The 1734-IV4 is the sourcing counterpart of the 1734-IB series: instead of sinking current from a powered sensor, it feeds the input circuit from field power and expects the sensor to pull that point low. 4 points on one slice, 24V DC nominal.
That direction matters at commissioning. A sourcing input is wired to a sinking sensor or a dry contact to common, and reversing the two is the single most common cause of a slice that reads all eight points ON.
| 1734-IV4 | 4 sourcing 24V DC inputs, 2...15 mA per point, 31.8 g | IN STOCK |
| 1734-IV8 | 8 sourcing 24V DC inputs, 1.2 W dissipation, 32.3 g | IN STOCK |
| 1734-IB4D | 4 sinking 24V DC inputs with open-wire and short circuit diagnostics | IN STOCK |
Number of inputs |
4 (1 group of 4), sourcing |
Voltage, on-state, nom |
24V DC |
Voltage, on-state range |
11...28.8V DC |
Voltage, off-state range |
-3...+5V DC |
Current, on-state range |
2...15 mA |
Current, off-state, max |
1.5 mA |
Input filter time |
0.5 ms hardware plus 0...65 ms selectable |
POINTBus current, max |
75 mA @ 5V DC |
Power dissipation, max |
1.0 W @ 28.8V DC |
Thermal dissipation, max |
3.4 BTU/hr @ 28.8V DC |
Isolation voltage |
50V (continuous), reinforced insulation, type tested at 2500V DC for 60 s, field side to system |
External DC power supply |
None required - the module sources its inputs from field power |
Terminal base |
1734-TB or 1734-TBS |
Keyswitch position |
1 |
Dimensions, HxWxD |
56 x 12 x 75.5 mm |
Weight, approx |
31.75 g |
Temperature, operating |
-20...55 deg C (-4...131 deg F), T4A |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-SG001E-EN-P (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
With a sourcing input the module supplies the wetting current and the field device sinks it. A PNP sensor drops straight in; an NPN sensor will not, and neither will a sinking-output photoeye. Decide the sensor family before ordering the slice, because the two directions are not field-convertible.
On-state starts at 11V DC, off-state is guaranteed between -3V and +5V DC. The upper bound is 28.8V, so a nominal 24V supply with normal tolerance is inside the window and a 30V rail is not. Reverse polarity on the field supply is handled by the module, but a sustained 30V still sits above the rating.
On-state current range 2...15 mA, off-state leakage up to 1.5 mA. The 2 mA floor is what wets a dry contact; a sensor that only sources 500 uA may never cross it, which reads as a stuck-off point. Leakage above 1.5 mA from a failed sensor or a long shielded run reads as a stuck-on point.
0.5 ms hardware filter plus a 0...65 ms selectable digital window. The hardware stage is short enough for a counter-style signal at low speed; the digital stage is the debounce for mechanical contacts. Dissipation is 1.0 W @ 28.8V DC per slice at 28.8V DC - 3.4 BTU/hr @ 28.8V DC BTU/hr - and the slice draws 75 mA from the 5V POINTBus.
Panels that already run PNP sensors, or that feed inputs from a common positive rail, save the interposing relays and the extra terminal blocks when they use 1734-IV4 instead of a sinking slice. The isolation is 50V reinforced, type tested at 2500V DC for 60 s, the same envelope as the IB family, so replacing an IB slice with an IV slice does not change the panel's segregation plan.
What is a sourcing input?
The module supplies the wetting current from field power and the field device sinks it to common. PNP sensors wire directly; NPN sensors do not.
What voltage range does 1734-IV4 accept?
24V DC nominal, on-state 11...28.8V DC, off-state guaranteed from -3V to +5V DC.
How much current does each point need?
Between 2 and 15 mA in the on state, with a maximum of 1.5 mA leakage in the off state.
Which base fits 1734-IV4?
1734-TB or 1734-TBS at keyswitch position 1, drawing 75 mA from the 5V POINTBus.
How does it differ from 1734-IB4?
Direction of current only: IB4 sinks, IV4 sources. Voltage window, filter time and the 50V reinforced isolation are the same family values.