The 1734-OB4E is the protected four-point 24V DC sourcing output of the POINT I/O Series C range. Four channels in one group, 1.0 A per channel with a 3.0 A module ceiling, and a red fault LED on every channel.
Electrically it is the same output stage as 1734-OB4; the additional diagnostic hardware is what changes the application, because a single shorted coil no longer takes the whole slice offline without telling you which channel caused it.
| 1734-OB2E | 2 protected sourcing outputs, red fault LED per channel, 2.0 A per module | IN STOCK |
| 1734-OB4E | 4 protected sourcing outputs, red fault LED per channel, 3.0 A per module | IN STOCK |
| 1734-OB8E | 8 protected sourcing outputs, red fault LED per channel, 3.0 A per module | IN STOCK |
Number of outputs |
4 (1 group of 4), non-isolated, sourcing |
Output current rating, per output |
1.0 A |
Output current rating, max, per module |
3.0 A |
External DC supply current |
16 mA |
On-state voltage, min |
10V DC |
On-state voltage, nominal |
24V DC |
On-state voltage, max |
28.8V DC |
On-state voltage drop, max |
0.2V DC |
On-state current, min per channel |
1.0 mA |
Off-state leakage, max |
0.5 mA @ 28.8V DC |
Surge current |
2 A for 10 ms, repeatable every 3 s |
POINTBus current, max |
75 mA @ 5V DC |
Isolation voltage |
50V (continuous), reinforced insulation type, tested 2500V DC for 60 s, field side to system |
External DC supply, nominal |
24V DC |
External DC supply range |
10...28.8V DC |
Terminal base screw torque |
0.8 Nm (7 lb-in) |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Wiring category |
2 - on signal ports |
Operating temperature |
-20...55 °C |
Enclosure |
None (open style) |
Power dissipation, max @ 28.8V DC |
1.2 W @ 28.8V DC |
Thermal dissipation, max @ 28.8V DC |
4.1 BTU/hr @ 28.8V DC |
Weight, approx |
33.17 g |
Module location |
1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS |
Field wiring terminations |
0/1/2/3 - Outputs 0/1/2/3, 4/5/6/7 - Common |
Indicators |
4 yellow output status, 4 red output fault, 2 green/red module and network status |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN056-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Indicator count scales with the module: four yellow status, four red fault and two green/red module/network. On a four-channel slice the fault LED sits directly beside the channel it reports, which is why this module is common on small valve manifolds where a single coil failure stops a station.
1.0 A per output, 3.0 A per module: four channels at full rating would be 4 A, so the realistic loads are three at 1.0 A or four averaging 0.75 A. Compute the simultaneous current, not the nameplate sum, when the manifold only lifts three valves at once.
Outputs 0 to 3 are terminals 0 to 3, common is terminals 4 to 7. The external 24V DC supply feeds the output stage through the internal power bus and the module draws 16 mA from it. Range is 10...28.8V DC, drop 0.2V DC maximum.
Only 1734-TB, 1734-TBS, 1734-TOP and 1734-TOPS are listed for the four-point protected module. If a TB3 base is already installed, it accepts the two-point 1734-OB2E but not this module, so check the base before ordering a replacement.
If diagnostics are handled at the adapter or through the drive, and loads are short-wired interposing relays, 1734-OB4 delivers the same electrical performance for less. The protected version earns its place where a fault must be localised to a channel without instruments.
What does the extra red LED on a protected output give me?
One red output-fault indicator per channel, driven from the logic side. When a channel trips on short circuit or thermal overload its yellow status LED goes off and its red fault LED comes on, so the electrician knows which of the eight loads to look at without pulling the module.
Does a protected module limit current or latch off?
The module limits the channel current and reports the fault; the published rating is 1.0 A per output with a module maximum of 2.0 A for 1734-OB2E and 3.0 A for 1734-OB4E and 1734-OB8E. Clearing the fault is by removing the cause and re-energising the channel - there is no manual reset button.
What is the difference between 1734-OB8 and 1734-OB8E?
The output stage, voltage window and current ratings are identical; the difference is per-channel electronic protection with a dedicated fault indicator instead of module-level reporting only. Both use the same 1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS base.
Are the outputs isolated from the backplane?
Outputs are non-isolated from the external 24V DC field supply and isolated from the system side by 50V continuous reinforced insulation, tested at 2500V DC for 60 s field side to system.
Which bases fit a 1734-OB8E?
1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS. The two-point 1734-OB2E also accepts 1734-TB3, 1734-TB3S, 1734-TOP3 and 1734-TOP3S, so a TB3 position can only take the two-point protected module.
How do I size the field supply?
The module itself draws 8 mA (1734-OB2E), 16 mA (1734-OB4E) or 32 mA (1734-OB8E) from the external 24V DC supply, and the load current passes through the same supply. Add the simultaneous load current to that figure when selecting the 1734-FPD or 1734-EP24DC.