Product Details:
Payment & Shipping Terms:
|
| 1756-A10 | ControlLogix 10 Slots Chassis | IN STOCK |
| 1756-A13 | 13 SLOT CONTROLLOGIX CHASSIS | IN STOCK |
| 1756-A17 | ControlLogix 17 Slots Chassis | IN STOCK |
| 1756-A4 | ControlLogix 4 Slots Chassis | IN STOCK |
| 1756-A4LXT | ControlLogix XT 4 Slots Chassis | IN STOCK |
| 1756-A5XT | ControlLogix XT 5 Slots Chassis | IN STOCK |
| 1756-A7 | ControlLogix 7 Slots Chassis | IN STOCK |
| 1756-A7LXT | ControlLogix XT 7 Slots Chassis | IN STOCK |
| 1756-A7XT | 1756 Extended Temp 7-Slot Chassis | IN STOCK |
| 1756-BA1 | LOGIX5000 BATTERY ASSY | IN STOCK |
| 1756-BA2 | LOGIX5000 BATT ASSY-1756-L6X SER B ONLY | IN STOCK |
| 1756-BATA | REPLACEMENT BATTERY ASSY FOR 1756-BATM | IN STOCK |
| 1756-BATM | CONTROLLOGIX BATTERY MODULE | IN STOCK |
The 1756-BA1 is the battery assembly for Series A ControlLogix 1756-L6x controllers - a lithium cell on a flying lead with a plug that seats in the controller's battery compartment. Its job is single and unsentimental: hold the controller's date/time and retain memory contents while the rack is powered down.
Compatibility is the whole specification here. Series A controllers take 1756-BA1; Series B 1756-L6x controllers take 1756-BA2, and the two are not substitutes - different assembly, different plug, and a controller that expects one will not accept the other. The Australian mining certification requirement is the sharpest expression of this: only a Series A controller with a 1756-BA1 battery is covered.
The part is at end of life: Rockwell Automation has announced discontinuation as of 31 December 2027 with no planned replacement. Buying one now means sustaining an installed Series A rack, and the sensible question is not which battery but how long the rack will stay in service after that date.
|
Amperage Rating
|
Lithium cell, 0.59 g lithium content (Series A 1756-L6x controllers only) |
|
Application
|
Battery backup for Series A ControlLogix 1756-L6x controllers; not interchangeable with 1756-BA2 (Series B) |
|
Brand Name
|
PLC Module
|
|
Cat Num
|
1756-BA1
|
|
Functions
|
Battery Backup
|
|
Material
|
Lithium
|
|
Parent Figure-Model Number
|
For Use With ControlLogix5560 Series A Controllers
|
|
Standard
|
GOST,KC,MARINE
|
|
Sub Brand
|
ControlLogix
|
|
Temperature Rating
|
0...60 C (32...140 F)
|
|
Type
|
Battery assembly, end of life 31 December 2027, no planned Rockwell Automation replacement |
|
UNSPSC
|
32151703
|
|
Voltage Rating
|
Lithium battery assembly with flying lead and plug; capacity is given by the controller battery-life table, not a fixed mAh rating |
Battery life is not a fixed number: it is estimated from the controller's battery-life table, which accounts for the time the rack spends de-energised. When the controller raises a battery warning, the remaining window is short - the estimator in the controller manual gives the expected life after the warning, and that is the period to arrange the swap within.
Replacement practice: power down, or replace with the rack energised only if the procedure allows it; the assembly seats in a compartment with the red lead to the positive terminal, and the install date is written on the label inside the compartment. That label is the only reliable service record on these racks - without it, battery age is a guess and a mid-shutdown failure is the consequence.
How to tell which battery a rack needs before opening it: the controller's series is on the label, and the battery compartment physically differs between the two assemblies - a BA2 plug will not seat where a BA1 is expected. Reading the label beats ordering both and returning one, and on a mixed plant it is worth writing the series on the maintenance schedule next to the battery change date.
Storage and handling: 0.59 g of lithium per assembly, hazardous-location rules apply to connecting or disconnecting the lead while energised (an arc can occur), and cells should be stored cool and dry - around 25 °C at 40...60% RH - with transport excursions limited to 30 days at -45...+85 °C. The controller's temperature range is 0...60 °C, which is the ambient the battery actually lives in.
We Could Supply Full Range Of PLC Module.
If you find the PLC Module part that you are looking for, pls Skype / Email us for a quote.
There is no Rockwell Automation replacement catalog number, so the practical route is one of three: keep a stock of 1756-BA1 assemblies sized to the number of Series A racks still in service; consolidate those racks onto Series B controllers that use 1756-BA2; or accept that the date/time and retentive data are no longer guaranteed across a long power-down.
Stocking note: a shelf full of BA1 assemblies is not a battery strategy, because cells age whether or not they are installed. Size the stock to one change per rack per life interval plus one spare, record install dates, and replace on the controller's warning rather than on a calendar someone remembers - the warning exists precisely because the life estimate depends on how the rack is actually used.
The distinction between 1756-BA1 and the 1756-BATM battery module matters when tracing a fault: BATM is a chassis-mounted module for 1756-L55M controllers and uses 1756-BATA as its replacement assembly, while BA1 sits inside the L6x controller. A site that orders the wrong one gets a part that fits nothing in the panel.
Lifecycle status and compatibility are from the product's published lifecycle notice and description; lithium content and installation practice from publications 1756-IN033 and 1756-UM001; the mining certification restriction from the ControlLogix controller technical data, 1756-TD001.
Same-family catalog numbers: 1756-BA2, 1756-BATA, 1756-BATM. Each of those catalogue numbers has its own stock page on this store; this page covers what differs in the 1756 family.
ControlLogix controllers, chassis, power supplies and batteries are listed on our category page. Spare batteries: sales@plc-vip.com.