Allen Bradley PLC 1734-ADN / 1734ADN supplier Allen Bradley PLC 1734-ADN / 1734ADN supplier Allen Bradley PLC 1734-ADN / 1734ADN supplier Allen Bradley PLC 1734-ADN / 1734ADN supplier Allen Bradley PLC 1734-ADN / 1734ADN supplier Allen Bradley PLC 1734-ADN / 1734ADN supplier Allen Bradley PLC 1734-ADN / 1734ADN supplier Allen Bradley PLC 1734-ADN / 1734ADN supplier

Large Image :  Allen Bradley PLC 1734-ADN / 1734ADN

Product Details:

Place of Origin: Made in SINGAPORE
Brand Name: PLC Module
Certification: All goods we supply are 100% original factory sealed with 1 year warranty!
Model Number: Allen Bradley PLC 1734-ADN / 1734ADN

Payment & Shipping Terms:

Minimum Order Quantity: 1 /PCS
Price: $159.00 (USD/PCS)
Packaging Details: 100% original new
Delivery Time: IN STOCK; 4-6 Weeks for ordering
Payment Terms: Paypal, T/T and Western Union.
Supply Ability: 25 PCS
Detailed Product Description

1734-ADN technical data PDF download POINT I/O 1734-ADN / 1734ADN DeviceNet Adapter

Category: PLCs, Power Supplies & I/Os
Manufacturer: Rockwell
Group: POINT I/O Communication Adapter

The 1734-ADN is the DeviceNet head of a POINT I/O assembly: one DeviceNet node address, 63 modules and 504 I/O points behind it, at 125, 250 or 500 kbit/s with the corresponding 500, 250 or 100 m segment lengths.

DeviceNet power comes in at 11...25V DC drawing 30 mA, and the adapter's own isolation test voltage is 800V DC for 60 s - an order of magnitude below the mains-capable modules, which matters when the assembly sits next to a drive cabinet.

1734-AENT EtherNet/IP adapter, 10/100 Mbit, 63 modules, 1.0 A POINTBus IN STOCK
1734-ADN DeviceNet adapter, 125/250/500 kbit, 63 modules IN STOCK
1734-ADNX DeviceNet adapter with Subnet scanner, node 0 on the subnet IN STOCK
1734-ACNR ControlNet adapter, redundant coax A/B, node 01...99 IN STOCK
1734-APB PROFIBUS DP adapter, 63 modules on one DP node IN STOCK

Product Specifications 1734-ADN (PDF)
 DeviceNet communication rate
 125 kbit/s (500 m max), 250 kbit/s (250 m max), 500 kbit/s (100 m max)
 Node address
 00...63 on the thumbwheel, 64...99 selects the stored address
 DeviceNet current
 30 mA
 Module location
 Starter module, left side of the POINT I/O system
 Module capacity
 63 powered modules, up to 504 I/O points
 POINTBus current
 1000 mA @ 5V DC (4.75...5.25V)
 Field power bus
 24V DC nominal, 10...28.8V DC, 10 A max
 24V current load for the adapter
 400 mA
 Input byte capacity
 248 bytes
 Output byte capacity
 248 bytes
 Isolation voltage
 50V continuous, tested 800V DC for 60 s
 Power consumption
 8.1 W @ 28.8V DC
 Power dissipation, max
 2.8 W @ 28.8V DC
 Thermal dissipation, max
 9.5 BTU/hr @ 28.8V DC
 Terminal base screw torque
 0.5...0.6 Nm (5...7 lb-in)
 Wire size
 0.25...2.5 mm2 (22...14 AWG) copper rated 75 °C or greater, 1.2 mm insulation max
 Temperature code
 T4A (North American), T4 (UKEX/ATEX and IECEx)
 Dimensions, HxWxD
 79.8 x 56.3 x 133.1 mm
 Weight, approx
 260 g

Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN026 (module specifications) and 1734-UM002 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.

1734-ADN original product photograph, wide view 1734-ADN original product photograph, label view 1734-ADN original product photograph, second unit

Baud rate sets the cable length

125 kbit/s allows 500 m, 250 kbit/s 250 m and 500 kbit/s 100 m. Going faster to shorten the poll cycle halves or fifths the allowable trunk, so a long conveyor line usually runs at 125 or 250 kbit/s and accepts the scan penalty rather than adding a repeater.

Node addressing, including the 64...99 trick

The two-position thumbwheel sets 00...63 directly. Setting 64...99 tells the adapter to use the address stored in nonvolatile memory instead, which is how a replacement adapter can be dropped in with the right node number already configured by RSNetWorx.

The 1.0 A POINTBus budget and 63 modules

63 modules and 504 points are the published maxima, but POINTBus current is 1000 mA at 5V DC. The adapter does not add a second supply, so a stack of analog modules hits the current ceiling before the module count; 1734-EP24DC extension power supplies are how a full rack gets built.

Isolation and environment

50V continuous, tested at 800V DC for 60 s - a field-side rating for a 24V network, not a mains rating. Field power is 10...28.8V DC at up to 10 A, the adapter consumes 8.1 W and dissipates 2.8 W, and the temperature code is T4A in North America and T4 under UKEX/ATEX and IECEx.

Series compatibility

The 1734-ADN supports the Series A/B generation of digital, analog and specialty modules listed in its publication, which is why it remains the right head for an existing DeviceNet panel that predates Series C. Replacing it with 1734-AENT would force a module-by-module series upgrade.

What the 248-byte image buys

248 input bytes and 248 output bytes are the adapter's ceiling, which at 4 bytes per digital module covers the full 63-module assembly with room for analog data. The limit becomes real when specialty modules are present: a counter or SSI module consumes far more than four bytes, and the scan connection count, not the byte count, is usually what runs out first on a DeviceNet master.

FAQ — 1734-ADN

What is the maximum number of modules on 1734-ADN?

63 powered modules and up to 504 I/O points, within a POINTBus current budget of 1000 mA at 5V DC.

How do I set the DeviceNet node address?

With the two-position thumbwheel from 00 to 63. A setting between 64 and 99 tells the adapter to use the address stored in nonvolatile memory, set through RSNetWorx for DeviceNet.

What cable lengths are allowed?

500 m at 125 kbit/s, 250 m at 250 kbit/s and 100 m at 500 kbit/s, using Allen-Bradley 1485C cable.

What isolation does the adapter provide?

50V continuous, tested at 800V DC for 60 s - a 24V field-side rating, not a mains barrier.

Can 1734-ADN be replaced by 1734-AENT?

Only with a module upgrade. 1734-AENT requires Series C modules, while 1734-ADN is published with the earlier Series A/B module list.


Data sources. Technical values on this page come from Rockwell publication 1734-IN026 (POINT I/O DeviceNet Adapter 1734-ADN) and 1734-UM002 (POINT I/O DeviceNet Adapter 1734-ADN, 1734-ADNX User Manual). Any attribute the publication does not print is marked Not published rather than taken from a distributor page. Catalog number, packaging and stock status are the stock record of this listing.