 1794-IE12K | 12-channel analog input module, conformal coated | IN STOCK |
| 1794-IF4I | 4-channel isolated analog input module | IN STOCK |
| 1794-IF4IXT | 4-channel isolated analog input, extended temperature | IN STOCK |
| 1794-IF4ICFXT | 4-channel isolated analog input, conformal coated | IN STOCK |
| 1794-IF8IH | 8-channel HART isolated analog input module | IN STOCK |
| 1794-IR8 | 8-channel RTD input module | IN STOCK |
| 1794-IRT8 | 8-channel thermocouple/RTD input module | IN STOCK |
| 1794-IRT8XT | 8-channel thermocouple/RTD input, extended temperature | IN STOCK |
| 1794-IT8 | 8-channel thermocouple/mV input module | IN STOCK |
| 1794-IE8XOE4 | 8-input, 4-output analog combination module | IN STOCK |
| 1794-IE4XOE2 | 4-input, 2-output analog combination module | IN STOCK |
| 1794-IF2XOF2I | 2-input, 2-output isolated analog combination module | IN STOCK |
| 1794-OE4 | 4-channel analog output module | IN STOCK |
| 1794-OE12 | 12-channel analog output module | IN STOCK |
Application |
FLEX I/O isolated analog combination, 1794 terminal base |
Cat Num |
1794-IF2XOF2IXT |
Brand Name |
Rockwell |
Channels |
2 inputs and 2 outputs, channel-to-channel isolated |
Input ranges |
0...20 mA, +/-10V DC |
Input resolution |
16 bits; 0.156/0.313 mV, 0.320/0.640 uA |
Input conversion |
Sigma-delta, 2.5, 5.0 or 7.5 ms |
Input accuracy |
0.1% of full scale |
Input drift |
0.0038, 0.0028, 0.0025 or 0.0012 %FS per deg C |
Output resolution |
15 bits plus sign; 0.656 uA, 0.320 mV |
Output conversion |
Digital-to-analog converter, 2.5 or 5.0 ms |
Load |
0...750 Ohm current; 3 mA maximum on voltage output |
Isolation |
120V continuous with TB3/TB3S/TB2/TB3T/TB3TS, 250V with TBN; 1500V AC 60 s, 2550V DC 1 s |
External supply current |
150 mA at 24V DC |
Power dissipation |
3.3 W at 31.2V DC (11 BTU/hr) |
Operating temperature |
-20...70 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
-20...70 deg C operating range and conformal coating are the two differences from the standard 1794-IF2XOF2I.
75 mm body depth — deeper than a standard module, so base clearance and enclosure depth need checking before the rail is cut.
Channel-to-channel isolation at 120V or 250V depending on the terminal base, with 1500V AC for 60 s and 2550V DC for 1 s type tests.
Two inputs and two outputs, each isolated, in one slot.
16-bit sigma-delta input at 2.5, 5.0 or 7.5 ms with 0.1% of full scale accuracy.
Drift from 0.0038 to 0.0012 %FS per deg C depending on the filter setting — over 90 deg C of range, the filter choice matters more than on the standard card.
15 bits plus sign on the output at 0.656 uA or 0.320 mV per count, DAC at 2.5 or 5.0 ms.
0...750 Ohm current load and 3 mA maximum on voltage output.
150 mA at 24V DC and 3.3 W (11 BTU/hr) is the electrical budget, unchanged from the standard module.
An unheated enclosure must shed 11 BTU/hr without a fan, which is usually easy and occasionally the deciding number.
Storage -40...85 deg C, 5...95% RH non-condensing are the environmental limits outside operation.
Isolation is a base-dependent rating, so the 250V case needs a TBN base in the bill of materials.
Two inputs and two outputs share one slot and one supply, which is why the 150 mA consumption does not rise with the extended temperature option.
Each channel has its own return — do not common the four returns at the terminals, which would defeat the isolation.
Shielded pair per loop with the shield at the panel, and no shield connection at the field device.
Verify the base type before wiring: a TBN base is required for a 250V circuit.
Conformal coating and cold start: check each channel against a known source at low temperature before the first production run.
Isolated loops in cold or hot locations, -20...70 deg C.
Two-loop valve or transmitter stations in an unheated cabinet.
Not for dense analog I/O; the 1794-IE8XOE4 offers twelve channels per slot without isolation.
Not for HART; isolated HART outputs are on the 1794-OF8IH.
How does the 1794-IF2XOF2IXT differ from the standard module?
It is rated -20...70 deg C, conformally coated, and 75 mm deep; the channel specifications are the same.
What isolation does it provide?
Channel-to-channel at 120V continuous with TB3-family bases or 250V with TBN; type tested at 1500V AC for 60 s.
What resolution does the input offer?
16 bits with sigma-delta conversion at 2.5, 5.0 or 7.5 ms.
What load can the outputs drive?
0...750 Ohm on current output and 3 mA maximum on voltage output.
What current does the module draw?
150 mA at 24V DC, dissipating 3.3 W at 31.2V DC.
Why 75 mm deep?
The isolated extended-temperature body is deeper than a standard module, so base clearance must allow it.
What is the accuracy of the input?
0.1% of full scale, with drift between 0.0038 and 0.0012 %FS per deg C depending on the filter setting.