The 1794-OC16 drives 16 sourcing 48V DC outputs, 500 mA per channel, for field devices that run on a 48V rail.
It is the 48V counterpart of the 1794-OB16, and the module everyone asks about when a 24V output card cannot reach a 48V solenoid.
| 1794-OB8 | 8-point 24V DC sourcing output module | IN STOCK |
| 1794-OB8EP | 8-point 2 A electronically fused sourcing output module | IN STOCK |
| 1794-OB16 | 16-point 24V DC sourcing output module | IN STOCK |
| 1794-OB16P | 16-point protected sourcing output module | IN STOCK |
| 1794-OB16D | 16-point diagnostic 24V DC output module | IN STOCK |
| 1794-OB32P | 32-point protected sourcing output module | IN STOCK |
| 1794-OB16PXT | 16-point protected sourcing output, extended temperature | IN STOCK |
| 1794-OB8EPXT | 8-point 2 A electronically fused output, extended temperature | IN STOCK |
| 1794-OV16 | 16-point sinking output module | IN STOCK |
| 1794-OV16P | 16-point protected sinking output module | IN STOCK |
| 1794-OV32 | 32-point sinking output module | IN STOCK |
| 1794-OC16 | 16-point 48V DC sourcing output module | IN STOCK |
| 1794-OG16 | 16-point 5V DC sourcing output module | IN STOCK |
| 1794-OW8 | 8-point isolated relay output module | IN STOCK |
Application |
FLEX I/O digital output, 48V DC |
Cat Num |
1794-OC16 |
Brand Name |
Rockwell |
Number of outputs |
16, nonisolated, sourcing |
Output voltage |
30V DC min, 48V DC nom, 60V DC max |
Output current |
2.0 mA min, 500 mA max per channel |
Surge current |
4 A for 10 ms, repeatable every 2 s |
Voltage drop |
1.0V DC max at 0.5 A |
Off-state leakage |
1.0 mA max |
External supply |
30...60V DC, 13...27 mA |
Terminal base |
1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK |
Operating temperature |
0...55 deg C |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
500 mA maximum per channel, 2.0 mA minimum, with a 4 A surge for 10 ms repeatable every 2 s.
30...60V DC output range, 1.0V drop at 0.5 A, 1.0 mA off-state leakage, which matters for a device that must not hold on a leakage current.
16 sourcing outputs, nonisolated, with 16 yellow status indicators.
Key detail: outputs are not fused; publication 1794-IN105 recommends a 2 A, 150V AC M02 normal fuse externally.
External supply 30...60V DC, 13...27 mA module draw, plus the load current.
The supply commons land on B-16...B-33, internally connected, and the load returns to them.
Fusing must be provided outside the module, per the publication's own recommendation.
The terminal base carries 10 A total, so a fully loaded card can approach it.
48V solenoids, lamps and small relays where 24V would not pull in reliably.
Long cable runs that suit 48V for voltage-drop margin.
Not for AC loads; the 1794-OA16 and 1794-OM16 are the AC output cards.
Not for 125V DC; there is no 125V output card in this family.
Outputs on A-0...A-15, commons on B-17...B-32, supply on C-34.
Jumper C-51 to C-34 and B-33 to B-16 to continue into the next base.
Keyswitch position 1, as for the input module of the same voltage.
The 1794-TB2 works here because the output card needs fewer supply terminals.
48V DC machine panels in a FLEX I/O island.
Applications where 24V field devices were undersized and the rail was raised.
Not for high inrush AC loads; use the AC output family.
Not for diagnostics; the 1794-OB16D reports faults, this card does not.
How many outputs has the 1794-OC16?
16 nonisolated sourcing outputs.
What is the maximum output current?
500 mA per channel, with a 4 A surge for 10 ms every 2 s.
What voltage does it switch?
30...60V DC, 48V DC nominal.
Are the outputs fused?
No; external fusing is recommended, 2 A 150V AC M02.
What is the off-state leakage?
1.0 mA maximum.
What is the operating temperature?
0...55 deg C.