The 1734-OA2 switches two 120/220V AC loads from a POINT I/O slice. Each channel is a non-isolated triac output rated 10 mA to 750 mA, and the module carries 1.5 A total at 50 °C, derating to 1.3 A at 55 °C.
The AC side is isolated from the POINTBus by 240V reinforced insulation tested at 3250V DC for 60 s, so mains loads and 24V DC I/O can share one adapter without extra hardware.
| 1734-OA2 | 2 triac AC outputs, 74...264V AC, 0.75 A per channel, 1.5 A per module | IN STOCK |
| 1734-OA4 | 4 triac AC outputs, 74...264V AC, 0.75 A per channel, 2.0 A per module | IN STOCK |
Outputs per module |
2, non-isolated, sourcing |
Output current rating |
1.5 A (2 channels at 0.75 A each) |
Current versus temperature |
1.5 A per module at 50 deg C, derate 13% to 1.3 A at 55 deg C |
On-state voltage, min |
74V AC |
On-state voltage, nominal |
120/220V AC |
On-state voltage, max |
264V AC |
On-state voltage drop, max |
1.0V @ 0.75 A |
On-state current, min per channel |
10 mA |
On-state current, max per channel |
750 mA |
Off-state leakage, max |
2.7 mA @ 264V AC |
Surge current |
16 A for 100 ms, repeatable every 10 s |
Turn-off time |
1/2 cycle |
POINTBus current, max |
75 mA @ 5V DC |
Isolation voltage |
240V (continuous), Reinforced Insulation, tested 3250V DC for 60 s, field side to system |
External AC supply |
120/220V AC at 60 Hz |
Terminal base screw torque |
0.8 Nm (7 lb-in) |
Dimensions, HxWxD |
56.0 x 12.0 x 75.5 mm |
Wiring category |
1 - on signal ports |
Temperature code |
T4 (North American) |
Operating temperature |
-20...55 °C |
Power dissipation, max |
2 W @ 264V AC |
Thermal dissipation, max |
6.8 BTU/hr @ 264V AC |
Weight, approx |
30.9 g |
Field wiring terminations |
0 - Channel 0, 1 - Channel 1, 2/3 - No connection, 4/5 - L2/N, 6/7 - L1 |
Indicators |
2 output status, module and network status |
Attribute values above are reproduced from the manufacturer's product data. For the authoritative technical record see Rockwell publications 1734-IN009-EN-E (module specifications) and 1734-UM001 (installation instructions). Certification details, with certificate and file numbers, are listed in the FAQ below.
Terminals 0 and 1 are the two channel connections, 2 and 3 are no connection, 4 and 5 are L2/N (the 120/220V AC return) and 6 and 7 are L1 (the AC supply). Field power is supplied from the internal power bus, which is why both L1 and L2/N appear on the base rather than being taken from a separate terminal strip.
The 1.5 A headline applies at or below 50 °C. Above that the module derates linearly by 13% to 1.3 A at 55 °C. In a sealed enclosure at the top of the ambient range, two channels at 0.75 A already sit exactly at the limit, so any margin has to come from reducing load current or moving heat out of the cabinet.
2.7 mA of leakage at 264V AC is enough to keep a neon indicator or a very small relay coil partly energised. That is why the minimum on-state current is 10 mA per channel - below that the triac may not latch, and above the leakage threshold a load may not drop out. Small indicators should be driven through a relay module instead.
2 W at 264V AC, 6.8 BTU/hr, on a slice 12 mm wide. The heat is produced in the output stage and scales with load current, so the cabinet calculation has to use the actual switched current, not the quiescent figure.
If the load is DC, if it needs a dry contact for another panel, or if the circuit must be isolated contact-to-contact, 1734-OW2 provides two Form A isolated relay contacts in the same footprint. The triac module is the cheaper choice only when the load really is a small AC device.
What load types can a 1734-OA2 switch?
The triac output is for AC loads between 10 mA and 750 mA per channel at 74 to 264V AC. Resistive and inductive AC loads such as solenoids, contactors and lamps work; the published on-state drop is 1.0V at 0.75 A and off-state leakage is 2.7 mA at 264V AC.
Why does the module have a derating curve?
Because the triac dissipates heat that depends on load current and ambient. 1734-OA2 carries 1.5 A total up to 50 deg C and derates linearly by 13% to 1.3 A at 55 deg C; 1734-OA4 carries 2.0 A up to 45 deg C and derates by 30% to 1.4 A at 55 deg C. A cabinet at 55 deg C cannot use the headline current rating.
Can these modules switch DC loads?
No. The output stage is a triac for AC only, with a 1/2 cycle turn-off. For DC loads use the sourcing 1734-OB family or the sinking 1734-OV family, or a 1734-OW relay module if isolation between the load circuit and the module is required.
What is the surge capability?
16 A for 100 ms, repeatable every 10 s, which covers the inrush of small AC solenoids and incandescent lamps. It does not cover a motor start every few seconds.
What isolation does the AC output provide?
240V continuous reinforced insulation, tested at 3250V DC for 60 s from field side to system - the highest test voltage in the 1734 digital family, which is why mains circuits can sit on the same slice as 24V DC I/O.