Product Details:
Payment & Shipping Terms:
|
The 1734-EP24DC is the 24V DC expansion supply: it takes 24V DC in, generates the 5V POINTBus for 4 to 17 modules to its right, and starts a new field power segment for them at the same time.
The reason it exists is a hard ceiling. A single 1734 adapter or 1734-PDN supplies 1.3 A of POINTBus current and 63 modules total; past that, the rack needs another supply, and the EP24DC is what the 24V DC side uses to get there.
| 1734-AENT | EtherNet/IP adapter, 10/100 Mbit, 63 modules, 1.0 A POINTBus | IN STOCK |
| 1734-ADN | DeviceNet adapter, 125/250/500 kbit, 63 modules | IN STOCK |
| 1734-ADNX | DeviceNet adapter with Subnet scanner, node 0 on the subnet | IN STOCK |
| 1734-ACNR | ControlNet adapter, redundant coax A/B, node 01...99 | IN STOCK |
| 1734-APB | PROFIBUS DP adapter, 63 modules on one DP node | IN STOCK |
| 1734-PDN | DeviceNet communication interface, 24V DC 400 mA, 1.3 A POINTBus | IN STOCK |
| 1734-EP24DC | 24V DC expansion power supply, 1.3 A POINTBus at 19.2...28.8V input | IN STOCK |
| 1734-EPAC | 120/240V AC expansion power supply, 1.3 A POINTBus, 3250V DC isolation | IN STOCK |
| 1734-FPD | Field potential distributor, breaks the field power bus, no current draw | IN STOCK |
| 1734-ARM | Address reserve module, 75 mA POINTBus, keeps a slot addressed | IN STOCK |
Input voltage rating |
24V DC nominal, 10...28.8V DC range |
POINTBus output, horizontal mounting |
1 A @ 10...19.2V input; 1.3 A @ 19.2...28.8V input |
POINTBus output, vertical mounting |
1 A @ 10...28.8V input |
I/O module capacity |
4...17 modules, depending on the current rating of each module |
Field side power requirement |
24V DC @ 400 mA max (28.8V DC maximum) |
Inrush current, max |
6 A for 10 ms |
Power consumption, max |
9.8 W @ 28.8V DC |
Power dissipation, max |
3.0 W @ 28.8V DC |
Thermal dissipation, max |
10.0 BTU/hr @ 28.8V DC |
Isolation voltage |
50V continuous, tested at 2600V DC for 60 s |
Field power bus |
10 A max, 10...28.8V DC |
Module location |
Between I/O modules, breaks the field power bus |
Dimensions, HxWxD |
76.2 x 25.4 x 133.4 mm |
Weight, approx |
120 g |
Wire size |
0.324...2.08 mm2 (22...14 AWG), 75 deg C or greater |
Terminal base screw torque |
0.6 Nm (7 lb-in) |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN058 (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
1.3 A only above 19.2V input, and only on horizontal DIN rail. At 10...19.2V input, or vertically mounted at any voltage, the output is 1 A. On a 24V rail that sits at 20V or dips during a brownout, the module count drops from 17 to 13 at 75 mA per slice.
Field power to the left is separated from field power to the right, so inputs and outputs, or analog and digital, can run from different supplies. The field side draws 400 mA maximum at 28.8V DC - that is the supply's own field-side requirement, not the load current of the field devices.
+V DC on terminals 6 and 7, -V DC on 4 and 5, chassis ground on 2 and 3 - each pair repeated for daisy-chaining the supply to the next segment. Never connect 120/240V AC to this module; that is the 1734-EPAC's job.
9.8 W consumption and 3.0 W dissipation at 28.8V DC, 10 BTU/hr. In a sealed enclosure that is the number to add when summing the thermal load; the AC version dissipates more than twice as much.
How much POINTBus current does 1734-EP24DC provide?
1.3 A at 19.2...28.8V input and 1 A at 10...19.2V input, horizontal mounting; 1 A at 10...28.8V input when mounted vertically.
How many I/O modules can it support?
4 to 17, depending on each module's POINTBus current - 17 only with 75 mA slices at 19.2V or above.
Can 120/240V AC be connected to it?
No. The EP24DC takes 24V DC only; use the 1734-EPAC for AC field power.
What current does the field side draw?
400 mA maximum at 28.8V DC, with 6 A inrush for 10 ms.
What isolation and dissipation does it have?
50V continuous isolation tested at 2600V DC for 60 s, with 3.0 W dissipation and 10 BTU/hr at 28.8V DC.
1734-EP24DC is a head-of-slice unit in the POINT I/O system. Head units sit to the left of the I/O modules and either own the network connection, supply the POINTBus, or distribute field power; the modules to their right exist only as a slice hanging off that head unit.
| Attribute | Value |
| Catalog number | 1734-EP24DC |
| Role | 24V DC expansion power supply |
| Width | 56.1 mm (2.21 in.) for the network adapters, 25.4 mm (1.00 in.) for expansion supplies, distributors and the compact head unit |
| Mounting | DIN rail, at the head of the slice |
| System clearance | 25.4 mm on all sides; 50.8 mm above when safety modules are present |
| Ordering note | Terminal bases for the I/O modules are separate line items |
POINTBus current is the budget that decides how many modules a slice can carry: most digital and analog modules draw 75 mA, the 1734-OW2 draws 80 mA, and 1734-IB4D draws 50 mA. The usable current of the adapter, plus that of any expansion power supply, divided by the per-module draw gives the maximum slice length, and that is a planning calculation rather than a rule of thumb.
Mechanically the system is width-driven: adapters occupy 56.1 mm, expansion power supplies and field power distributors 25.4 mm each, standard I/O modules 12.1 mm each, and safety I/O modules 24.1 mm each. Total panel width is the sum of those, and a layout that assumes a uniform module width is wrong on both the adapter and the safety side.
Clearance is a specification, not a courtesy: 25.4 mm on all sides of the system is the minimum, and a system with POINT I/O safety modules needs 50.8 mm above the assembly. Cabinets that pass at 25 mm on a digital-only slice fail once a safety module is added to the same rail.
The width difference between 56.1 mm and 25.4 mm is the difference between an adapter that carries a network port and a unit that only carries power. Both can head a slice, and both feed the POINTBus, but only the adapter appears on the network as a node; the expansion supply and the field power distributor exist to extend the slice inside the cabinet.
Ordering discipline for this family is the practical point: the module alone does not make a working channel, because the terminal base assembly is a separate catalog number, the RTB is a separate replacement part, and the head unit sets how many modules the slice can carry.