Product Details:
Payment & Shipping Terms:
|
The 1734-APB puts a POINT I/O assembly on PROFIBUS DP: 63 modules on a single DP node, a 9-pin RS-485 port, and address selection from 01 to 99 on the front thumbwheel.
It is the adapter for a Siemens or third-party DP master - the GSD file 173404EF.GSD is what makes the assembly appear as a slave with the module order the panel was built with.
| 1734-AENT | EtherNet/IP adapter, 10/100 Mbit, 63 modules, 1.0 A POINTBus | IN STOCK |
| 1734-ADN | DeviceNet adapter, 125/250/500 kbit, 63 modules | IN STOCK |
| 1734-ADNX | DeviceNet adapter with Subnet scanner, node 0 on the subnet | IN STOCK |
| 1734-ACNR | ControlNet adapter, redundant coax A/B, node 01...99 | IN STOCK |
| 1734-APB | PROFIBUS DP adapter, 63 modules on one DP node | IN STOCK |
Network |
PROFIBUS DP, RS-485, 9-pin sub-D connector |
GSD file |
173404EF.GSD, supplied with the adapter |
Baud rate |
Selected in the PROFIBUS master's bus parameters |
Node address |
2-position thumbwheel, 01...99 |
Expansion I/O capacity |
63 modules on one PROFIBUS DP node, with expansion power supplies as needed |
POINTBus output current, max |
1000 mA @ 5V DC (4.75...5.25V DC) |
Input voltage rating, nom |
24V DC, range 10...28.8V DC |
Field side power requirement |
400 mA @ 24V DC (+20% = 28.8V DC) |
Inrush current |
6 A for 10 ms |
Power consumption |
8.0 W @ 24V DC |
Power dissipation, max |
2.8 W @ 28.8V DC |
Input overvoltage protection |
Reverse polarity protected |
Supply interruption |
Output stays within specification for a 10 ms drop at 10V with maximum load |
Dimensions, HxWxD |
79.8 x 56.1 x 133.1 mm |
Wire size |
0.25...2.5 mm2 (22...14 AWG) copper rated 75 °C or greater |
Enclosure |
None (open-style) |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN014 (module specifications) and 1734-UM005 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
PROFIBUS addresses a whole assembly as one slave, so 63 POINT I/O modules cost one node number on a segment that may only allow 32 devices per repeater section. That is the reason the APB exists: a 63-module assembly on DeviceNet would be one node too, but on DP it also saves the gateway that a third-party DP-to-DeviceNet bridge would need.
The supplied GSD, 173404EF.GSD, is imported into the master's configuration tool and the POINT I/O modules are added in physical order. The adapter reports the module list it finds to the master; a mismatch between the configured order and the built order shows up as a configuration fault rather than as bad data, which makes commissioning deterministic but unforgiving of a module inserted in the wrong slot.
The adapter supplies 1000 mA at 5V DC, which in the published table is 14 modules at 75 mA. Beyond that, 1734-EP24DC expansion power supplies extend the backplane current, and the module count can rise to 63 as long as the total 5V current is covered. Reading the 63 as a capacity without doing the current arithmetic is the usual mistake.
RS-485 on a 9-pin sub-D: pin 3 is the positive data line, pin 8 the negative, pin 6 carries 5V bus for a terminating resistor and pin 4 is request-to-send; pins 1 and 2 are not connected. Termination belongs in the connector, at both physical ends of the segment.
8.0 W consumption at 24V, 2.8 W dissipation at 28.8V, 400 mA taken from the 24V field supply for the adapter, and 6 A inrush for 10 ms. The inrush matters when several adapters share one 24V supply: ten assemblies starting together look like a 60 A load for 10 ms, which trips supplies that are fine on steady-state current alone.
The APB keeps the I/O hardware Rockwell and the network PROFIBUS, which is common when the controller is a Siemens S7 and the existing spares are POINT I/O. The trade-off is diagnostics: DP masters see the adapter as one slave, so a single failed module is reported through the adapter's status rather than as its own DP device.
How many POINT I/O modules can one 1734-APB handle?
63 modules on a single PROFIBUS DP node, with 1734-EP24DC expansion power supplies where the 1000 mA POINTBus current is not enough - 14 modules at 75 mA is the published figure without expansion.
Which GSD file does 1734-APB use?
173404EF.GSD, supplied with the adapter and imported into the PROFIBUS master's configuration tool.
How is the PROFIBUS address set?
With the 2-position thumbwheel on the front, valid from 01 to 99.
What baud rate does the adapter run?
The baud rate is set in the master's bus parameters; the adapter follows the segment it is connected to.
What is the inrush current?
6 A for 10 ms, with 400 mA steady field-side draw at 24V DC.