Product Details:
Payment & Shipping Terms:
|
The 1734-FPD is a passive slice: it passes every POINT I/O backplane signal through except the internal field power bus, which it breaks and restarts from whatever the terminals are wired to.
It draws nothing and dissipates nothing. What it buys is voltage partitioning - a group of slices on 120V AC, the next group on 24V DC, or outputs on a separate supply from inputs, without adding another power supply to the rack.
| 1734-AENT | EtherNet/IP adapter, 10/100 Mbit, 63 modules, 1.0 A POINTBus | IN STOCK |
| 1734-ADN | DeviceNet adapter, 125/250/500 kbit, 63 modules | IN STOCK |
| 1734-ADNX | DeviceNet adapter with Subnet scanner, node 0 on the subnet | IN STOCK |
| 1734-ACNR | ControlNet adapter, redundant coax A/B, node 01...99 | IN STOCK |
| 1734-APB | PROFIBUS DP adapter, 63 modules on one DP node | IN STOCK |
| 1734-PDN | DeviceNet communication interface, 24V DC 400 mA, 1.3 A POINTBus | IN STOCK |
| 1734-EP24DC | 24V DC expansion power supply, 1.3 A POINTBus at 19.2...28.8V input | IN STOCK |
| 1734-EPAC | 120/240V AC expansion power supply, 1.3 A POINTBus, 3250V DC isolation | IN STOCK |
| 1734-FPD | Field potential distributor, breaks the field power bus, no current draw | IN STOCK |
| 1734-ARM | Address reserve module, 75 mA POINTBus, keeps a slot addressed | IN STOCK |
Function |
Breaks the internal field power bus and starts a new segment |
Field power bus supply voltage |
12V DC, 24V DC, 10...28.8V DC range; 120/240V AC, 50/60 Hz |
Field power bus voltage, max |
264V AC |
POINTBus current |
Pass through - the module consumes none |
Power consumption |
None |
Power dissipation |
None |
Indicators |
None |
Isolation voltage |
50V continuous, tested at 2600V DC for 60 s |
Module location |
Between I/O modules in the POINT I/O system |
Field wiring terminals |
6 = +V DC or L1, 4 = -V DC or L2/N, 2 = chassis ground |
Dimensions, HxWxD |
79.8 x 25.3 x 133.1 mm |
Weight, approx |
0.12 kg |
Wire size |
0.25...2.5 mm2 (24...14 AWG), 75 deg C or greater, 1.2 mm insulation max |
Terminal base screw torque |
0.6 Nm (7 lb-in) |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN059 (module specifications) and 1734-UM016 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Power consumption, dissipation, thermal dissipation and POINTBus current all read zero or pass-through in 1734-IN059. The module is a partition, not a source. If a segment needs more POINTBus current, that is the 1734-EP24DC or 1734-EPAC; the FPD only changes which field voltage the slices to its right see.
The field bus range covers 12V DC, 24V DC and 10...28.8V DC, plus 120V AC and 240V AC at 50/60 Hz, with a 264V AC maximum. Wiring is terminal 6 for +V DC or L1, terminal 4 for -V DC or L2/N, terminal 2 for chassis ground - the same three-point pattern on both DC and AC.
Typical use: 1734-IB8 input slices on 24V DC, then an FPD, then 1734-OA2 or 1734-OW4 slices fed at 120V AC. Isolation is 50V continuous, tested at 2600V DC for 60 s, so the partition is a functional separation, not a safety barrier for mains faults.
The I/O module in the base to the right has to come out first, then the RTB, then the orange DIN rail locking screw. Because the slice carries the bus through, pulling it with power on breaks the field power to every module to the right of it.
What does 1734-FPD actually do?
It breaks the internal field power bus and restarts it from the voltage wired to its terminals, so modules to the right run on a different field supply.
Does it consume POINTBus current or generate heat?
No. Consumption, power dissipation and thermal dissipation are all none, and POINTBus current is pass-through.
What voltages can it switch the field bus to?
12/24V DC in the 10...28.8V DC range, or 120/240V AC at 50/60 Hz, with a 264V AC maximum.
How is it wired?
Terminal 6 = +V DC or L1, terminal 4 = -V DC or L2/N, terminal 2 = chassis ground, at 0.6 Nm and 0.25...2.5 mm2 wire.
What isolation does it provide?
50V continuous, tested at 2600V DC for 60 s, with no indicators on the module.