Product Details:
Payment & Shipping Terms:
|
| 1756-EN2F | CLX HI CAP EIP MOD - FBR | IN STOCK |
| 1756-EN2T | ControlLogix Hi Capacity ENET/IP | IN STOCK |
| 1756-EN2TR | 2-PORT CLX HI-CAP ENET/IP MODULE - TP | IN STOCK |
| 1756-EN2TRXT | CLX ENET/IP Module - 2TP -X Envt | IN STOCK |
| 1756-EN2TSC | EtherNet/IP Hi Prof Sngl Port VPN Bridge | IN STOCK |
| 1756-EN2TXT | CLX ENET/IP MODULE - TP, X-ENVT | IN STOCK |
| 1756-EN3TR | ControlLogix Ethernet Motion Module | IN STOCK |
| 1756-ENBT | ControlLogix Communication Module | IN STOCK |
| 1756-EWEB | ControlLogix Web Server Module | IN STOCK |
| 1756-EXT | ControlLogix Backplane Extender | IN STOCK |
| 1756-HIST1G | Historian ME 1 Gig in ControlLogix Rack | IN STOCK |
| 1756-HIST2G | Historian ME 2 Gig in ControlLogix Rack | IN STOCK |
| 1756-HSC | ControlLogix High-Speed Counter Module | IN STOCK |
| 1756-HYD02 | ControlLogix Analog Combination Module | IN STOCK |
The 1756-ENBT is the first-generation ControlLogix EtherNet/IP bridge: one copper RJ45 port at 10/100 Mbps, 128 CIP (Logix) connections, 64 TCP/IP connections, and 64+64 unconnected messages across the backplane and the Ethernet side.
Its role in a chassis is threefold - control I/O and drives over EtherNet/IP, act as an adapter for distributed I/O on remote EtherNet/IP links, and route messages to devices on other networks. On a running ControlLogix line it is usually the module that carries both the I/O traffic and the programming path, which is why the connection count matters: 128 CIP connections is the budget that covers an I/O tree plus HMI plus messaging, and a large machine can genuinely exhaust it.
Lifecycle status is now part of the specification: the 1756-ENBT was discontinued on 31 December 2021 with the 1756-EN2T as the functional replacement. That makes this a spare-part and migration item rather than a new-build choice - the electrical and mechanical data below is what a like-for-like replacement has to match.
|
Application
|
EtherNet/IP bridge; discontinued 31 December 2021, functional replacement 1756-EN2T |
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1756-ENBT
|
|
Communication
|
EtherNet/IP; 128 CIP (Logix) connections, 64 TCP/IP connections, 64+64 unconnected messages |
|
Enclosure
|
None (open-style)
|
|
Display
|
Digital
|
|
Interface
|
1 Ethernet RJ45 Category 5, 10/100 Mbps |
|
Number Of Channels
|
1
|
|
Mounting
|
Chassis
|
|
Sub Brand
|
ControlLogix
|
|
Standard
|
CE,CSA,CUL,GOST,KC,MARINE,NRTL,RCM,UL
|
|
UNSPSC
|
32151705
|
|
Type
|
ControlLogix EtherNet/IP bridge module, 700 mA at 5.1V DC, 3.7 W dissipation |
Power: 700 mA at 5.1 V dc from the chassis backplane plus 3 mA at 24 V dc, dissipating 3.7 W (12.6 BTU/hr). In a 1756 chassis that already carries a controller and several I/O modules, 700 mA is a real number against the power supply budget - the 1756-PA72/PA75/PB72/PB75/PC75/PH75 family, or the redundant PA75R/PB75R/PSCA2 pair.
Isolation: 30 V continuous, basic insulation type, between the Ethernet network and the backplane, type tested at 707 V dc for 60 s. There is no isolation between individual Ethernet ports because there is only one port on this module - the dual-port embedded-switch capability arrived with the EN2TR generation.
Mechanics and environment: one slot width, chassis-based in any slot of a 1756-A4, -A7, -A10, -A13 or -A17 chassis, open-style enclosure, North American temperature code T4. Ethernet cabling is 802.3 compliant shielded or unshielded twisted pair on Category 5.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
Three differences decide whether an EN2T drops in cleanly: connection capacity (128 CIP on the ENBT versus 256 on the EN2T), current draw (700 mA versus 1 A at 5.1 V), and firmware - an ENBT at version 16.03 or later is the usual baseline for modern Logix firmware, and older revisions can stop a project download.
The practical check before ordering a replacement is the connection count actually in use. If the I/O tree, the HMI and the messaging already sit near 128 CIP connections, an EN2T is not just a spare - it is the fix for the fault that made the module look bad in the first place.
Topology consequence: one Ethernet port means no embedded switch and no device-level ring on this module. A ring built around ENBTs has to be created with external switches and a ring supervisor elsewhere; the dual-port EN2TR is what allows a ring to be closed at the module itself. Where the existing architecture uses external switches, an ENBT-to-EN2T swap does not change that, and the network design stays as it was.
One more migration detail: the ENBT and EN2T share the same chassis slot, the same 1756-A series racks and the same power supply family, so a swap needs no mechanical change. What does change is the firmware revision the project expects and the number of connections a single module can host - on a large rack that is the reason a plant replaces an ENBT with an EN2T before the ENBT fails, rather than after.
Specifications on this page are from the ControlLogix Communication Modules Specifications, publication 1756-TD003, and the module's published lifecycle notice.
Same-family catalog numbers: 1756-EN2F, 1756-EN2T, 1756-EN2TR, 1756-EN2TRXT. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1756 family.
ControlLogix chassis, power supplies and communication modules are listed on our category page. Quotes: sales@plc-vip.com.