Product Details:
Payment & Shipping Terms:
|
The 1794-OE12 puts twelve analog outputs on one FLEX I/O slot, at 0.1% of full scale accuracy and a 0.641 uA or 320 uV per count resolution, with an out-of-range bit on every channel.
Density is the argument: twelve valve positioners or drive references in one slot, where three four-channel cards would occupy three bases and three rail lengths.
| 1794-IE8 | 8-channel analog input module | IN STOCK |
| 1794-IE8XT | 8-channel analog input module, extended temperature | IN STOCK |
| 1794-IE8H | 8-channel HART analog input module | IN STOCK |
| 1794-IE12 | 12-channel analog input module | IN STOCK |
| 1794-IE12K | 12-channel analog input module, conformal coated | IN STOCK |
| 1794-IF4I | 4-channel isolated analog input module | IN STOCK |
| 1794-IF4IXT | 4-channel isolated analog input, extended temperature | IN STOCK |
| 1794-IF4ICFXT | 4-channel isolated analog input, conformal coated | IN STOCK |
| 1794-IF8IH | 8-channel HART isolated analog input module | IN STOCK |
| 1794-IR8 | 8-channel RTD input module | IN STOCK |
| 1794-IRT8 | 8-channel thermocouple/RTD input module | IN STOCK |
| 1794-IRT8XT | 8-channel thermocouple/RTD input, extended temperature | IN STOCK |
| 1794-IT8 | 8-channel thermocouple/mV input module | IN STOCK |
| 1794-IE8XOE4 | 8-input, 4-output analog combination module | IN STOCK |
| 1794-IE4XOE2 | 4-input, 2-output analog combination module | IN STOCK |
| 1794-IF2XOF2I | 2-input, 2-output isolated analog combination module | IN STOCK |
| 1794-OE4 | 4-channel analog output module | IN STOCK |
| 1794-OE12 | 12-channel analog output module | IN STOCK |
Application |
FLEX I/O analog output, 1794 terminal base |
Cat Num |
1794-OE12 |
Brand Name |
Rockwell |
Channels |
12, individually configurable, out-of-range bit per channel |
Output ranges |
0...20 mA, 4...20 mA, +/-10V DC |
Resolution |
320 uV/cnt, 0.641 uA/cnt |
Conversion |
Digital-to-analog converter |
Step response |
About 70% first conversion, 96% second, 100% third |
Accuracy |
0.1% of full scale at 25 deg C, current and voltage |
Load |
0...750 Ohm current; 3 mA maximum on voltage output |
Isolation |
850V DC type test for 60 s, field to system; no channel isolation |
External supply current |
320 mA at 24V DC, 720 mA at 10V DC |
Power dissipation |
4.3 W at 24V DC (14.7 BTU/hr) |
Operating temperature |
-20...60 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Twelve channels, individually configurable for 0...20 mA, 4...20 mA or +/-10V DC.
0.641 uA and 320 uV per count is a 16-bit-class step, materially finer than the four-channel card's 5.13 uA.
0.1% of full scale at 25 deg C on both current and voltage is the published accuracy, with 0.004% per deg C of drift.
Out-of-range status bit per channel reports a value outside the configured span without a program comparison.
The outputs stay at 0 mA until the module is configured , which is stated in the publication and matters at first power-up.
Digital-to-analog conversion rather than pulse-width modulation, so the output does not carry the PWM ripple of the four-channel card.
Step response is about 70% on the first conversion, 96% on the second and 100% on the third, which is how the card describes settling rather than a single time constant.
0...750 Ohm resistive load over the full supply range is wider than the 1794-OE4's 15...750 Ohm.
3 mA maximum on a voltage output is unchanged, so a voltage-driven device still has to be high impedance.
Calibration is not required; the card is internally calibrated and there is no trim step in maintenance.
320 mA at 24V DC and 720 mA at 10V DC is a serious supply load: twelve output stages draw far more than four.
4.3 W at 24V DC (14.7 BTU/hr) is the heat at the normal operating point, with 4.0 W published at both 31.2V and 10V.
-20...60 deg C operating range sits between the standard -20...55 deg C and the XT -20...70 deg C.
Isolation is 850V DC for 60 s field to system, with no isolation between channels.
Twelve field conductors on one base is the practical challenge: the wire schedule is planned before the card is ordered, not after.
Loop continuity on a 4...20 mA output is checked by measuring current with a meter in series, which also proves the 0...750 Ohm load is inside range.
A voltage-configured channel on a current device reads a plausible voltage and produces no movement; verify the configuration against the device nameplate before condemning the card.
Field terminals on the base, so a card exchange leaves twelve wires in place.
Dense analog output panels — a machine with twelve valves or drives on one island.
Applications that need 0.1% accuracy rather than the 0.4% of the four-channel current output.
Not for isolated field devices — the 1794-OF8IH provides eight isolated HART outputs.
Not below -20 deg C or above 60 deg C; the XT cards cover the wider window.
How many outputs has the 1794-OE12?
Twelve individually configurable analog outputs with an out-of-range bit per channel.
What ranges does it produce?
0...20 mA, 4...20 mA and +/-10V DC.
What is the resolution and accuracy?
320 uV or 0.641 uA per count, with 0.1% of full scale accuracy at 25 deg C.
What load can it drive?
0...750 Ohm on current output and 3 mA maximum on voltage output.
What current does the module draw?
320 mA at 24V DC, or 720 mA at 10V DC.
What does it output before configuration?
0 mA on every channel until the module is configured.