Product Details:
Payment & Shipping Terms:
|
The 1734-IR2E is the precision version of the RTD input: 2.4 mohm per count, four times finer than the 1734-IR2, but restricted to a 78.12...234.38 ohm window and to 100 ohm Pt sensors between -50 and +325 deg C.
It exists for narrow-span measurements where the temperature range is known and small - a bearing temperature or a chilled-water loop - not for general-purpose plant temperature mapping.
| 1734-IR2 | 2-channel RTD input, 0...600 ohm, 16 bits | IN STOCK |
| 1734-IR2E | 2-channel high resolution RTD input, 0.006 deg C per count | IN STOCK |
| 1734-IT2I | 2-channel isolated thermocouple input, types B/C/E/J/K/N/R/S/T | IN STOCK |
Input range |
78.12...234.38 ohm |
Resolution per count |
2.4 mohm, 0.006 °C (Pt 385 @ 25 °C), 0.0114 °C at 77 °C |
Sensors supported |
100 ohm Pt, alpha 0.00385 European, -50...325 °C only |
Maximum overload |
No input protection |
Notch filter |
-3 dB at 13.1 Hz (50 Hz), 15.7 Hz (60 Hz), 26.2 Hz (100 Hz), 31.4 Hz (120 Hz), 52.4 Hz (200 Hz), 62.9 Hz (240 Hz), 78.6 Hz (300 Hz), 104.8 Hz (400 Hz), 125.7 Hz (480 Hz) |
Number of inputs |
2 single-ended, non-isolated |
Resolution |
16 bits |
Absolute accuracy |
0.1% full scale @ 25 °C |
Accuracy drift with temperature |
30 ppm/°C |
Conversion type |
Delta Sigma |
Common mode rejection |
120 dB |
Normal mode rejection |
100 dB |
Input update rate |
40 ms @ 50 Hz notch, 33 ms @ 60 Hz (default), 20 ms @ 100 Hz, 17 ms @ 120 Hz, 10 ms @ 200 Hz, 8 ms @ 240 Hz, 7 ms @ 300 Hz, 5 ms @ 400 Hz, 4 ms @ 480 Hz (per module) |
Step response |
60 ms @ 50 Hz, 50 ms @ 60 Hz, 30 ms @ 100 Hz, 25 ms @ 120 Hz, 15 ms @ 200 Hz, 13 ms @ 240 Hz, 10 ms @ 300 Hz, 8 ms @ 400 Hz, 6 ms @ 480 Hz (per channel) |
Data format |
Signed integer |
Calibration |
Factory calibrated |
Terminal base |
1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS |
Terminal base screw torque |
0.8 Nm (7 lb-in) |
Keyswitch position |
6 |
POINTBus current, max |
220 mA @ 5V DC |
Power dissipation, max |
1.0 W |
Thermal dissipation, max |
3.3 BTU/hr |
Isolation voltage |
50V continuous, Basic insulation, I/O to system, type tested 1600V AC for 60 s |
External DC power |
None required |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Weight, approx |
36 g |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN011-EN-E (module specifications) and 1734-UM004 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
2.4 mohm per count against 9.5 mohm, and 0.006 deg C per count against 0.03 deg C for a Pt 385 sensor at 25 deg C. The price is the input window: 78.12 to 234.38 ohm, which for a Pt100 corresponds to -50 to +325 deg C. Outside that window the reading saturates, so a sensor that is expected to see 400 deg C cannot use this module at all.
A 5 deg C control band on a bearing housing is a 0.02 ohm change in a Pt100. At 9.5 mohm per
count the IR2 resolves that in roughly two counts; at 2.4 mohm the IR2E resolves it in eight. That is the difference between a trend that moves smoothly and one that steps, and it decides whether a slow-developing fault is visible before the alarm point.
Both modules use delta-sigma conversion with 120 dB common mode and 100 dB normal mode rejection, are factory calibrated to 0.1% of full scale with 30 ppm/deg C drift, and both are specified with no input protection and 50V basic isolation tested at 1600V AC for 60 s. The E does not add ruggedness, only resolution.
The supported table lists a single entry: 100 ohm Pt at alpha 0.00385, -50...325 deg C. No 200 ohm, no US alpha 0.003916, no nickel, no copper. A maintenance department that standardises on IR2E has to standardise its sensors with it - mixing a US-curve Pt100 into that slot produces a reading that is wrong by several degrees and looks plausible.
Keyswitch 6, 220 mA at 5V DC, 1.0 W dissipation, 3.3 BTU/hr, TB/TBS/TOP/TOPS bases, 36 g, 56.6 x 12.1 x 77.5 mm, no external supply. Physically interchangeable with the IR2, which is convenient - and dangerous, because a module swap between the two changes the usable temperature range without any visible difference on the label's part number shape.
What is the difference between 1734-IR2 and 1734-IR2E?
Resolution and range. IR2E resolves 2.4 mohm per count (0.006 deg C) over 78.12...234.38 ohm with 100 ohm Pt only from -50 to +325 deg C; IR2 resolves 9.5 mohm over 0...600 ohm with eight sensor types from -200 to 870 deg C.
Which sensors can 1734-IR2E read?
Only 100 ohm Pt at alpha 0.00385 (European curve), -50...325 deg C. No 200 ohm, nickel or copper sensors.
How accurate is it?
0.1% of full scale at 25 deg C, with 30 ppm/deg C drift, factory calibrated.
Is the input protected against field power?
No - the module has no input protection, so power must be removed before changing a sensor.
Can 1734-IR2E replace 1734-IR2 in the same base?
Physically yes, both use TB/TBS/TOP/TOPS at keyswitch 6 and draw 220 mA. But the usable range and sensor list change, so the swap only works if the sensor is a 100 ohm Pt within the E's -50...325 deg C window.