Product Details:
Payment & Shipping Terms:
|
The 1756-IT6I (also written 1756IT6I) is the six-channel thermocouple input of the first isolated analog generation: six channels with two millivolt ranges, -12...78 mV for full thermocouple spans and -12...30 mV for the high-resolution range, backplane load 200 mA at 5.1 V DC and 150 mA at 24 V DC, total backplane power 4.6 W (1756-TD002).
The two ranges decide the usable span per thermocouple type, and the published table makes that explicit: a type K covers -270...1372 °C on the 78 mV range but only -270...725 °C on the 30 mV range, and a type B is full range on both because its output rises late in the span. Choosing the narrow range for resolution can therefore cost most of the measurement range.
Resolution is quoted per type: approximately 0.05 °C for E, J, K, T and N on the wide range and 0.03 °C on the narrow range, 0.15 °C for B, R, S and C, 0.07 °C for D and 0.02 °C for L (TXK/XK). Calibrated accuracy is 0.05 % of full range typical and better than 0.1 % worst case, with a 12-month calibration interval.
Cold junction compensation uses the sensor shipped with the module, part number 94238301, replaceable as RP-94238301 — one sensor for the module, not one per channel. Technical data 1756-TD002, user manual 1756-UM009.
1756-IF4FXOF2F |
4 high-speed differential inputs + 2 outputs, 375 mA, reinforced isolation |
In stock |
1756-IF6CIS |
6 isolated current inputs with sourcing 24 V DC loop supply |
In stock |
1756-IF6I |
6 isolated inputs, 16-bit, 250 mA, channel-to-channel basic isolation |
In stock |
1756-IF8 |
8 single-ended / 4 differential inputs, 200 mA, 250 V basic to backplane |
In stock |
1756-IF8H |
8 differential HART current inputs, A and B series |
In stock |
1756-IF16 |
16 single-ended / 8 differential inputs, 200 mA, 15 Hz bandwidth |
In stock |
1756-IF16H |
16 differential HART current inputs, A and B series |
In stock |
1756-IRT8I |
8 isolated RTD and thermocouple inputs, 24-bit, 1756-CJC required |
In stock |
1756-IR6I |
6 isolated RTD inputs, 20-pin block, discontinued 2017 |
In stock |
1756-IT6I |
6 thermocouple inputs, two mV ranges, one CJC sensor |
In stock |
1756-IT6I2 |
6 isolated thermocouple inputs, 16-bit, two CJC sensors |
In stock |
Application |
Analog input |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-IT6I |
Communication |
Backplane (producer/consumer) |
Display |
— |
Enclosure |
None (open-style) |
Interface |
Removable terminal block |
Mounting |
Chassis slot |
Number Of Channels |
6 |
Standard |
CE, UL, CSA, RCM |
Sub Brand |
ControlLogix |
Type |
Analog Input Module |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN063 (analog I/O installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The IT6I is a legacy-support module now: six thermocouples in panels built before the 1756-IRT8I and 1756-IT16 generations, where the field wiring and the terminal block are already in place.
Where the module is still specified by an existing drawing, the two-range arrangement is its advantage: mixed type K and type B on one module, each channel set to the range that gives usable resolution over its span.
For new work the IT16 provides 16 channels and the IRT8I provides 8 isolated channels accepting both thermocouples and RTDs, with 24-bit resolution.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| Check 2 | One CJC for six channels | The 94238301 sensor serves the module. A thermocouple landed on a channel whose CJC is far away in temperature measures a gradient, not the process. |
| Check 3 | Input impedance above 10 MΩ | High enough that a thermocouple's loop resistance does not load the junction; the limit that matters is the 120 V AC/DC overvoltage rating. |
| Check 4 | 250 V basic, channel to channel | Per-channel isolation on the 6-channel family, at a basic rating. Reinforced barriers are on the newer 1756-IRT8I and 1756-IT16. |
| Check 5 | Open circuit detected within 2 s | A broken thermocouple reads positive full scale within 2 seconds — a diagnostic the project should be configured to alarm on. |
Specifications per Rockwell publication 1756-TD002 (ControlLogix I/O Modules Specifications); module behaviour per 1756-UM009 and 1756-IN050.
For 16 thermocouple channels, 1756-IT16 carries the wider count in one slot.
The 1756-IRT8I accepts thermocouples and RTDs on 8 isolated channels at 24-bit resolution, with the 1756-CJC as its cold junction sensor.
For RTDs rather than thermocouples, 1756-IR12 provides 12 channels at 24-bit; the 6-channel predecessor is 1756-IR6I.
What is the 1756-IT6I?
A 6-channel thermocouple input module with two millivolt ranges, -12...78 mV and -12...30 mV.
What is the backplane current?
200 mA at 5.1 V DC and 150 mA at 24 V DC, 4.6 W total backplane power (1756-TD002).
Why two ranges?
The narrow range gives higher resolution but a shorter usable span for most thermocouple types — type K reaches 1372 °C on the wide range and 725 °C on the narrow one.
How accurate is it?
0.05 % of full range typical, better than 0.1 % worst case, with a 12-month calibration interval.
Does it need a cold junction sensor?
Yes — one 94238301 sensor is shipped with the module and serves all six channels.
What isolation does it provide?
250 V continuous basic insulation, channel-to-channel and to the backplane.
Does it detect a broken thermocouple?
Yes — positive full scale reading within 2 seconds, which the project should be configured to alarm on.
What replaces it?
1756-IT16 for 16 channels, or 1756-IRT8I for 8 isolated channels accepting thermocouples and RTDs at 24-bit resolution.
Data sources. Technical values on this page come from Rockwell publications 1756-TD003 (ControlLogix Communication Modules Specifications), 1756-IN050 (1756 EtherNet/IP Communication Modules, installation instructions), 1756-UM004 (ControlLogix EtherNet/IP Network Devices User Manual) and the manufacturer's product page for 1756-IT6I. Values re-checked 15 November 2026.