The 1734-OV4E is the four-point protected sinking output of the POINT I/O Series C range. Four channels in one group, 1.0 A per channel with a 3.0 A module ceiling, red fault indication per channel and one byte of status data back to the controller.
Its on-state drop is 0.7V DC at full load and 55 deg C, and isolation is 240V basic type tested at 2550V DC for 60 s - both higher field-side figures than the sourcing outputs.
| 1734-OV2E | 2 protected sinking outputs, 0.7V DC drop, 2.0 A per module | IN STOCK |
| 1734-OV4E | 4 protected sinking outputs, 0.7V DC drop, 3.0 A per module | IN STOCK |
| 1734-OV8E | 8 protected sinking outputs, 0.7V DC drop, 3.0 A per module | IN STOCK |
Number of outputs |
4 (1 group of 4), non-isolated, sinking |
Output current rating, max per module |
1.0 A per output, not to exceed 3.0 A max per module |
External DC supply current |
16 mA |
On-state voltage, min |
10V DC |
On-state voltage, nominal |
24V DC |
On-state voltage, max |
28.8V DC |
On-state voltage drop, max |
0.7V DC @ 28.8V DC, 55 deg C, full load |
On-state current, min per channel |
1.0 mA |
On-state current, max per channel |
1.0 A (electronically protected) |
Off-state voltage, max |
28.8V DC |
Off-state leakage, max |
0.5 mA |
Output signal delay |
0.1 ms off to on, 0.1 ms on to off |
Surge current |
2 A for 10 ms, repeatable every 3 s |
Data image |
Produces 1 byte of input data (status), consumes 1 byte of output data |
Pilot duty rating |
24V DC 1.0 A |
Keyswitch position |
1 |
Module location |
1734-TB or 1734-TBS wiring base assembly |
POINTBus current, max |
75 mA @ 5V DC |
Isolation voltage |
240V, Basic Insulation Type, tested at 2550V DC for 60 s, output to system |
External DC supply, nominal |
24V DC |
External DC supply range |
10...28.8V DC |
Terminal base screw torque |
0.6 Nm |
Wire size |
0.25...2.5 mm2 (22...14 AWG) solid or stranded copper, 75 deg C or greater |
Dimensions, HxWxD |
56 x 12 x 75.5 mm |
Wire category |
2 - on signal ports |
Temperature code |
T4 (North American) |
Operating temperature |
-20...55 deg C |
Enclosure |
None (open style) |
Power dissipation, max @ 28.8V DC |
1.2 W @ 28.8V DC |
Thermal dissipation, max @ 28.8V DC |
4.1 BTU/hr @ 28.8V DC |
Weight, approx |
33.17 g |
Field wiring terminations |
0/1/2/3 - Outputs 0/1/2/3, 4/5/6/7 - Supply |
Indicators |
4 yellow output status, 4 red output fault, 2 green/red module and network status |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN585D-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Terminals 0 to 3 are outputs 0 to 3 and terminals 4 to 7 are all supply terminals on this module, which differs from 1734-OB4 where 4 to 7 are common. Field power comes from the internal power bus, sourced from the adapter, a 1734-FPD or a 1734-EP24DC, and the module draws 16 mA of it for the output stage.
Four channels at full 1.0 A would be 4 A, so in practice three channels at rating or four averaging 0.75 A. Because protection trips per channel at 1.0 A, an oversized load shows up as a red LED on that channel only, which is exactly the diagnostic the unprotected modules cannot give.
The slice dissipates 1.2 W at 28.8V DC, 4.1 BTU/hr, and the load current adds heat in the field devices rather than in the module. In an enclosure sized by temperature rise this sits between the two-point and eight-point versions and is a reason to split a six-channel load across two four-point modules.
One byte is produced and one byte consumed. The produced byte carries channel status, so an HMI or a program can flag a tripped channel without waiting for an operator to walk the panel. That is the practical reason to pay for the E variant on a remote station.
Mounts on 1734-TB or 1734-TBS; wire 0.25 to 2.5 mm2 (22 to 14 AWG) copper at 75 deg C or greater, 1.2 mm maximum insulation; terminal base screw torque 0.6 Nm. The TOP and TB3 bases used elsewhere in the family are not listed for this module.
What is the difference between a 1734-OV8E and a 1734-OB8E?
The 1734-OV8E is a sinking output: it pulls the load to 0V and the load is tied to the positive supply. The 1734-OB8E is a sourcing output: it switches the positive supply to the load and the load returns to common. Both are protected, both are 1.0 A per channel and 3.0 A per module, and both carry a red fault LED per channel.
Why is the on-state voltage drop of a sink output larger than a source output?
The published figure is 0.7V DC maximum at 28.8V DC, 55 deg C and full load, against 0.2V DC for the sourcing 1734-OB family. The drop is part of the protection circuit, so at 1.0 A the module dissipates roughly 0.7 W in the output stage - check it against a load that is sensitive to receiving 23.3V DC rather than 24V DC.
How many bytes does the module exchange with the scanner?
Two. It produces one byte of input data carrying channel status and consumes one byte of output data carrying the channel commands, which is how the module reports a faulted channel back to the controller.
What is the isolation rating?
240V continuous, Basic Insulation Type, tested at 2550V DC for 60 s from output to system. This is a higher field-side rating than the 50V used on the sourcing 1734-OB and 1734-IB families.
Which terminal base and wire gauge?
1734-TB or 1734-TBS only. Wire is 0.25 to 2.5 mm2 (22 to 14 AWG) solid or stranded copper rated 75 deg C or greater with 1.2 mm maximum insulation, and terminal base screw torque is 0.6 Nm - note this is lower than the 0.8 Nm used on the input and sourcing output modules.
What happens on a short circuit?
The channel is electronically protected and limits current to 1.0 A; the yellow status LED goes out and the red fault LED for that channel comes on. Remove the cause and re-energise the channel. Surge capability is 2 A for 10 ms repeatable every 3 s.