Product Details:
Payment & Shipping Terms:
|
The 1756-L65 (also written 1756L65) is the largest-memory controller of the ControlLogix 5560 range: 32 MB of user memory in one chassis slot, with one RS-232 serial port and backplane access to the rack's communication and I/O modules. Rockwell lists it as discontinued since 1 June 2017 under the functional replacement category.
Everything else is the 5560 envelope: 478 KB of I/O memory, 128,000 digital and 4,000 analogue I/O points as maximums, 32 tasks with 100 programs per task, 250 controller connections, 1200 mA at 5.1 V DC plus 14 mA at 24 V DC, 3.5 W and 11.9 BTU/hr, and 30 V continuous basic isolation on the RS-232 port (1756-TD001S). Two published cautions travel with this part: the scan time of a project loaded in an L64 or L65 can be slower than the same project in the smaller 5560 controllers, and the L64 and L65 do not carry the ATEX certification the rest of the family holds.
| 1756-L61 | ControlLogix 5560 controller, 2 MB user memory | IN STOCK |
| 1756-L62 | ControlLogix 5560 controller, 4 MB user memory | IN STOCK |
| 1756-L63 | ControlLogix 5560 controller, 8 MB user memory | IN STOCK |
| 1756-L65 | ControlLogix 5560 controller, 32 MB user memory | IN STOCK |
| 1756-L63XT | ControlLogix-XT 5560 controller, 8 MB, -25 to +70 C | IN STOCK |
| 1756-L61S | GuardLogix 5560 safety controller, 2 MB | IN STOCK |
| 1756-L62S | GuardLogix 5560 safety controller, 4 MB | IN STOCK |
| 1756-L63S | GuardLogix 5560 safety controller, 8 MB | IN STOCK |
Application |
Programmable Logic Controller |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-L65 |
Communication |
Backplane (EtherNet/IP, ControlNet, DeviceNet, DH+, Remote I/O, SERCOS) |
Display |
Indicators (OK, RUN, I/O, FORCE, BATTERY, RS-232) |
Enclosure |
None (open-style) |
Interface |
1 RS-232 serial port |
Mounting |
Chassis |
Number Of Channels |
1 |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Controller |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-UM001 (ControlLogix controller user manual). Certification details, with certificate and file numbers, are listed in the FAQ below.
32 MB is the answer when a program is memory-bound rather than I/O-bound: recipe tables and product data held in the controller, historical logging, or a large sequential or batch program that was split across controllers on the smaller models.
Two consequences belong in the design review. Scan time for a project loaded in this controller can be slower than the same project in a smaller 5560 controller, so cycle-time budgets are re-measured rather than scaled. And the missing ATEX entry means a classified location needs a different part number, not an argument.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| OK | Flashing green | Power-up self-test in progress; wait for solid. |
| OK | Red | Major fault or self-test failure. Read the fault in the project before any restart. |
| RUN | Green solid | Program running. |
| RUN | Red | Major fault latched; the program is stopped. |
| I/O | Green solid | All configured I/O modules are communicating. |
| I/O | Flashing green | One or more configured modules are not responding. |
| I/O | Red | Faulted I/O connection; the program may still be running. |
| FORCE | Amber | Forces enabled — a live wiring check is not valid while this is lit. |
| BATTERY | Red | Battery low or missing; the project in RAM is not protected across a power cycle. |
| RS-232 | Green flashing | Serial activity on the programming port. |
Indicator behaviour per Rockwell publication 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and 1756-IN050.
Discontinued on 1 June 2017, replacement category functional replacement. The successor in the 5570 family is the 1756-L73E for racks of similar size; above it the 5580 controllers carry more memory with a much higher CIP packet rate and an embedded Ethernet port.
The migration matters most for memory-bound projects: the tag and program sizes are re-checked against the new controller, the scan-time assumption is re-measured, and any hazardous-area requirement is re-read against the new part's certification list before the order is placed.
How much memory does the 1756-L65 have?
32 MB of user memory with 478 KB of I/O memory — the largest in the 5560 range — and maximums of 128,000 digital and 4,000 analogue I/O points (1756-TD001S, ControlLogix 5560 Controllers).
Does a bigger controller mean a faster scan?
Not here. Rockwell publishes that the scan time for a project loaded in a 1756-L64 or L65 controller can be slower than for the same project loaded in one of the other 5560 controllers, and points to publication 1756-RM087 for instruction execution times. Cycle-time budgets are therefore measured, not assumed.
Is the 1756-L65 discontinued?
Yes. Discontinuation date 1 June 2017, replacement category functional replacement; the current families are the 5570 (L71E/L72E/L73E) and 5580 (L81E…L85E).
Is it certified for hazardous locations in Europe?
The ATEX entry in 1756-TD001S states explicitly that the 1756-L64 and 1756-L65 controllers do not carry that certification, unlike the L61, L62 and L63. The Class I Division 2 listings (UL E194810, CSA LR69960C, FM) are still published, so North American Division 2 use is covered while European Zone 2 use is not.
How many connections does it support?
250 controller connections, shared by I/O connections, produced and consumed tags and every HMI or programming session on the controller.
What is its current draw and dissipation?
1200 mA at 5.1 V DC and 14 mA at 24 V DC, 3.5 W and 11.9 BTU/hr, one slot wide (1756-TD001S). The same as every other 5560 controller — the memory size does not change the slot budget.
Which chassis, supplies and battery apply?
1756-A4, A7, A10, A13 or A17, any slot, one slot wide; standard supplies 1756-PA50, PA72, PA75, PB50, PB72, PB75, redundant PA75R, PB75R or PSCA2. Battery 1756-BA2 for Series B, 1756-BA1/BA1M/BATA for Series A.
What are the environmental limits?
Operating 0…60 °C with 60 °C maximum surrounding air, storage -40…85 °C, 5…95% RH non-condensing, 2 g vibration at 10…500 Hz, 30 g operating and 50 g non-operating shock, CISPR 11 Class A, ESD 6 kV contact and 8 kV air, radiated RF 10 V/m 80…2000 MHz and 3 V/m 2000…2700 MHz, EFT ±4 kV at 5 kHz and surge ±2 kV line-earth on the RS-232 port, conducted RF 10 V rms 150 kHz…80 MHz (1756-TD001S).
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) and 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and the manufacturer's product page for 1756-L65. Values re-checked 15 November 2026.