Allen Bradley PLC 1734-APB / 1734APB supplier Allen Bradley PLC 1734-APB / 1734APB supplier Allen Bradley PLC 1734-APB / 1734APB supplier Allen Bradley PLC 1734-APB / 1734APB supplier Allen Bradley PLC 1734-APB / 1734APB supplier Allen Bradley PLC 1734-APB / 1734APB supplier Allen Bradley PLC 1734-APB / 1734APB supplier Allen Bradley PLC 1734-APB / 1734APB supplier

Large Image :  Allen Bradley PLC 1734-APB / 1734APB

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1734-APB / 1734APB

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $235.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 25 PCS
Detailed Product Description

1734-APB technical data PDF download POINT I/O 1734-APB / 1734APB PROFIBUS DP Adapter

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: POINT I/O Communication Adapter

The 1734-APB puts a POINT I/O assembly on PROFIBUS DP: 63 modules on a single DP node, a 9-pin RS-485 port, and address selection from 01 to 99 on the front thumbwheel.

It is the adapter for a Siemens or third-party DP master - the GSD file 173404EF.GSD is what makes the assembly appear as a slave with the module order the panel was built with.

1734-AENT EtherNet/IP adapter, 10/100 Mbit, 63 modules, 1.0 A POINTBus IN STOCK
1734-ADN DeviceNet adapter, 125/250/500 kbit, 63 modules IN STOCK
1734-ADNX DeviceNet adapter with Subnet scanner, node 0 on the subnet IN STOCK
1734-ACNR ControlNet adapter, redundant coax A/B, node 01...99 IN STOCK
1734-APB PROFIBUS DP adapter, 63 modules on one DP node IN STOCK

Product Specifications 1734-APB (PDF)
 Network
 PROFIBUS DP, RS-485, 9-pin sub-D connector
 GSD file
 173404EF.GSD, supplied with the adapter
 Baud rate
 Selected in the PROFIBUS master's bus parameters
 Node address
 2-position thumbwheel, 01...99
 Expansion I/O capacity
 63 modules on one PROFIBUS DP node, with expansion power supplies as needed
 POINTBus output current, max
 1000 mA @ 5V DC (4.75...5.25V DC)
 Input voltage rating, nom
 24V DC, range 10...28.8V DC
 Field side power requirement
 400 mA @ 24V DC (+20% = 28.8V DC)
 Inrush current
 6 A for 10 ms
 Power consumption
 8.0 W @ 24V DC
 Power dissipation, max
 2.8 W @ 28.8V DC
 Input overvoltage protection
 Reverse polarity protected
 Supply interruption
 Output stays within specification for a 10 ms drop at 10V with maximum load
 Dimensions, HxWxD
 79.8 x 56.1 x 133.1 mm
 Wire size
 0.25...2.5 mm2 (22...14 AWG) copper rated 75 °C or greater
 Enclosure
 None (open-style)

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN014 (module specifications) and 1734-UM005 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1734-APB original product photograph, wide view 1734-APB original product photograph, label view 1734-APB original product photograph, second unit

One DP node, 63 modules

PROFIBUS addresses a whole assembly as one slave, so 63 POINT I/O modules cost one node number on a segment that may only allow 32 devices per repeater section. That is the reason the APB exists: a 63-module assembly on DeviceNet would be one node too, but on DP it also saves the gateway that a third-party DP-to-DeviceNet bridge would need.

GSD file and module order

The supplied GSD, 173404EF.GSD, is imported into the master's configuration tool and the POINT I/O modules are added in physical order. The adapter reports the module list it finds to the master; a mismatch between the configured order and the built order shows up as a configuration fault rather than as bad data, which makes commissioning deterministic but unforgiving of a module inserted in the wrong slot.

1000 mA POINTBus, 63 modules with expansion supplies

The adapter supplies 1000 mA at 5V DC, which in the published table is 14 modules at 75 mA. Beyond that, 1734-EP24DC expansion power supplies extend the backplane current, and the module count can rise to 63 as long as the total 5V current is covered. Reading the 63 as a capacity without doing the current arithmetic is the usual mistake.

Wiring the DP port

RS-485 on a 9-pin sub-D: pin 3 is the positive data line, pin 8 the negative, pin 6 carries 5V bus for a terminating resistor and pin 4 is request-to-send; pins 1 and 2 are not connected. Termination belongs in the connector, at both physical ends of the segment.

Power and heat

8.0 W consumption at 24V, 2.8 W dissipation at 28.8V, 400 mA taken from the 24V field supply for the adapter, and 6 A inrush for 10 ms. The inrush matters when several adapters share one 24V supply: ten assemblies starting together look like a 60 A load for 10 ms, which trips supplies that are fine on steady-state current alone.

Where it fits in a mixed-vendor panel

The APB keeps the I/O hardware Rockwell and the network PROFIBUS, which is common when the controller is a Siemens S7 and the existing spares are POINT I/O. The trade-off is diagnostics: DP masters see the adapter as one slave, so a single failed module is reported through the adapter's status rather than as its own DP device.

FAQ — 1734-APB

How many POINT I/O modules can one 1734-APB handle?

63 modules on a single PROFIBUS DP node, with 1734-EP24DC expansion power supplies where the 1000 mA POINTBus current is not enough - 14 modules at 75 mA is the published figure without expansion.

Which GSD file does 1734-APB use?

173404EF.GSD, supplied with the adapter and imported into the PROFIBUS master's configuration tool.

How is the PROFIBUS address set?

With the 2-position thumbwheel on the front, valid from 01 to 99.

What baud rate does the adapter run?

The baud rate is set in the master's bus parameters; the adapter follows the segment it is connected to.

What is the inrush current?

6 A for 10 ms, with 400 mA steady field-side draw at 24V DC.


Data sources. Technical values on this page come from Rockwell publication 1734-IN014 (POINT I/O PROFIBUS Adapter 1734-APB), 1734-UM005 (POINT I/O PROFIBUS Adapter Module User Manual) and 1734-SG001F-EN-P (POINT I/O selection guide, power tables). Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.

Contact Details
PLC-VIP SHOP

Contact Person: Miss. linda

Tel: 00-852-65626925

Fax: 00-852-90164956

Send your inquiry directly to us (0 / 3000)