Product Details:
Payment & Shipping Terms:
|
The 1734-OB2 is the two-point 24V DC sourcing output of the POINT I/O Series C family. Two outputs share one non-isolated group and switch the external 24V DC field supply that arrives through the base terminals, which makes it the natural driver for a pair of small solenoid valves or two interposing relays at a remote station.
Per channel the published rating is 1.0 A with a module total of 2.0 A, an on-state drop of 0.2V DC maximum and 0.5 mA maximum off-state leakage. Both channels switch in 0.1 ms.
| 1734-OB2 | 2 sourcing 24V DC outputs, 2.0 A per module, 32.60 g | IN STOCK |
| 1734-OB4 | 4 sourcing 24V DC outputs, 3.0 A per module, 33.17 g | IN STOCK |
| 1734-OB8 | 8 sourcing 24V DC outputs, 3.0 A per module, 35.4 g | IN STOCK |
Outputs per module |
2 (1 group of 2), non-isolated, sourcing |
Output current rating |
1.0 A per output, 2.0 A max per module |
External DC supply current |
8 mA |
On-state voltage range, min |
10V DC |
On-state voltage range, nominal |
24V DC |
On-state voltage range, max |
28.8V DC |
On-state voltage drop, max |
0.2V DC |
On-state current, min per channel |
1.0 mA |
Off-state leakage, max |
0.5 mA @ 28.8V DC |
Output signal delay, off to on |
0.1 ms |
Output signal delay, on to off |
0.1 ms |
Surge current |
2 A for 10 ms, repeatable every 3 s |
POINTBus current, max |
75 mA @ 5V DC |
Isolation voltage |
50V (continuous), reinforced insulation type |
External DC supply, nominal |
24V DC |
External DC supply range |
10...28.8V DC |
Terminal base screw torque |
0.8 Nm (7 lb-in) |
Dimensions, HxWxD |
56.6 x 12.1 x 77.5 mm |
Wiring category |
2 - on signal ports |
Temperature code |
T4A (North American), T4 (IEC) |
Operating temperature |
-20...55 °C |
Relative humidity |
5...95% non-condensing |
Enclosure |
None (open style) |
Power dissipation, max @ 28.8V DC |
0.8 W @ 28.8V DC |
Thermal dissipation, max @ 28.8V DC |
2.7 BTU/hr @ 28.8V DC |
Weight, approx |
32.60 g |
Module location |
1734-TB, 1734-TBS, 1734-TB3, 1734-TB3S, 1734-TOP, 1734-TOPS, 1734-TOP3, 1734-TOP3S |
Field wiring terminations |
0/2 - Output 0, 1/3 - Output 1, 4/5 - Common, 6/7 - Supply |
Indicators |
2 yellow output status, 2 green/red module and network status |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN018-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
A two-point output costs the same panel width as an eight-point module, so it is chosen for location, not for density: the valves it drives are physically at that end of the machine and the alternative is running two long cables back to a central cabinet. The slice then carries 75 mA of POINTBus current and 0.8 W of dissipation, the lowest of the three sourcing outputs.
Terminals 0 and 2 are output 0, terminals 1 and 3 are output 1, 4 and 5 are common and 6 and 7 are supply. Field power is supplied by the internal power bus, sourced from the adapter, a 1734-FPD or a 1734-EP24DC, so the external supply range must stay within 10...28.8V DC and the supply current draw is 8 mA plus the load.
Off-to-on and on-to-off delays are both 0.1 ms, which is fast enough for pneumatic valve pilot duty and for pulse outputs to a counter. Surge capability is 2 A for 10 ms repeatable every 3 s, so an inrush-heavy lamp or a small DC motor start is tolerable, but a capacitive load that repeats faster than that will trip the module's protection.
Because 0.5 mA of leakage flows even when the channel is off, a very low-current input on the load side may not see a clean off state. The usual answer is an interposing relay for loads below about 5 mA or for circuits that must be isolated from the 24V DC field supply; the module then switches the relay coil instead of the load.
Series C sourcing outputs are electronically protected against short circuit and thermal overload but report it only through the module status LED - there is no per-point diagnostic channel. If you need per-channel fault reporting, the equivalent protected module is 1734-OB2EP, which has its own installation instructions.
Are the outputs isolated from the POINTBus?
The outputs are non-isolated from the field supply and isolated from the system side by 50V (continuous) reinforced insulation. Each module switches the external 24V DC supply that the adapter, a 1734-FPD or a 1734-EP24DC feeds through the base terminals.
What is the maximum current per module?
Each output carries 1.0 A. The module total is 2.0 A for 1734-OB2, while 1734-OB4 and 1734-OB8 allow up to 3.0 A per module as long as no single channel exceeds 1.0 A. Surge capability is 2 A for 10 ms, repeatable every 3 s.
What happens to the outputs when the controller stops?
The module holds the last state it was given until the adapter drops the connection or the field supply is removed; there is no watchdog in the module itself. Configure the adapter's fault action and the output module's program-to-fault state so a communication loss drives the outputs to the safe state your risk assessment requires.
Can a 1734-OB8 drive eight contactor coils directly?
Only if the total coil current stays inside the module limit. Eight coils of 0.15 A come to 1.2 A, which is acceptable on any member of the family, but a group of sealed contactors drawing 0.6 A each would exceed the 1.0 A per channel and the 3.0 A module limit - use interposing relays or split the load across two modules.
Which terminal base fits a 1734-OB8?
1734-TB, 1734-TBS, 1734-TOP or 1734-TOPS. The two-point 1734-OB2 additionally accepts 1734-TB3, 1734-TB3S, 1734-TOP3 and 1734-TOP3S. Terminal base screw torque is 0.8 Nm (7 lb-in).
How much current does the module take from the adapter?
75 mA at 5V DC on POINTBus, plus the external 24V DC supply current for the output stage - 8 mA for 1734-OB2, 16 mA for 1734-OB4 and 32 mA for 1734-OB8, with the load current on top of that.