Product Details:
Payment & Shipping Terms:
|
The 1734-IE2C reads two 4...20 mA or 0...20 mA loops into a POINT I/O slice with 16-bit resolution over the 0...21 mA span, which is 0.32 µA per count. Both channels are single-ended and share a common, and the module is unipolar only.
At the default configuration each channel scales 4 mA to 3277 and 20 mA to 16,383 in a 16-bit signed integer - the 4 mA offset is kept visible so a broken loop reads as an under-range value rather than as zero process value.
| 1734-IE2C | 2 analog current inputs, 4...20 mA, 16 bits over 0...21 mA, 60 ohm | IN STOCK |
| 1734-IE2V | 2 analog voltage inputs, 0...10V or +/-10V, 15 bits plus sign, 100 kOhm | IN STOCK |
| 1734-IE4S | 4 analog inputs, 0...20 mA / 0...10V, 16 bits, isolated | IN STOCK |
| 1734-IE8C | 8 analog current inputs, 4...20 mA, 16 bits | IN STOCK |
Number of inputs |
2 single-ended, non-isolated, current |
Resolution |
16 bits over 0...21 mA, 0.32 uA/count |
Input current range |
4...20 mA (default) or 0...20 mA, unipolar |
Input impedance |
60 ohm |
Accuracy drift with temperature |
30 ppm/deg C |
Isolation voltage |
50V continuous, no isolation between channels, tested 2550V DC for 60 s |
Power dissipation, max |
0.6 W @ 28.8V DC |
Thermal dissipation, max |
2.0 BTU/hr @ 28.8V DC |
Data format |
16-bit signed integer, default scaling 3277 @ 4 mA and 16,383 @ 20 mA |
Temperature code |
T5 (North American) |
Field wiring terminations |
0/1 - input 0/1, 2/3 - chassis ground, 4/5 - common, 6/7 - supply |
Terminal base |
1734-TB, 1734-TBS, 1734-TB3, 1734-TB3S, 1734-TOP, 1734-TOPS, 1734-TOP3 or 1734-TOP3S |
Terminal base screw torque |
0.6 Nm (7 lb-in) |
Indicator |
1 module status, 1 network status, 2 input status (green/red) |
Keyswitch position |
3 |
POINTBus current, max |
75 mA @ 5V DC |
Absolute accuracy |
0.1% full scale @ 25 °C, including offset, gain, non-linearity and repeatability |
Conversion type |
Delta Sigma |
Common mode rejection |
120 dB |
Input update rate |
120 ms @ 50 Hz notch, 100 ms @ 60 Hz (default), 24 ms @ 250 Hz, 12 ms @ 500 Hz |
Input step response |
80 ms @ 50 Hz, 70 ms @ 60 Hz, 16 ms @ 250 Hz, 8 ms @ 500 Hz |
Digital filter time constant |
0...10,000 ms (default 0 ms) |
Field power |
24V DC nominal, 10...28.8V DC range, from the internal field power bus |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Weight, approx |
33 g |
Wiring category |
1 - on signal ports |
Wire size |
0.25...2.5 mm2 (22...14 AWG) shielded copper rated 75 °C or greater, 1.2 mm insulation max |
Operating temperature |
-20...55 °C (-4...131 °F) |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN027G-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Terminals 0 and 1 are the two inputs, 2 and 3 are chassis ground, 4 and 5 are the shared common and 6 and 7 are the 12/24V DC supply from the internal field power bus. Because the channels are non-isolated and share one common, both loops must sit on the same reference; a floating transmitter on a second supply needs an isolator, not a second common.
The default range is 4...20 mA, so the module reports under-range when a loop drops below about 3.6 mA and over-range above roughly 21 mA. 0...20 mA is available per module but loses that broken-wire discrimination - the two modes are a configuration choice, not a wiring change.
16 bits over 21 mA gives 0.32 µA per count, but the specified accuracy is 0.1% of full scale at 25 °C, including offset, gain, non-linearity and repeatability, drifting 30 ppm/°C. For a 4...20 mA loop that is about 21 µA of absolute error - fine for pressure and level, not enough for a calibrated metering circuit.
The notch filter sets the speed: 100 ms per module update at 60 Hz with a 70 ms step response, 24 ms at 250 Hz, 12 ms at 500 Hz. A 50 Hz notch is 120 ms. Choose the notch for the mains frequency in the plant and accept that the analog channel is far slower than a digital input - do not put a fast pressure trip on this module.
The input image is six bytes: two data words plus one status byte each. The status bits report channel fault, calibration mode, low alarm, high alarm, low/low alarm, high/high alarm and under-range, so alarm annunciation happens in the module without extra ladder logic for the threshold comparison itself.
What is the resolution of 1734-IE2C?
16 bits over the 0...21 mA span, which is 0.32 uA per count. The 4...20 mA range maps 4 mA to 3277 and 20 mA to 16,383 at the default scaling.
Are the two input channels isolated from each other?
No. Both channels are single-ended and non-isolated and share a common at terminals 4 and 5. Isolation is 50V continuous from field to system, tested at 2550V DC for 60 s, with no channel-to-channel isolation.
What accuracy can I expect over temperature?
0.1% of full scale at 25 deg C including offset, gain, non-linearity and repeatability, with 30 ppm/deg C drift. That is roughly 21 uA of error on a 4...20 mA loop across the whole span.
Why does a 4...20 mA input show an under-range value?
The module is configured for 4...20 mA by default and reports values below 4 mA as under-range, which is how a broken wire or a dead loop is detected. A 0...20 mA configuration removes that diagnostic.
How fast does the module update?
100 ms per module at the default 60 Hz notch, 120 ms at 50 Hz, 24 ms at 250 Hz and 12 ms at 500 Hz. The step response per channel is 70 ms at 60 Hz.
Which terminal bases and wire are accepted?
1734-TB, 1734-TBS, 1734-TB3, 1734-TB3S, 1734-TOP, 1734-TOPS, 1734-TOP3 or 1734-TOP3S, torque 0.6 Nm, with 0.25...2.5 mm2 (22...14 AWG) shielded copper rated 75 deg C or greater.