Product Details:
Payment & Shipping Terms:
|
The 1794-OB8EPXT is the 8-point extended-temperature output with an electronic fuse on every channel: 2.0 A per point, 10.0 A per module.
Where a glass fuse would need replacing after a fault, this card reports the fault in read bits F0...F7 and resets with the FR bit or a power cycle.
| 1794-OB8 | 8-point 24V DC sourcing output module | IN STOCK |
| 1794-OB8EP | 8-point 2 A electronically fused sourcing output module | IN STOCK |
| 1794-OB16 | 16-point 24V DC sourcing output module | IN STOCK |
| 1794-OB16P | 16-point protected sourcing output module | IN STOCK |
| 1794-OB16D | 16-point diagnostic 24V DC output module | IN STOCK |
| 1794-OB32P | 32-point protected sourcing output module | IN STOCK |
| 1794-OB16PXT | 16-point protected sourcing output, extended temperature | IN STOCK |
| 1794-OB8EPXT | 8-point 2 A electronically fused output, extended temperature | IN STOCK |
| 1794-OV16 | 16-point sinking output module | IN STOCK |
| 1794-OV16P | 16-point protected sinking output module | IN STOCK |
| 1794-OV32 | 32-point sinking output module | IN STOCK |
| 1794-OC16 | 16-point 48V DC sourcing output module | IN STOCK |
| 1794-OG16 | 16-point 5V DC sourcing output module | IN STOCK |
| 1794-OW8 | 8-point isolated relay output module | IN STOCK |
Application |
FLEX I/O-XT protected sourcing output |
Cat Num |
1794-OB8EPXT |
Brand Name |
Rockwell |
Number of outputs |
8, nonisolated, sourcing, one group |
On-state voltage |
19.2V DC min, 24V DC nom, 31.2V DC max |
Output current |
1.0 mA min, 2.0 A max per channel |
Module current |
10.0 A max, e.g. 8 outputs at 1.25 A |
Output surge |
4.0 A for 10 ms, repeatable every 3 s |
Voltage drop |
0.2V DC max |
Isolation |
type tested 1500V AC for 60 s |
Fault reporting |
F0...F7 read bits, FR reset bit |
Terminal base |
1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Each output is electronically fused and the fault appears as bit F0...F7 in the read word.
Reset with the FR bit in the write word, by software, or by cycling the module's input power.
Fault status goes to the processor, which a plain protected output cannot do.
Recovery is not automatic on this type; a reset is required.
2.0 A per channel and 10.0 A per module, so the split can be 8 at 1.25 A or 5 at 2.0 A.
4.0 A surge for 10 ms repeatable every 3 s, 0.2V drop, 0.5 mA leakage, which suits valves and contactors.
19.2...31.2V DC on-state, 24V DC nominal, 55 mA supply at 24V, not counting load current.
8 yellow status plus 8 red fault indicators on the module face.
Even terminals 0...14 carry the outputs, odd terminals 0...15 the commons on a TB2 or TB3.
On a 1794-TBN the outputs are B-0...B-14 with commons C-1...C-15, per the wiring table.
The odd terminals are internally tied to 24V DC common on TB2, TB3 and TB3S.
<Keyswitch position per 1794-IN124, and the base must suit the coating for a full -XT island.
<Extended-temperature islands down to -20 deg C.
Outputs that must report a fault rather than just stop.
Not a 16-point density; the 1794-OB16PXT doubles it at 500 mA.
Not for AC loads.
Valve and contactor groups needing 2 A per point with diagnostics.
Panels where fuse replacement is a nuisance.
Not for high inrush AC devices.
Not for 48V DC; the 1794-OC16 covers that.
What does the EP suffix mean?
Electronically fused: the output opens on fault and reports it to the processor.
What current can each output carry?
2.0 A per channel and 10.0 A per module.
How is a fault reset?
With the FR bit, by software, or by cycling input power.
Which bases are used?
1794-TB2, 1794-TB3, 1794-TB3S or 1794-TBN.
What is the operating temperature?
-20...70 deg C, conformally coated.
Does it report which channel faulted?
Yes, through read bits F0...F7.
1794-OB8EPXT is a protected digital DC output with 8 outputs in the FLEX I/O range, rated for 24V DC, non-isolated, protected. It mounts on the 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TB3K, 1794-TB3SK, 1794-TBNK terminal base unit, which is ordered separately and is the part that actually carries the field terminals.
| Attribute | Value |
| Catalog number | 1794-OB8EPXT |
| Module type | protected digital DC output |
| Points | 8 outputs |
| Electrical range | 24V DC, non-isolated, protected |
| Terminal base unit | 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TB3K, 1794-TB3SK, 1794-TBNK |
| Temperature rating | Extended temperature version of the 1794-OB8EP |
| Protection behaviour | Electronic fuse with a reset by push button, software, or power cycle, and fault status reported to the processor |
The XT suffix is the extended temperature build rather than a different circuit: the same terminal base list, the same field voltage, and an operating range that reaches 70 C instead of the 55 C of the standard version. Specifying XT and then derating the panel back to 55 C gives away the only thing that was paid for.
Conformal coated variants carry a K suffix and exist because the same base can be asked to survive washdown, condensate, or corrosive atmosphere. Ordering the uncoated base and treating it in the field is not equivalent and does not carry the same published rating.
One point about the 24V DC digital slices that catches panel builders: the adapter supplies the field power for the modules on its own 24V output, and that output is current limited. On a 1794-ADN the supply output is 450 mA at 24V, so a slice of 16 point DC modules can exhaust the adapter before the cabinet is half filled, and a separate field supply has to be introduced rather than assumed.
Temperature class is written per module and per base, and the lower of the two governs the slice. A 70 C base carrying a 55 C module is a 55 C slice, which is why the extended temperature modules exist as a matched set rather than as an upgrade to one part of the pair.
On the 32 point bases the common and voltage terminals are grouped in eight pairs rather than eighteen, which is why the 32 point digital modules can mix sinking and sourcing groups in one slice and why the terminal numbering on the drawing does not follow the 16 point pattern.
Any FLEX I/O position is a pair on the purchase order: one base, one module. Stocking modules without bases, or bases without the matching modules, produces a slice that cannot be commissioned, and the two part numbers are never interchangeable across the 8, 16 and 32 point families.
Practical check before ordering: confirm the permitted terminal base for the module, confirm the conductor range and current capacity of that base against the field wiring schedule, confirm whether the location needs the conformal coated K variant, and confirm the operating temperature class against the panel interior rather than the room.
Related models, options and spare parts for this range are listed in the Allen-Bradley Flex I/O 1794 modules category.