The 1734-IR2E is the precision version of the RTD input: 2.4 mohm per count, four times finer than the 1734-IR2, but restricted to a 78.12...234.38 ohm window and to 100 ohm Pt sensors between -50 and +325 deg C.
It exists for narrow-span measurements where the temperature range is known and small - a bearing temperature or a chilled-water loop - not for general-purpose plant temperature mapping.
| 1734-IR2 | 2-channel RTD input, 0...600 ohm, 16 bits | IN STOCK |
| 1734-IR2E | 2-channel high resolution RTD input, 0.006 deg C per count | IN STOCK |
| 1734-IT2I | 2-channel isolated thermocouple input, types B/C/E/J/K/N/R/S/T | IN STOCK |
Input range |
78.12...234.38 ohm |
Resolution per count |
2.4 mohm, 0.006 °C (Pt 385 @ 25 °C), 0.0114 °C at 77 °C |
Sensors supported |
100 ohm Pt, alpha 0.00385 European, -50...325 °C only |
Maximum overload |
No input protection |
Notch filter |
-3 dB at 13.1 Hz (50 Hz), 15.7 Hz (60 Hz), 26.2 Hz (100 Hz), 31.4 Hz (120 Hz), 52.4 Hz (200 Hz), 62.9 Hz (240 Hz), 78.6 Hz (300 Hz), 104.8 Hz (400 Hz), 125.7 Hz (480 Hz) |
Number of inputs |
2 single-ended, non-isolated |
Resolution |
16 bits |
Absolute accuracy |
0.1% full scale @ 25 °C |
Accuracy drift with temperature |
30 ppm/°C |
Conversion type |
Delta Sigma |
Common mode rejection |
120 dB |
Normal mode rejection |
100 dB |
Input update rate |
40 ms @ 50 Hz notch, 33 ms @ 60 Hz (default), 20 ms @ 100 Hz, 17 ms @ 120 Hz, 10 ms @ 200 Hz, 8 ms @ 240 Hz, 7 ms @ 300 Hz, 5 ms @ 400 Hz, 4 ms @ 480 Hz (per module) |
Step response |
60 ms @ 50 Hz, 50 ms @ 60 Hz, 30 ms @ 100 Hz, 25 ms @ 120 Hz, 15 ms @ 200 Hz, 13 ms @ 240 Hz, 10 ms @ 300 Hz, 8 ms @ 400 Hz, 6 ms @ 480 Hz (per channel) |
Data format |
Signed integer |
Calibration |
Factory calibrated |
Terminal base |
1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS |
Terminal base screw torque |
0.8 Nm (7 lb-in) |
Keyswitch position |
6 |
POINTBus current, max |
220 mA @ 5V DC |
Power dissipation, max |
1.0 W |
Thermal dissipation, max |
3.3 BTU/hr |
Isolation voltage |
50V continuous, Basic insulation, I/O to system, type tested 1600V AC for 60 s |
External DC power |
None required |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Weight, approx |
36 g |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN011-EN-E (module specifications) and 1734-UM004 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
2.4 mohm per count against 9.5 mohm, and 0.006 deg C per count against 0.03 deg C for a Pt 385 sensor at 25 deg C. The price is the input window: 78.12 to 234.38 ohm, which for a Pt100 corresponds to -50 to +325 deg C. Outside that window the reading saturates, so a sensor that is expected to see 400 deg C cannot use this module at all.
A 5 deg C control band on a bearing housing is a 0.02 ohm change in a Pt100. At 9.5 mohm per
count the IR2 resolves that in roughly two counts; at 2.4 mohm the IR2E resolves it in eight. That is the difference between a trend that moves smoothly and one that steps, and it decides whether a slow-developing fault is visible before the alarm point.
Both modules use delta-sigma conversion with 120 dB common mode and 100 dB normal mode rejection, are factory calibrated to 0.1% of full scale with 30 ppm/deg C drift, and both are specified with no input protection and 50V basic isolation tested at 1600V AC for 60 s. The E does not add ruggedness, only resolution.
The supported table lists a single entry: 100 ohm Pt at alpha 0.00385, -50...325 deg C. No 200 ohm, no US alpha 0.003916, no nickel, no copper. A maintenance department that standardises on IR2E has to standardise its sensors with it - mixing a US-curve Pt100 into that slot produces a reading that is wrong by several degrees and looks plausible.
Keyswitch 6, 220 mA at 5V DC, 1.0 W dissipation, 3.3 BTU/hr, TB/TBS/TOP/TOPS bases, 36 g, 56.6 x 12.1 x 77.5 mm, no external supply. Physically interchangeable with the IR2, which is convenient - and dangerous, because a module swap between the two changes the usable temperature range without any visible difference on the label's part number shape.
What is the difference between 1734-IR2 and 1734-IR2E?
Resolution and range. IR2E resolves 2.4 mohm per count (0.006 deg C) over 78.12...234.38 ohm with 100 ohm Pt only from -50 to +325 deg C; IR2 resolves 9.5 mohm over 0...600 ohm with eight sensor types from -200 to 870 deg C.
Which sensors can 1734-IR2E read?
Only 100 ohm Pt at alpha 0.00385 (European curve), -50...325 deg C. No 200 ohm, nickel or copper sensors.
How accurate is it?
0.1% of full scale at 25 deg C, with 30 ppm/deg C drift, factory calibrated.
Is the input protected against field power?
No - the module has no input protection, so power must be removed before changing a sensor.
Can 1734-IR2E replace 1734-IR2 in the same base?
Physically yes, both use TB/TBS/TOP/TOPS at keyswitch 6 and draw 220 mA. But the usable range and sensor list change, so the swap only works if the sensor is a 100 ohm Pt within the E's -50...325 deg C window.
The table reproduces the sibling list this page publishes, with each catalog number put in the class of module it is; the paragraph after it places this part in that ladder, and the arithmetic at the end uses this page's own POINTBus figure against the 1.0 A budget the adapters print.
| Catalog number | What the published line says | Class of module |
| 1734-IR2 | 2-channel RTD input, 0...600 ohm, 16 bits | Temperature input |
| 1734-IR2E | 2-channel high resolution RTD input, 0.006 deg C per count | Temperature input |
| 1734-IT2I | 2-channel isolated thermocouple input, types B/C/E/J/K/N/R/S/T | Temperature input |
1734-IR2E is the high-resolution RTD module, 0.006 deg C per count at 2.4 mOhm, and it is the middle of three in this list: 1734-IR2 reads 0...600 ohm at 16 bits and 1734-IT2I takes thermocouples instead. The printed sensor support on this page is narrow - 100 ohm Pt, alpha 0.00385, -50...325 deg C only.
At the 220 mA this module prints, the 1.0 A POINTBus carries 4 modules with nothing left over. A full 63-module rack of this module would be 13860 mA, 13.9 times the 1.0 A budget, so the 63-module figure is a slot count and the current is what decides how many expansion supplies go into the rack.
Two catalog numbers one digit apart often differ in exactly one published figure, and that figure is the one the specification is written around - which is why the ladder is worth reading as a table rather than as a list of options.
What the printed data does not carry: this page prints the sibling descriptions but not their POINTBus currents, so the 220 mA is the only draw in the table that can be used; and no page in this family states a maximum number of modules between two power supplies.
Source: Rockwell publication 1734-IN001 (POINT I/O module and adapter installation instructions) and the module specification tables published on these pages; the class column and the module count are read off the printed lines, not assumed.
Other catalog numbers and accessories for the same range are collected in the Allen-Bradley POINT I/O 1734 modules category.