Product Details:
Payment & Shipping Terms:
|
The 1756-L63XT (also written 1756L63XT) is the ControlLogix-XT version of the 8 MB 5560 controller: the same one-slot controller, RS-232 programming port and backplane, built with conformal coating and the XT environmental qualification for harsh and corrosive atmospheres. Rockwell lists it as discontinued on 1 June 2017 under the functional replacement category, series B, UPC 612598554812, country of origin United States of America.
Electrical values are shared with the standard 5560 controller: 8 MB user memory, 478 KB I/O memory, 128,000 digital and 4,000 analogue I/O points as maximums, 32 tasks with 100 programs per task, 250 controller connections, 1200 mA at 5.1 V DC plus 14 mA at 24 V DC, 3.5 W and 11.9 BTU/hr dissipation, one slot wide, with 30 V continuous basic isolation from the RS-232 port to the system (1756-TD001). The XT difference is in the environmental table and the coating, not in the current draw.
| 1756-L61 | 5560 controller, 2 MB | IN STOCK |
| 1756-L62 | 5560 controller, 4 MB | IN STOCK |
| 1756-L63 | 5560 controller, 8 MB | IN STOCK |
| 1756-L63XT | ControlLogix-XT 5560 controller, 8 MB, conformal coated | IN STOCK |
| 1756-L64 | 5560 controller, 16 MB | IN STOCK |
| 1756-L65 | 5560 controller, 32 MB | IN STOCK |
| 1756-L71 | 5570 controller, 2 MB | IN STOCK |
| 1756-L73 | 5570 controller, 8 MB | IN STOCK |
Application |
Programmable Logic Controller |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-L63XT |
Communication |
Backplane (EtherNet/IP, ControlNet, DeviceNet, DH+, Remote I/O, SERCOS) |
Display |
Indicators (OK, RUN, I/O, FORCE, BATTERY, RS-232) |
Enclosure |
None (open-style) |
Interface |
1 RS-232 serial port |
Mounting |
Chassis |
Number Of Channels |
1 |
Standard |
CCC,CE,CSA,C-TICK,CUL,GOST,KC,MARINE,NRTL,RCM,UL Vendor attribute list — the current Rockwell certification record, with certificate and file numbers, is in the FAQ. |
Sub Brand |
ControlLogix |
Type |
Controller |
UNSPSC |
32151705 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-UM001 (ControlLogix controller user manual). Certification details, with certificate and file numbers, are listed in the FAQ below.
The L63XT is specified where the 8 MB program size is right but the panel is not: an outdoor cabinet, a wash-down area, a plant with sulphur-bearing gases, or a location that swings below freezing. Conformal coating plus the XT qualification is what makes the controller installable in those cabinets at all.
Because the electrical figures are identical to the standard L63, the rack budget does not change when the XT part is chosen. What changes is the rest of the assembly: the chassis, the communication modules and the I/O have to be XT parts as well, or the extended rating applies only to the controller.
8 MB remains a workable program size for a line-level controller, and it is the reason most XT upgrades of existing 5560 racks are built around L63XT rather than the smaller memory sizes.
Three bi-colour indicators plus the alphanumeric display cover almost every commissioning fault, so most problems are resolved at the panel without a laptop.
| Indicator | State | Meaning and first action |
| OK | Flashing green | Power-up self-test in progress; wait for solid. |
| OK | Red | Major fault or self-test failure. Read the fault in the project before any restart. |
| RUN | Green solid | Program running. |
| RUN | Red | Major fault latched; the program is stopped. |
| I/O | Green solid | All configured I/O modules are communicating. |
| I/O | Flashing green | One or more configured modules are not responding. |
| I/O | Red | Faulted I/O connection; the program may still be running. |
| FORCE | Amber | Forces enabled — a live wiring check is not valid while this is lit. |
| BATTERY | Red | Battery low or missing; the project in RAM is not protected across a power cycle. |
| RS-232 | Green flashing | Serial activity on the programming port. |
Indicator behaviour per Rockwell publication 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and 1756-IN050.
Rockwell's discontinuation notice for 1756-L63XT is dated 1 June 2017 with the functional replacement category; the successor path is the 5570 XT range (1756-L71XT, L72XT, L73XT) and above it the 5580 XT controllers.
The XT swap has one extra condition the standard swap does not: the replacement has to be an XT part, and the modules around it have to match, otherwise the panel loses the environmental rating the L63XT was bought for.
Where the panel is only slightly warm rather than corrosive or freezing, a standard 5560 or 5570 controller in a conditioned enclosure is the cheaper answer, and the coating is not needed.
How much user memory does the 1756-L63XT have?
8 MB of user memory, with 478 KB of I/O memory and maximums of 128,000 digital and 4,000 analogue I/O points (1756-TD001).
What does the XT suffix change?
The controller is conformally coated and carries the ControlLogix-XT environmental qualification for harsh and corrosive atmospheres; the memory, connections and current draw are those of the standard 5560 controller.
How much current does it draw from the backplane?
1200 mA at 5.1 V DC and 14 mA at 24 V DC, dissipating 3.5 W and 11.9 BTU/hr in one slot (1756-TD001).
Is the module still available new?
No — Rockwell lists the discontinuation date as 1 June 2017, replacement category functional replacement, series B.
What are the UPC and country of origin?
UPC 612598554812, country of origin United States of America, as published on the Rockwell product record.
How many controller connections does it support?
250 controller connections, covering I/O modules, produced and consumed tags, and HMI or programming sessions.
Which chassis and modules must be used with it?
XT chassis and XT modules: the extended environmental rating applies to the assembly, not to the controller alone, so the standard 1756-A4…A17 chassis do not carry it.
Which battery and firmware does it need?
Series B uses the 1756-BA2 lithium battery; firmware has to match the project revision, because a controller at an older revision will not accept a project built at a newer one.
Data sources. Technical values on this page come from Rockwell publications 1756-TD001 (ControlLogix and GuardLogix Controller Specifications) and 1756-UM001 (ControlLogix 5570 and 5560 Controllers User Manual) and the manufacturer's product page for 1756-L63XT. Values re-checked 16 November 2026.