Product Details:
Payment & Shipping Terms:
|
The 1756-A5XT (also written 1756A5XT) is the five-slot ControlLogix-XT chassis: one slot more than the 1756-A4LXT, rated to -25…+70 °C instead of +60 °C, conformally coated and mounted horizontally in a 50.8 x 76.2 x 20.3 cm minimum cabinet.
Published figures are 5 slots, 10 A chassis and 6 A per slot at 5.1 V DC, 2 A / 2 A at 24 V DC, 4 A / 4 A at 3.3 V DC, 4.4 W maximum chassis dissipation, and 1.45 kg approximate weight (1756-TD006). The wider temperature window is the practical difference from the four-slot chassis, which stops at +60 °C.
1756-A4LXT/B |
4 slots, 50.8 x 50.8 x 20.3 cm, -25…+60 °C, 10 A at 5.1 V DC |
In stock |
1756-A5XT/B |
5 slots, 50.8 x 76.2 x 20.3 cm, -25…+70 °C, 10 A at 5.1 V DC |
In stock |
1756-A7LXT/B |
7 slots, 50.8 x 60.9 x 20.3 cm, -25…+60 °C, 10 A at 5.1 V DC |
In stock |
1756-A7XT/B |
7 slots, 50.8 x 60.9 x 20.3 cm, -25…+70 °C, 10 A at 5.1 V DC |
In stock |
1756-A7XT/C |
7 slots, -25…+70 °C, 15 A at 5.1 V DC, Series C |
In stock |
1756-A10XT/C |
10 slots, 50.8 x 85.75 x 20.3 cm, -25…+70 °C, 15 A at 5.1 V DC |
In stock |
Application |
Chassis / backplane |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-A5XT |
Communication |
EtherNet/IP |
Display |
Digital |
Enclosure |
Open chassis, conformally coated (XT) |
Interface |
1756-A5XT |
Mounting |
Horizontal only, panel located |
Number Of Channels |
1756-A5XT |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Chassis |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN005 (chassis installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Five slots is a deliberate count: a controller, a communication module and three I/O modules, with no empty slot to leave open. In an XT panel that means an outdoor cabinet with a small I/O count and no room for a larger chassis.
The +70 °C rating is what the extra slot is usually bought for. A cabinet that reaches +65 °C in summer derates the four-slot chassis to its +60 °C limit, so the five-slot part is often chosen for the temperature rather than the space.
A chassis has no indicators; its limits are the numbers that decide whether the rack can carry the modules planned for it. Every row below is quoted from the chassis specification 1756-TD006.
| Indicator | State | Meaning and first action |
| Backplane current at 5.1 V DC | 10 A / 6 A | Chassis total / per-slot maximum. Sum the 5.1 V current of every module against this figure before the layout is fixed. |
| Backplane current at 24 V DC | 2 A / 2 A | Chassis total / per-slot maximum, for modules that take their 24 V from the backplane. |
| Backplane current at 3.3 V DC | 4 A / 4 A | Chassis total / per-slot maximum, common to the whole XT family. |
| Backplane current at 1.2 V DC | 1.5 A / – | Chassis total, with no per-slot limit published. |
| Power dissipation | See the specification table | The chassis itself dissipates 3.7 W to 5.0 W depending on size; it adds to the enclosure thermal load. |
| Operating temperature | -25…+70 °C (-13…+158 °F) | The surrounding-air rating of this chassis. Every module in the rack has to share it or the assembly drops to the lower figure. |
| Mounting | Horizontal only | Panel mount, minimum cabinet depth 20.3 cm; the XT chassis is conformally coated for ISA G3 environments. |
| Earth grounding | 8 AWG functional / 14 AWG protective | Copper wire rated 90 °C or greater; the coating does not replace the earth connection. |
Slot counts, backplane current, enclosure sizes and environmental ratings per Rockwell publication 1756-TD006F-EN-E (1756 ControlLogix Chassis Specifications) and 1756-IN050.
The step down is the 1756-A4LXT at four slots and -25…+60 °C; the step up is the 1756-A7LXT at seven slots, 10 A and the same +60 °C limit, or the 1756-A7XT at seven slots and +70 °C.
Because the electrical budget is identical across the 10 A group, a slot-count change inside that group is a mechanical and thermal decision, not a supply re-calculation.
How many slots does the 1756-A5XT have?
Five slots at 10 A chassis / 6 A per slot on 5.1 V DC (1756-TD006).
What is its temperature range?
-25…+70 °C surrounding air, against +60 °C on the 1756-A4LXT and 1756-A7LXT.
How does it differ from the 1756-A4LXT?
One more slot (+1), a wider temperature window (+70 °C instead of +60 °C), a wider minimum cabinet (50.8 x 76.2 cm instead of 50.8 x 50.8 cm) and a slightly higher chassis dissipation (4.4 W against 3.7 W).
What backplane current is available?
10 A at 5.1 V DC (6 A per slot), 2 A at 24 V DC (2 A per slot), 4 A at 3.3 V DC (4 A per slot), 1.5 A at 1.2 V DC.
Which power supplies fit?
The XT supplies 1756-PAXT, 1756-PBXT, 1756-PA30XT and 1756-PB30XT mount on the left of the chassis; the redundant XT pair uses 1756-PAXTR / 1756-PBXTR with the 1756-PSCA2XT adapter.
What cabinet and mounting?
Minimum 50.8 x 76.2 x 20.3 cm (20 x 30 x 8 in.), horizontal only, panel located, open-style enclosure.
What is the weight?
1.45 kg (3.2 lb) approximately.
What certifications apply?
UL Listed (E65584), UL Class I Division 2 (E194810), FM Approved, CE, RCM, ATEX Ex nA IIC T5 Gc, IECEx, KC and EAC, when marked.
Data sources. Technical values on this page come from Rockwell publications 1756-TD006 (1756 ControlLogix Chassis Specifications) and 1756-IN005 (ControlLogix chassis installation instructions) and the manufacturer's product page for 1756-A5XT. Values re-checked 16 November 2026.