Product Details:
Payment & Shipping Terms:
|
The 1794-APB Series B is the PROFIBUS DP adapter for FLEX I/O, running any rate up to 12.0 Mbit/s through a 9-pin D-shell drop connector, with node addresses 00...99 on the faceplate thumbwheels.
Because PROFIBUS needs a GSD file rather than an EDS, commissioning starts with the GSD from Rockwell's network site — not with RSNetWorx.
| 1794-AENT | EtherNet/IP adapter, single RJ45, 8 modules | IN STOCK |
| 1794-AENTR | dual-port EtherNet/IP adapter, redundancy capable | IN STOCK |
| 1794-AENTRXT | dual-port EtherNet/IP adapter, extended temperature | IN STOCK |
| 1794-ACN15 | ControlNet adapter, 15 Mbps, 8 modules | IN STOCK |
| 1794-ACN15K | ControlNet adapter, 15 Mbps, conformal coated | IN STOCK |
| 1794-ACNR | ControlNet adapter with redundant media | IN STOCK |
| 1794-ACNR15XT | ControlNet adapter, redundant media, extended temperature | IN STOCK |
| 1794-ACN | ControlNet adapter module, 8 modules | IN STOCK |
| 1794-ADN | DeviceNet adapter, 8 modules | IN STOCK |
| 1794-ADNK | DeviceNet adapter, conformal coated | IN STOCK |
| 1794-APB | Profibus DP adapter, 8 modules | IN STOCK |
| 1794-APBDPV1 | Profibus DP-V1 adapter, 8 modules | IN STOCK |
| 1794-ASB | Remote I/O adapter, 8 modules | IN STOCK |
| 1794-ASB2 | Remote I/O adapter, extended functionality | IN STOCK |
| 1794-ASBLT | Remote I/O adapter with built-in termination | IN STOCK |
Application |
FLEX I/O PROFIBUS adapter |
Cat Num |
1794-APB Series B |
Brand Name |
Rockwell |
I/O module capacity |
8 modules |
Input voltage |
24V DC nom, 19.2...31.2V DC |
Input current |
450 mA max, 330 mA at 24V DC |
Inrush current |
23 A for 2 ms |
Communication rate |
Up to 12.0 Mbit/s |
Node address |
00...99 by thumbwheel |
Flexbus output |
640 mA max |
Operating temperature |
0...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Any rate up to 12.0 Mbit/s, set on the network master, not on the adapter.
9-pin D-shell connector: pin 1 shield to earth, pin 3 B/B' RXD/TXD-P, pin 5 DGND, pin 8 A/A' RXD/TXD-N.
Node address 00...99 on thumbwheel switches with + and - buttons.
GSD files are required and are published at the Rockwell networks GSD page.
19.2...31.2V DC at 450 mA maximum, 330 mA typical at 24V DC.
23 A inrush for 2 ms per adapter on the 24V supply.
640 mA maximum Flexbus output.
Isolation tested at 850V DC for 1 s between user power and Flexbus.
87 x 68 x 69 mm, the narrow PROFIBUS envelope.
7.68 W dissipation and 26 BTU/hr at 19.2V DC.
0...55 deg C operating, -40...85 deg C storage, 5...95 percent noncondensing humidity.
0.8 N*m terminal torque, DC power wiring under 3 m.
Status indicator: off no power, solid green normal, flashing red/off recoverable fault.
PROFIBUS indicator: solid green when data is being transmitted, solid red for an unrecoverable fault.
Recoverable faults include invalid parameter data and invalid check configuration data.
Class I Division 2 Groups A to D approval when marked.
FLEX I/O islands on a PROFIBUS DP segment.
Panels with a Siemens or other DP master.
Not DP-V1; the 1794-APBDPV1 is the extended-function part.
Not EtherNet/IP, ControlNet or DeviceNet.
What is the maximum PROFIBUS rate?
Up to 12.0 Mbit/s.
How is the node address set?
Thumbwheel switches on the front, valid 00...99.
What connector does it use?
A 9-pin D-shell PROFIBUS drop connector.
How many modules can it carry?
8 FLEX I/O modules.
What is the input current?
450 mA maximum, 330 mA at 24V DC, with 23 A inrush for 2 ms.
What file does the master need?
A GSD file, available from the Rockwell networks GSD page.