The 1756-OA8E (also written 1756OA8E) is the 8-point AC output module with electronic fusing and a higher current rating than the diagnostic OA8D: 2 A per point at 60 °C and a 20 A surge per point.
Total backplane power is 7.02 W, dissipation 5.5 W at 60 °C (18.76 BTU/hr).
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
Application |
AC digital output module |
Brand Name |
Rockwell (Rockwell) |
Cat Num |
1756-OA8E |
Outputs |
8, electronic fusing |
Voltage Category |
120 V AC 50/60 Hz |
Operating Voltage Range |
74…132 V AC, 47…63 Hz |
Output Delay |
9.3 ms @ 60 Hz; 11 ms @ 50 Hz |
Backplane Power |
7.02 W |
Power Dissipation |
5.5 W @ 60 °C |
Thermal Dissipation |
18.76 BTU/hr |
Current per Point |
2 A @ 60 °C |
Current per Group |
4 A @ 30 °C, linear derating to 2 A @ 60 °C |
Current per Module |
8 A @ 30 °C, linear derating to 4 A @ 60 °C |
Surge Current per Point |
20 A for 43 ms, repeatable every 2 s @ 60 °C |
Off-state Leakage |
3 mA per point, max |
On-state Voltage Drop |
4 V peak @ 2 A |
Load Current, Min |
10 mA per point |
Slot Width |
1 |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1756-TD003 (module specifications) and 1756-IN050 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The choice between OA8D and OA8E is a current decision, not a feature decision. Both fuse electronically; the OA8E carries 2 A per point at 60 °C without the 1 A/30 °C starting point that halves on the diagnostic module.
Group current is still the binding limit: 4 A per group at 30 °C, 2 A at 60 °C, and 8 A per module at 30 °C falling to 4 A at 60 °C. Four points sharing a group cannot each run at 2 A in a warm panel.
The 20 A surge for 43 ms per point, repeatable every 2 s, is what makes this module usable on contactor coils and small motor starters where the OA8D's 8 A or 5 A surge is marginal.
On-state voltage drop is higher here, up to 4 V peak at 2 A, because the module carries twice the current. On a 120 V circuit that is a 3% loss and a real thermal item at the device, not at the module.
Off-state leakage remains 3 mA per point, with a 10 mA minimum load. The leakage is unchanged by the higher rating, so the same caution applies to small relays and indicator lamps.
Total backplane power of 7.02 W means this module is a slightly heavier load on the chassis than the diagnostic version, even though its per-point capability is double — worth noting when two cards are swapped during a retrofit.
Protection is electronic fusing per group of four points, and the current rating is a 60 °C figure: the group limit, not the point limit, decides how many devices can share a card.
| Indicator | State | Meaning and first action |
| Output heats up at 60 °C panel temperature | — | Current per point derates with temperature: 1 A at 30 °C becomes 0.5 A at 60 °C on the diagnostic module. |
| Output stays on with no command | — | Off-state leakage is up to 3 mA per point, enough to hold a small relay or a neon indicator energised. |
| Diagnostic does not report a short | — | The short-circuit trip needs a fault current above the published minimum; a soft short below it looks like a normal load. |
Backplane current, dissipation, derating and isolation per Rockwell publication 1756-TD002-EN-E and 1756-IN050.
Confirm the group and module current limits for the actual panel temperature.
Do not swap an OA8D for an OA8E to solve a fusing problem without checking whether the group limit is the real cause.
Recheck field devices that rely on low off-state leakage; leakage is unchanged at 3 mA per point.
What is the 1756-OA8E?
An 8-point AC output module with electronic fusing and 2 A per point at 60 °C.
How much current can one point carry?
2 A at 60 °C.
What are the group and module limits?
4 A per group at 30 °C derating to 2 A at 60 °C; 8 A per module at 30 °C derating to 4 A at 60 °C.
What surge can it handle?
20 A for 43 ms per point, repeatable every 2 s.
How much backplane power does it use?
7.02 W total.
What does it dissipate?
5.5 W at 60 °C, 18.76 BTU/hr.
What is the on-state voltage drop?
Up to 4 V peak at 2 A.
How much off-state leakage?
3 mA per point maximum.
What minimum load is required?
10 mA per point.
Data sources. Technical values on this page come from Rockwell publications 1756-TD002 (ControlLogix I/O Modules Specifications) - the table for 1756-OA8E, including backplane current, dissipation and per-point derating and the manufacturer's product page for 1756-OA8E. Values re-checked 16 November 2026.