Product Details:
Payment & Shipping Terms:
|
The 1794-OB8EPXT is the 8-point extended-temperature output with an electronic fuse on every channel: 2.0 A per point, 10.0 A per module.
Where a glass fuse would need replacing after a fault, this card reports the fault in read bits F0...F7 and resets with the FR bit or a power cycle.
| 1794-OB8 | 8-point 24V DC sourcing output module | IN STOCK |
| 1794-OB8EP | 8-point 2 A electronically fused sourcing output module | IN STOCK |
| 1794-OB16 | 16-point 24V DC sourcing output module | IN STOCK |
| 1794-OB16P | 16-point protected sourcing output module | IN STOCK |
| 1794-OB16D | 16-point diagnostic 24V DC output module | IN STOCK |
| 1794-OB32P | 32-point protected sourcing output module | IN STOCK |
| 1794-OB16PXT | 16-point protected sourcing output, extended temperature | IN STOCK |
| 1794-OB8EPXT | 8-point 2 A electronically fused output, extended temperature | IN STOCK |
| 1794-OV16 | 16-point sinking output module | IN STOCK |
| 1794-OV16P | 16-point protected sinking output module | IN STOCK |
| 1794-OV32 | 32-point sinking output module | IN STOCK |
| 1794-OC16 | 16-point 48V DC sourcing output module | IN STOCK |
| 1794-OG16 | 16-point 5V DC sourcing output module | IN STOCK |
| 1794-OW8 | 8-point isolated relay output module | IN STOCK |
Application |
FLEX I/O-XT protected sourcing output |
Cat Num |
1794-OB8EPXT |
Brand Name |
Rockwell |
Number of outputs |
8, nonisolated, sourcing, one group |
On-state voltage |
19.2V DC min, 24V DC nom, 31.2V DC max |
Output current |
1.0 mA min, 2.0 A max per channel |
Module current |
10.0 A max, e.g. 8 outputs at 1.25 A |
Output surge |
4.0 A for 10 ms, repeatable every 3 s |
Voltage drop |
0.2V DC max |
Isolation |
type tested 1500V AC for 60 s |
Fault reporting |
F0...F7 read bits, FR reset bit |
Terminal base |
1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1794-DU001 (module specifications) and 1794-SG002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Each output is electronically fused and the fault appears as bit F0...F7 in the read word.
Reset with the FR bit in the write word, by software, or by cycling the module's input power.
Fault status goes to the processor, which a plain protected output cannot do.
Recovery is not automatic on this type; a reset is required.
2.0 A per channel and 10.0 A per module, so the split can be 8 at 1.25 A or 5 at 2.0 A.
4.0 A surge for 10 ms repeatable every 3 s, 0.2V drop, 0.5 mA leakage, which suits valves and contactors.
19.2...31.2V DC on-state, 24V DC nominal, 55 mA supply at 24V, not counting load current.
8 yellow status plus 8 red fault indicators on the module face.
Even terminals 0...14 carry the outputs, odd terminals 0...15 the commons on a TB2 or TB3.
On a 1794-TBN the outputs are B-0...B-14 with commons C-1...C-15, per the wiring table.
The odd terminals are internally tied to 24V DC common on TB2, TB3 and TB3S.
<Keyswitch position per 1794-IN124, and the base must suit the coating for a full -XT island.
<Extended-temperature islands down to -20 deg C.
Outputs that must report a fault rather than just stop.
Not a 16-point density; the 1794-OB16PXT doubles it at 500 mA.
Not for AC loads.
Valve and contactor groups needing 2 A per point with diagnostics.
Panels where fuse replacement is a nuisance.
Not for high inrush AC devices.
Not for 48V DC; the 1794-OC16 covers that.
What does the EP suffix mean?
Electronically fused: the output opens on fault and reports it to the processor.
What current can each output carry?
2.0 A per channel and 10.0 A per module.
How is a fault reset?
With the FR bit, by software, or by cycling input power.
Which bases are used?
1794-TB2, 1794-TB3, 1794-TB3S or 1794-TBN.
What is the operating temperature?
-20...70 deg C, conformally coated.
Does it report which channel faulted?
Yes, through read bits F0...F7.