The 1734-OB4 is the four-point 24V DC sourcing output module for POINT I/O Series C. Four channels in one group with a 3.0 A module total gives a station enough drive for a small valve manifold or four interposing relays without spending a second slot.
Each channel is rated 1.0 A with 0.2V DC maximum drop, 0.5 mA maximum leakage and 0.1 ms switching delay, and the external supply current for the output stage is 16 mA at 24V DC.
| 1734-OB2 | 2 sourcing 24V DC outputs, 2.0 A per module, 32.60 g | IN STOCK |
| 1734-OB4 | 4 sourcing 24V DC outputs, 3.0 A per module, 33.17 g | IN STOCK |
| 1734-OB8 | 8 sourcing 24V DC outputs, 3.0 A per module, 35.4 g | IN STOCK |
Outputs per module |
4 (1 group of 4), non-isolated, sourcing |
Output current rating |
1.0 A per output, not to exceed 3.0 A max per module |
External DC supply current |
16 mA |
On-state voltage range, min |
10V DC |
On-state voltage range, nominal |
24V DC |
On-state voltage range, max |
28.8V DC |
On-state voltage drop, max |
0.2V DC |
On-state current, min per channel |
1.0 mA |
Off-state leakage, max |
0.5 mA @ 28.8V DC |
Output signal delay, off to on |
0.1 ms |
Output signal delay, on to off |
0.1 ms |
Surge current |
2 A for 10 ms, repeatable every 3 s |
POINTBus current, max |
75 mA @ 5V DC |
Isolation voltage |
50V (continuous), reinforced insulation type |
External DC supply, nominal |
24V DC |
External DC supply range |
10...28.8V DC |
Terminal base screw torque |
0.8 Nm (7 lb-in) |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Wiring category |
2 - on signal ports |
Temperature code |
T4A (North American), T4 (IEC) |
Operating temperature |
-20...55 °C |
Relative humidity |
5...95% non-condensing |
Enclosure |
None (open style) |
Power dissipation, max @ 28.8V DC |
1.2 W @ 28.8V DC |
Thermal dissipation, max @ 28.8V DC |
4.1 BTU/hr @ 28.8V DC |
Weight, approx |
33.17 g |
Module location |
1734-TB, 1734-TBS, 1734-TOP, 1734-TOPS |
Field wiring terminations |
0/1/2/3 - Outputs 0/1/2/3, 4/5/6/7 - Common |
Indicators |
4 yellow output status, 2 green/red module and network status |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN018-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
The binding limit is the module, not the channel: four channels at 1.0 A would be 4 A and the module allows 3.0 A. In practice that means three fully loaded channels, or four channels averaging 0.75 A. Compute the actual coil currents before wiring, because a manifold of four 0.9 A solenoids is 3.6 A and must be split across two modules.
Terminals 0 to 3 are outputs 0 to 3 and terminals 4 to 7 are all common; unlike 1734-OB2 there are no dedicated supply terminals on the base. Field power is supplied by the internal power bus from the adapter, a 1734-FPD or a 1734-EP24DC, and the module draws 16 mA of that supply for its output stage.
At 28.8V DC the module dissipates 1.2 W, or 4.1 BTU/hr, roughly half the heat of an eight-point sourcing output. In an enclosure sized by temperature rise this is the reason to prefer two four-point modules over one eight-point module when the point count is six to eight and the loads are light.
1734-OB4 mounts on 1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS. It does not use the TB3 family - those three-row bases are listed for the two-point 1734-OB2 only, so a retrofit that swaps an eight-point module for a four-point one keeps the same base, while a TB3-equipped position must be re-based.
Standard 1734-OB4 is electronically protected but reports faults at module level only. For channels that feed long cables or field devices that can short, the protected 1734-OB2EP family adds per-channel protection diagnostics; the wiring and voltage window stay the same.
Are the outputs isolated from the POINTBus?
The outputs are non-isolated from the field supply and isolated from the system side by 50V (continuous) reinforced insulation. Each module switches the external 24V DC supply that the adapter, a 1734-FPD or a 1734-EP24DC feeds through the base terminals.
What is the maximum current per module?
Each output carries 1.0 A. The module total is 2.0 A for 1734-OB2, while 1734-OB4 and 1734-OB8 allow up to 3.0 A per module as long as no single channel exceeds 1.0 A. Surge capability is 2 A for 10 ms, repeatable every 3 s.
What happens to the outputs when the controller stops?
The module holds the last state it was given until the adapter drops the connection or the field supply is removed; there is no watchdog in the module itself. Configure the adapter's fault action and the output module's program-to-fault state so a communication loss drives the outputs to the safe state your risk assessment requires.
Can a 1734-OB8 drive eight contactor coils directly?
Only if the total coil current stays inside the module limit. Eight coils of 0.15 A come to 1.2 A, which is acceptable on any member of the family, but a group of sealed contactors drawing 0.6 A each would exceed the 1.0 A per channel and the 3.0 A module limit - use interposing relays or split the load across two modules.
Which terminal base fits a 1734-OB8?
1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS. The two-point 1734-OB2 additionally accepts 1734-TB3, 1734-TB3S, 1734-TOP3 and 1734-TOP3S. Terminal base screw torque is 0.8 Nm (7 lb-in).
How much current does the module take from the adapter?
75 mA at 5V DC on POINTBus, plus the external 24V DC supply current for the output stage - 8 mA for 1734-OB2, 16 mA for 1734-OB4 and 32 mA for 1734-OB8, with the load current on top of that.