The 1794-OC16 drives 16 sourcing 48V DC outputs, 500 mA per channel, for field devices that run on a 48V rail.
It is the 48V counterpart of the 1794-OB16, and the module everyone asks about when a 24V output card cannot reach a 48V solenoid.
| 1794-OB8 | 8-point 24V DC sourcing output module | IN STOCK |
| 1794-OB8EP | 8-point 2 A electronically fused sourcing output module | IN STOCK |
| 1794-OB16 | 16-point 24V DC sourcing output module | IN STOCK |
| 1794-OB16P | 16-point protected sourcing output module | IN STOCK |
| 1794-OB16D | 16-point diagnostic 24V DC output module | IN STOCK |
| 1794-OB32P | 32-point protected sourcing output module | IN STOCK |
| 1794-OB16PXT | 16-point protected sourcing output, extended temperature | IN STOCK |
| 1794-OB8EPXT | 8-point 2 A electronically fused output, extended temperature | IN STOCK |
| 1794-OV16 | 16-point sinking output module | IN STOCK |
| 1794-OV16P | 16-point protected sinking output module | IN STOCK |
| 1794-OV32 | 32-point sinking output module | IN STOCK |
| 1794-OC16 | 16-point 48V DC sourcing output module | IN STOCK |
| 1794-OG16 | 16-point 5V DC sourcing output module | IN STOCK |
| 1794-OW8 | 8-point isolated relay output module | IN STOCK |
Application |
FLEX I/O digital output, 48V DC |
Cat Num |
1794-OC16 |
Brand Name |
Rockwell |
Number of outputs |
16, nonisolated, sourcing |
Output voltage |
30V DC min, 48V DC nom, 60V DC max |
Output current |
2.0 mA min, 500 mA max per channel |
Surge current |
4 A for 10 ms, repeatable every 2 s |
Voltage drop |
1.0V DC max at 0.5 A |
Off-state leakage |
1.0 mA max |
External supply |
30...60V DC, 13...27 mA |
Terminal base |
1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK |
Operating temperature |
0...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
500 mA maximum per channel, 2.0 mA minimum, with a 4 A surge for 10 ms repeatable every 2 s.
30...60V DC output range, 1.0V drop at 0.5 A, 1.0 mA off-state leakage, which matters for a device that must not hold on a leakage current.
16 sourcing outputs, nonisolated, with 16 yellow status indicators.
Key detail: outputs are not fused; publication 1794-IN105 recommends a 2 A, 150V AC M02 normal fuse externally.
External supply 30...60V DC, 13...27 mA module draw, plus the load current.
The supply commons land on B-16...B-33, internally connected, and the load returns to them.
Fusing must be provided outside the module, per the publication's own recommendation.
The terminal base carries 10 A total, so a fully loaded card can approach it.
48V solenoids, lamps and small relays where 24V would not pull in reliably.
Long cable runs that suit 48V for voltage-drop margin.
Not for AC loads; the 1794-OA16 and 1794-OM16 are the AC output cards.
Not for 125V DC; there is no 125V output card in this family.
Outputs on A-0...A-15, commons on B-17...B-32, supply on C-34.
Jumper C-51 to C-34 and B-33 to B-16 to continue into the next base.
Keyswitch position 1, as for the input module of the same voltage.
The 1794-TB2 works here because the output card needs fewer supply terminals.
48V DC machine panels in a FLEX I/O island.
Applications where 24V field devices were undersized and the rail was raised.
Not for high inrush AC loads; use the AC output family.
Not for diagnostics; the 1794-OB16D reports faults, this card does not.
How many outputs has the 1794-OC16?
16 nonisolated sourcing outputs.
What is the maximum output current?
500 mA per channel, with a 4 A surge for 10 ms every 2 s.
What voltage does it switch?
30...60V DC, 48V DC nominal.
Are the outputs fused?
No; external fusing is recommended, 2 A 150V AC M02.
What is the off-state leakage?
1.0 mA maximum.
What is the operating temperature?
0...55 deg C.
1794-OC16 is a digital DC output with 16 outputs in the FLEX I/O range, rated for 48V DC, non-isolated. It mounts on the 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK terminal base unit, which is ordered separately and is the part that actually carries the field terminals.
| Attribute | Value |
| Catalog number | 1794-OC16 |
| Module type | digital DC output |
| Points | 16 outputs |
| Electrical range | 48V DC, non-isolated |
| Terminal base unit | 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK |
The D-shell bases, 1794-TB37DS and 1794-TB62DS, exist so a pre-wired cable can land on a connector instead of on screw terminals. They measure 127 by 94 by 69 mm with an expansion module installed, which is taller than the 94 by 94 by 69 mm envelope of the standard bases and has to be allowed for in the panel layout.
Temperature class is written per module and per base, and the lower of the two governs the slice. A 70 C base carrying a 55 C module is a 55 C slice, which is why the extended temperature modules exist as a matched set rather than as an upgrade to one part of the pair.
One point about the 24V DC digital slices that catches panel builders: the adapter supplies the field power for the modules on its own 24V output, and that output is current limited. On a 1794-ADN the supply output is 450 mA at 24V, so a slice of 16 point DC modules can exhaust the adapter before the cabinet is half filled, and a separate field supply has to be introduced rather than assumed.
Any FLEX I/O position is a pair on the purchase order: one base, one module. Stocking modules without bases, or bases without the matching modules, produces a slice that cannot be commissioned, and the two part numbers are never interchangeable across the 8, 16 and 32 point families.
Mounting is a DIN rail operation on both parts and the order of assembly is base first, module second: the base slides onto the rail, its backplane fingers engage the neighbouring base, and the module is then pressed onto the base and secured. Removing a module does not break the backplane, which is why a failed slice can be swapped without rewiring the row.
Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.
The Allen-Bradley Flex I/O 1794 modules category groups the other catalog numbers, options and spare parts in the same range.