The 1734-ADN is the DeviceNet head of a POINT I/O assembly: one DeviceNet node address, 63 modules and 504 I/O points behind it, at 125, 250 or 500 kbit/s with the corresponding 500, 250 or 100 m segment lengths.
DeviceNet power comes in at 11...25V DC drawing 30 mA, and the adapter's own isolation test voltage is 800V DC for 60 s - an order of magnitude below the mains-capable modules, which matters when the assembly sits next to a drive cabinet.
| 1734-AENT | EtherNet/IP adapter, 10/100 Mbit, 63 modules, 1.0 A POINTBus | IN STOCK |
| 1734-ADN | DeviceNet adapter, 125/250/500 kbit, 63 modules | IN STOCK |
| 1734-ADNX | DeviceNet adapter with Subnet scanner, node 0 on the subnet | IN STOCK |
| 1734-ACNR | ControlNet adapter, redundant coax A/B, node 01...99 | IN STOCK |
| 1734-APB | PROFIBUS DP adapter, 63 modules on one DP node | IN STOCK |
DeviceNet communication rate |
125 kbit/s (500 m max), 250 kbit/s (250 m max), 500 kbit/s (100 m max) |
Node address |
00...63 on the thumbwheel, 64...99 selects the stored address |
DeviceNet current |
30 mA |
Module location |
Starter module, left side of the POINT I/O system |
Module capacity |
63 powered modules, up to 504 I/O points |
POINTBus current |
1000 mA @ 5V DC (4.75...5.25V) |
Field power bus |
24V DC nominal, 10...28.8V DC, 10 A max |
24V current load for the adapter |
400 mA |
Input byte capacity |
248 bytes |
Output byte capacity |
248 bytes |
Isolation voltage |
50V continuous, tested 800V DC for 60 s |
Power consumption |
8.1 W @ 28.8V DC |
Power dissipation, max |
2.8 W @ 28.8V DC |
Thermal dissipation, max |
9.5 BTU/hr @ 28.8V DC |
Terminal base screw torque |
0.5...0.6 Nm (5...7 lb-in) |
Wire size |
0.25...2.5 mm2 (22...14 AWG) copper rated 75 °C or greater, 1.2 mm insulation max |
Temperature code |
T4A (North American), T4 (UKEX/ATEX and IECEx) |
Dimensions, HxWxD |
79.8 x 56.3 x 133.1 mm |
Weight, approx |
260 g |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN026 (module specifications) and 1734-UM002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
125 kbit/s allows 500 m, 250 kbit/s 250 m and 500 kbit/s 100 m. Going faster to shorten the poll cycle halves or fifths the allowable trunk, so a long conveyor line usually runs at 125 or 250 kbit/s and accepts the scan penalty rather than adding a repeater.
The two-position thumbwheel sets 00...63 directly. Setting 64...99 tells the adapter to use the address stored in nonvolatile memory instead, which is how a replacement adapter can be dropped in with the right node number already configured by RSNetWorx.
63 modules and 504 points are the published maxima, but POINTBus current is 1000 mA at 5V DC. The adapter does not add a second supply, so a stack of analog modules hits the current ceiling before the module count; 1734-EP24DC extension power supplies are how a full rack gets built.
50V continuous, tested at 800V DC for 60 s - a field-side rating for a 24V network, not a mains rating. Field power is 10...28.8V DC at up to 10 A, the adapter consumes 8.1 W and dissipates 2.8 W, and the temperature code is T4A in North America and T4 under UKEX/ATEX and IECEx.
The 1734-ADN supports the Series A/B generation of digital, analog and specialty modules listed in its publication, which is why it remains the right head for an existing DeviceNet panel that predates Series C. Replacing it with 1734-AENT would force a module-by-module series upgrade.
248 input bytes and 248 output bytes are the adapter's ceiling, which at 4 bytes per digital module covers the full 63-module assembly with room for analog data. The limit becomes real when specialty modules are present: a counter or SSI module consumes far more than four bytes, and the scan connection count, not the byte count, is usually what runs out first on a DeviceNet master.
What is the maximum number of modules on 1734-ADN?
63 powered modules and up to 504 I/O points, within a POINTBus current budget of 1000 mA at 5V DC.
How do I set the DeviceNet node address?
With the two-position thumbwheel from 00 to 63. A setting between 64 and 99 tells the adapter to use the address stored in nonvolatile memory, set through RSNetWorx for DeviceNet.
What cable lengths are allowed?
500 m at 125 kbit/s, 250 m at 250 kbit/s and 100 m at 500 kbit/s, using Allen-Bradley 1485C cable.
What isolation does the adapter provide?
50V continuous, tested at 800V DC for 60 s - a 24V field-side rating, not a mains barrier.
Can 1734-ADN be replaced by 1734-AENT?
Only with a module upgrade. 1734-AENT requires Series C modules, while 1734-ADN is published with the earlier Series A/B module list.
1734-ADN is a head-of-slice unit in the POINT I/O system. Head units sit to the left of the I/O modules and either own the network connection, supply the POINTBus, or distribute field power; the modules to their right exist only as a slice hanging off that head unit.
| Attribute | Value |
| Catalog number | 1734-ADN |
| Role | DeviceNet network adapter |
| Width | 56.1 mm (2.21 in.) for the network adapters, 25.4 mm (1.00 in.) for expansion supplies, distributors and the compact head unit |
| Mounting | DIN rail, at the head of the slice |
| System clearance | 25.4 mm on all sides; 50.8 mm above when safety modules are present |
| Ordering note | Terminal bases for the I/O modules are separate line items |
POINTBus current is the budget that decides how many modules a slice can carry: most digital and analog modules draw 75 mA, the 1734-OW2 draws 80 mA, and 1734-IB4D draws 50 mA. The usable current of the adapter, plus that of any expansion power supply, divided by the per-module draw gives the maximum slice length, and that is a planning calculation rather than a rule of thumb.
Mechanically the system is width-driven: adapters occupy 56.1 mm, expansion power supplies and field power distributors 25.4 mm each, standard I/O modules 12.1 mm each, and safety I/O modules 24.1 mm each. Total panel width is the sum of those, and a layout that assumes a uniform module width is wrong on both the adapter and the safety side.
Clearance is a specification, not a courtesy: 25.4 mm on all sides of the system is the minimum, and a system with POINT I/O safety modules needs 50.8 mm above the assembly. Cabinets that pass at 25 mm on a digital-only slice fail once a safety module is added to the same rail.
The width difference between 56.1 mm and 25.4 mm is the difference between an adapter that carries a network port and a unit that only carries power. Both can head a slice, and both feed the POINTBus, but only the adapter appears on the network as a node; the expansion supply and the field power distributor exist to extend the slice inside the cabinet.
Ordering discipline for this family is the practical point: the module alone does not make a working channel, because the terminal base assembly is a separate catalog number, the RTB is a separate replacement part, and the head unit sets how many modules the slice can carry.
Related models, options and spare parts for this range are listed in the Allen-Bradley POINT I/O 1734 modules category.